Net Safety Monitoring
MAN-0101 Rev 01 UVIRS-H2-A/H2-AR & UVIRS-H2-A-X/H2-AR-X
15
November 23, 2012
D
ETECTOR
F
UNCTIONALITY
D
ETECTOR
W
INDOW
/L
ENS
Figure 7: Detector Viewing Windows (Non-heater version shown)
Note: An optional heater is available to eliminate condensation on the
glass window/lens.
S
TART
U
P
P
ROCEDURE
Once powered up, the UV/IRS-H2 will begin a 90 second start up routine.
During this time, the current output will be 3 mA. The UV and IR source
lights and the Green power LED will be on for the 90 seconds. Once the start
up procedure has finished, and no faults are present, the detector will begin
normal operation (current output 4 mA and Green LED will remain on).
System Check
Once powered up, the system should be checked. Refer to the section entitled
"Manual Check Procedure
" for instructions.
WARNING:
When testing the system, ensure all external equipment is
disabled to prevent unwanted alarm activation. Enable external equipment
once testing is completed.
M
ONITOR
The Detector’s status can be determined by monitoring the current loop
and/or the condition LEDs.
Condition Status
—LEDs
There are three (3) LEDs used to indicate the status of the detector (refer to
Table 5: Status LEDs and Current Output).