[ENG] NetPing Input+Relay R404, User guide -[ENG] 7. [DKST 57]Connection of external sensors and actuators.
[ENG] 7. [DKST 57]Connection of external sensors and actuators.
–
Important! Sensors of the "dry contact" type: 220V presence sensor, leakage sensor and others are
connected to the INPUT lines of the device. You can connect any 16 sensors from this set.
The sensor comes with a non-detachable cable with lugs at the ends.
The cable length can be increased by
using
, which are connected in series into each other, or independently using any wire with a
cable section of at least 0.4 mm2. The maximum permissible loop length is 100 meters.
The motion sensor is connected with a four-wire line in accordance with the table:
Colored wire
Flat wire
Terminal
Green
Marked (red) wire
IN1 ... IN16
White
The first wire after the marked
GND
Black
The second wire after the marked
GND
Red
Third wire after marked
+12V
Important! Sensors of the "dry contact" type: 220V presence sensor, leakage sensor and others are
connected to the INPUT lines of the device. You can connect any 16 sensors from this set.
The sensor comes with a non-detachable cable with lugs at the ends.
The cable length can be increased by
using
, which are connected in series into each other, or independently using any wire with a
cable section of at least 0.4 mm2. The maximum permissible loop length is 100 meters.
is limited only by the number of free OUT and RELAYS lines.
When connecting the outlet to the device, all wires are involved, except for the brown (white) one. When the state is
"log. 0 "on the OUT line at the socket there will be 220 V - the load will be turned on. When the state is "log. 1 ”on the
OUT line, the socket will be de-energized, the load will be disconnected.
OUT line control:
Colored wire
Terminal
Red
+5V
Black
GND
Blue (green)
One of the OUT lines - 1 - 4 (in the "output" mode, log. 1)
RELAYS control (NO - normally open contact, NC - normally closed contact):
Important!
The brown (white) wire is not used and must remain unconnected!