6
Example of ConfigureCmd
FPort
:
0x07
Bytes
1
1
Var(Fix =9 Bytes)
CmdID
DeviceType
NetvoxPayLoadData
CmdID
– 1 byte
DeviceType
– 1 byte – Device Type of Device
NetvoxPayLoadData
– var bytes (Max=9bytes)
Description
Device
Cmd
ID
Device
Type
NetvoxPayLoadData
Config
ReportReq
R718N360
0x01
0xCA
MinTime
(2bytes, Unit: s)
MaxTime
(2bytes, Unit: s)
RawDataChange
(4bytes)
Reserved
(1byte, Fixed 0x00)
Config
ReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes, Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved (9Bytes, Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes, Unit: s)
MaxTime
(2bytes, Unit: s)
RawDataChange
(4bytes)
Reserved
(1bytes, Fixed 0x00)
(1)
Configure device parameters MinTime = 1min, MaxTime = 1min, CurrentChange = 100mA
Downlink: 01CA003C003C0000006400
The device returns:
81CA000000000000000000 (Configuration successful)
81CA010000000000000000 (Configuration fail)
(2)
Read device configuration parameters
Downlink: 02CA000000000000000000
The device returns:
82CA003C003C0000006400 (current device parameters)
Example for MinTime/MaxTime logic:
Example#1
based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime MaxTime
Sleeping(MinTime)
Sleeping(MinTime)
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange
value.
Wake up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.6V