5
5. Data Report
Data report configuration and sending period are as following:
Min Interval
(Unit: second)
Max Interval
(Unit: second)
Reportable Change
Current Change
≥
Reportable Change
Current Change
<
Reportable Change
Any number between
1~65535
Any number between
1~65535
Can not be 0.
Report
per Min Interval
Report
per Max Interval
The device will immediately send a version packet report and two attribute data reports.
Data will be reported by default setting before any configuration.
Default setting:
Max Interval: 3600s
Min Interval: 3600s (The current voltage is detected every Min Interval by default.)
Battery Voltage Change: 0x01 (0.1V)
Acceleration Change: 0x03 (m/s²)
R311FA1
Three-axis acceleration and velocity: s:
1.
After the three-axis acceleration of the device
exceeds ActiveThreshold
, a report is sent immediately to report the three-
axis acceleration and velocity.
2.
After reporting, the three-axis acceleration of the device needs to be
lower than InActiveThreshold
, and the duration is
greater than
5s
(cannot be modified). Then, the next detection will start. If the vibration continues during this process after
the report is sent, the timing will restart.
3.
The device sends two data packets, one is the acceleration of the three axes, and the other is the velocity of the three axes.
The interval between the two packets is 10s.
Note:
(1) The device report interval will be programmed based on the default firmware.
(2) The interval between two reports must be the minimum time.
The reported data is decoded by the Netvox LoRaWAN Application Command document and