5
Low Voltage Warning
Low Voltage
3.2V
5. Data Report
Data report configuration and sending period are as following:
Min. Interval
(Unit:second)
Max. Interval
(Unit:second)
Reportable Change
Current Change≥
Reportable Change
Current Change
<
Reportable Change
Any number between
1~65535
Any number between
1~65535
Can not be 0.
Report
per Min. Interval
Report
per Max. Interval
The device will immediately send a version package Report and a report data with leak detection status and voltage value.
The device sends data in the default configuration before any configuration is done.
Default setting:
Max Time: 60min
Min Time: 60min ( by default, the current voltage value is detected every Min Interval )
Battery Voltage Change: 0x01 (0.1V)
Note:
The data sending cycle will be programmed before shipment.
The interval between two reports must be the minimum time
Water leak detection:
When the leak sensor is immersed in water, it will immediately issue a report, leaking status:1.
When the leak sensor is out of the immersion state, a report is issued immediately, with no water leakage status: 0.
The data can be decoded by the Netvox LoRaWAN Application Command document and