APPENDIX 2
–
EVINOX INTEGRATION
SETTING UP EVINOX CHANNELS (only available when a supported Evinox HIU is connected)
•
The Energy Manager Controller is connected to
the Evinox HIU via an RS485 connection. Ensure
the appropriate cable connections are made
before continuing with setting up channels.
An Evinox HIU can be connected to a NetThings Energy Manager and provide meter readings for five distinct
meters:
Heating (Combi boiler)
Electricity
Cooling
Water Meter 1
Water Meter 2
The Evinox HIU informs the energy manager which of these five meters are enabled.
•
Once connections to the Evinox HIU are established, a configuration menu option will be available, providing
the following conditions are met.
PORT 2
✓
A properly configured and powered Evinox HIU is
correctly cabled to the Energy Manager.
✓
The Evinox HIU reports a least one meter as
available.
✓
No M-Bus meters have been configured. If an M-Bus
meter has been configured prior to connecting with
an Evinox HIU, the Evinox Configuration button will
never appear.
NOTE
- Likewise, after an Evinox HIU
has been cabled to the Energy Manager, M-Bus
configuration is no longer possible. The M-Bus
configuration button will never appear.
•
Enter the Evinox Channel configuration by pressing
Evinox Configuration.
The channel assignment page will
be displayed. Available meters will be shown.
•
To assign a meter to a channel, turn the switch to the
ON
position.
•
To unassign a meter to a channel, turn the switch to
the
OFF
position.
•
Click
Save Evinox Configuration
once you are finished
assigning and unassigning meters.
•
If the operation succeeded, the green banner stating
"Configuration Saved" will briefly display on top of
the screen, and the Assigned Channel column will
display the channel selected for the Evinox meter.
•
The configuration application attempts to assign
Evinox meters to the first disabled pulse channel. If
there are not enough pulse channels, an error banner
is displayed, and the switches are reset.
•
Click on the settings cog to return to the main menu.