5. Data Report
Data report configuration and sending period are as following:
5.1 Example of ReportDataCmd
FPort
:
0x06
Bytes
1
1
1
Var(Fix=8 Bytes)
Version
DeviceType
ReportType
NetvoxPayLoadData
Version
– 1 byte –0x01
——
the Version of NetvoxLoRaWAN Application Command Version
DeviceType
– 1 byte – Device Type of Device
The devicetype is listed in Netvox LoRaWAN Application Devicetype doc
ReportType
– 1 byte –the presentation of the NetvoxPayLoadData
,
according the devicetype
NetvoxPayLoadData
– Fixed bytes (Fixed =8bytes)
Min Interval
(Unit:second)
Max Interval
(Unit:second)
Reportable Change
Current Change≥
Reportable Change
Current Change
<
Reportable Change
Any number between
1~65535
Any number between
1~65535
Can not be 0.
Report
per Min Interval
Report
per Max Interval
The device will immediately send a version packet report along with an uplink packet including temperature, humidity and
battery voltage.
The device sends data in the default configuration before any configuration is done.
Default setting:
Max Interval: 0x0384 (900s)
Min Interval: 0x0384 (900s)
Battery Change: 0x01 (0.1V)
Temperature Change:0x0064 (1°C)
Humidity Change:0x0064 (1%)
Note:
The device report interval will be programmed based on the default firmware which may vary.
The interval between two reports must be the minimum time.
Please refer Netvox
LoRaWAN Application Command document
and
Netvox Lora Command Resolver