APPENDIX 2 

EVINOX INTEGRATION

SETTING UP EVINOX CHANNELS (only available when a supported Evinox HIU is connected)

The Energy Manager Controller is connected to 
the Evinox HIU via an RS485 connection. Ensure 
the appropriate cable connections are made 
before continuing with setting up channels.

An Evinox HIU can be connected to a NetThings Energy Manager and provide meter readings for five distinct 
meters:

Heating (Combi boiler)
Electricity
Cooling
Water Meter 1
Water Meter 2

The Evinox HIU informs the energy manager which of these five meters are enabled.

Once connections to the Evinox HIU are established, a configuration menu option will be available, providing 
the following conditions are met.

PORT 2

A properly configured and powered Evinox HIU is 
correctly cabled to the Energy Manager.

The Evinox HIU reports a least one meter as 
available.

No M-Bus meters have been configured.  If an M-Bus 
meter has been configured prior to connecting with 
an Evinox HIU, the Evinox Configuration button will 
never appear. 

NOTE

- Likewise, after an Evinox HIU 

has been cabled to the Energy Manager, M-Bus 
configuration is no longer possible.  The M-Bus 
configuration button will never appear.

Enter the Evinox Channel configuration by pressing 

Evinox Configuration.

The channel assignment page will 

be displayed. Available meters will be shown.

To assign a meter to a channel, turn the switch to the 

ON

position.   

To unassign a meter to a channel, turn the switch to 
the 

OFF

position.

Click 

Save Evinox Configuration

once you are finished 

assigning and unassigning meters.

If the operation succeeded, the green banner stating 
"Configuration Saved" will briefly display on top of 
the screen, and the Assigned Channel column will 
display the channel selected for the Evinox meter.

The configuration application attempts to assign 
Evinox meters to the first disabled pulse channel. If 
there are not enough pulse channels, an error banner 
is displayed, and the switches are reset.

Click on the settings cog to return to the main menu.

Содержание EMK-001 Series

Страница 1: ...ENERGY MANAGER INSTALLATION USER GUIDE NetThings Ltd 14 New Mart Road Edinburgh EH14 1RL UK E info netthings co uk T 44 0 131 331 5445 Document 200SM075 Version 2 0 ...

Страница 2: ...ION OVERVIEW 3 INSTALLATION CONNECTIONS 4 COMMISSIONING THE ENERGY MANAGER 5 USING THE ENERGY MANAGER 8 ADDITIONAL INFORMATION 10 SPECIFICATION 12 APPENDIX 1 M BUS INSTALLATION 13 APPENDIX 2 EVINOX INTEGRATION 15 ...

Страница 3: ...he services you require to be monitored then run cabling between these positions during your first fix installation 3 Fix the Energy Manager and Display in their final positions and make power supply connections Make connections to the service you require to be monitored Note Additional equipment may be required to connect to other manufacturer s products Please contact NetThings if in doubt Pair ...

Страница 4: ... appropriate pulse block As there are several different types please ensure that the correct pulse block is ordered The Display and the Controller need to be within 5m of each other otherwise the WIFI communication may be unreliable The Energy Manager Controller is typically mounted in a recessed 2 gang pattress box however should the Controller be mounted in a surface box or directly to the wall ...

Страница 5: ...plied with the Controller The SSID and password to pair Controller and Display can found within the packaging and also on a label on the top of the controller Select the correct Energy Manager WIFI from the list displayed to pair the display The SSID will start with NT_ Enter the password for the chosen Controller Check the signal strength and press ASSOCIATE WIFI CONNECTION Alternative Method The...

Страница 6: ...er to identify what is connected The Pulse Value field should be set to the corresponding value of the energy source that you are connecting to This value may be indicated on the connected energy source Press Save Channel Configuration before exiting and use setup button in the top right hand corner to return to the Configuration Menu SETTING UP PULSE INPUT CHANNELS CONFIGURATION Following a succe...

Страница 7: ...correctly on the home display Typical example of an Electricity Connection Once all the channels have been verified press the setup menu icon to enter the Configuration menu and then press Overview Press Activate this Configuration if the Overview is correct IMPORTANT Once the system is fully commissioned and ready to be handed over the yellow warning banner should be removed by changing the banne...

Страница 8: ...view our latest product range To return to the home screen at any point press the Home icon on the top left hand side of the display Channels that have been enabled during the commissioning process will now be visible Press the icon relating to the utility that you wish to monitor in order to see further information about your energy usage Channel number description and icon This section of the di...

Страница 9: ...will not want to connect to the Energy Manager by default Windows 10 Example of available WIFI Please Note The procedure below is based on a Windows10 connection Other platforms will follow a similar process Enter the password that is found on the label on the Controller Your device will now connect to the Netthings Controller Open your web browser and enter 172 16 0 254 This Energy Manger should ...

Страница 10: ... DATA ERASE Deletes viewable data Aggregate Config Data is preserved Allows WPS connection to the display or your device Allows Wi Fi channel changing from Channel1 to 6 or 11 Hold O button for 7 seconds Hold button for 3 seconds Hold button for 5 seconds NETWORK CONNECTIONS You do not need to have your home Wi Fi connected to the Energy Manager system in order for it to function The system broadc...

Страница 11: ... generated by a transistor logic TTL output should have their polarity observed and maintained Meters with mechanical pulse outputs are not polarity dependant Breaks in the interconnecting cables from meters to Energy Manager Installing cables exceeding the distance specified in IEC 62053 31 100meters Installing incorrect pulse cable type Belden 9501 or similar is recommended Incorrectly connectin...

Страница 12: ...rage Capacity Internal memory allowing storage for 10 years External microSD card slot for downloading data Power supply for display 5 8W Switching Power Supply I P 100 240VAC unterminated wire for spur connection O P DC 5V USB or barrel connector Dimensions 73mm x 30mm x 23 5mm Power supply for display 7 12W Switching Power Supply I P 100 240VAC unterminated wire for spur connection O P DC 5V bar...

Страница 13: ... The scan results will show all meters that been discovered however a maximum of 3 will have a channel assigned When starting from an empty list the order in which meters are found and allocated channels is dependant on the sequence in which the devices communicate to the Energy Manager On subsequent refreshes if the meters found are the same serial number and model then the order is preserved The...

Страница 14: ...rect and match up with the expected records to be read and their associated units Name This field can be changed by the installer to further identify the connected service Record This is the M Bus record that is being read on the connected meter It can be changed if it is incorrect or another record is required Type This is the type of connection being monitored for example Heat Cooling Water This...

Страница 15: ...meter has been configured prior to connecting with an Evinox HIU the Evinox Configuration button will never appear NOTE Likewise after an Evinox HIU has been cabled to the Energy Manager M Bus configuration is no longer possible The M Bus configuration button will never appear Enter the Evinox Channel configuration by pressing Evinox Configuration The channel assignment page will be displayed Avai...

Страница 16: ... manner from the channel configuration screen if desired otherwise there is no need for any further configuration SETTING UP EVINOX CHANNELS continued Click on Channels Configuration to view channels and select channels as required For Evinox assigned channels the name can be changed or the channel can be disabled but there are no other actions that can be performed from this screen Click on Save ...

Страница 17: ...THIS PAGE IS INTENTIONALLY BLANK ...

Страница 18: ...THIS PAGE IS INTENTIONALLY BLANK ...

Страница 19: ...THIS PAGE IS INTENTIONALLY BLANK ...

Страница 20: ...NetThings Ltd 14 New Mart Road Edinburgh EH14 1RL UK E info netthings co uk T 44 0 131 331 5445 ...

Отзывы: