NetUP Streamer 16xC. User manual
6
Environment requirement
Item
Requirement
Room space
When installing a rack in the room, make sure the distance between two
rows of racks is 1.2~1.5m and the distance to the wall is at least 0.8m.
Room floor
Electric isolation. Dust free
. The v
olume resistivity of ground anti-static
material: 1×107~1×1010
Ω
. Grounding current limiting resistance: 1M (Floor
bearing should be greater than 450Kg/m
2
).
Environment
temperature
5~40
℃
(sustainable),
0~45
℃
(short time).
I
nstalling air-conditioning is recommended.
Relative temperature
20%~80% (sustainable); 10%~90% (short time)
.
Pressure
86~105KPa
Door & window
Install rubber strip for sealing door
-gaps and dual level glasses for windows
Walls
Can
be covered with wallpaper or dark paint
.
Fire
protection
Fire alarm system and extinguisher
.
Power
The
device requires
AC 100V
-
220V±10%, 50/60Hz
.
Please carefully check before running
.
Grounding requirement
•
Connect the ground wire to the grounding hardware on the device. Ground resistance should be
no more than 1
Ω
Grounding is essential for device’s functionality, surge and electronic interference
protection
•
K
eep proper contact with the metal housing of the device
•
G
rounding wire must be made out of copper and as thick and short as possible
•
Make sure the two ends of grounding wire conduct electricity and are not rusty
•
It is prohibited to use any other devices as a part of groundi
ng electric circuit
•
All racks
should be connected with
a protective copper strip. G
round loops should be avoided
•
Grounding wire’
s contact area with the rack should be no less than 25mm
2