Net Safety Monitoring Inc
MLP-A/AR/AD-ST1400-25
11
RTU Registers
Register 40001 = % output (read only)
Register 40002 = RTU Status (read only)
Register 40101 = Reset latched relays (write)
Calibration Button
The Calibration Button provides access to the Millennium’s Main Menu, which
in turn allows calibration and options to be reviewed and set. Refer to Figure 12,
"Controller Functionality", on page 10 for more information.
•
Press and hold
the Calibration Button to Calibrate and access Main Menu.
•
Briefly press
to make a selection (select
YES?
).
WARNING:
Opening the Controller’s Housing should be avoided when the
presence of gas is possible (when in a hazardous environment). Do
not power up the system, with the Housing removed, unless the area
has been de-classified.
Table 2:
Status LEDs, Display Messages and Current Loop
Status LED
State
Current O/P
RED or GREEN
Display
Options
Review/Settings
3.0 mA
n/a
n/a
Standard level of
Oxygen present
17.4 mA
Blip/
blink
20.9 %O2
Start-up delay (90 sec) 3.0 mA
Slow
flash
Start Delay
Access Main Menu
3.0 mA
n/a
Switch On
10-0
Memory Error (contact
factory)
2.5 mA
Slow
flash
Memory Error
Black or Red Sensor
lead open
2.5 mA
Slow
flash
Sensor Fault
Auto zero set
3.0 mA
Solid
Apply Clean
Air
Apply calibration gas
3.3 mA
Fast
flash
Apply 20.9%
O2
Span is set, remove
gas
3.6 mA
Solid
Remove gas
Low alarm set point
-
Flash
XX Low Alarm
High alarm set point
-
Flash
XX High Alarm
Non-standard levels of
Oxygen present
>17.4 mA or
<17.4 mA
Blip/
blink
% O2
shown left
side display
Calibration procedure
failed/Sensor failed
3.0 / 3.3 mA
Flash
Flash
Fail Cal
Over 25% Range
20 mA
Solid
<25%O2
Table 3:
RTU Status Register (40002) Read Only (Binary)
RTUstat_fault
0x0001
(fault sensor...)
RTUstat_low_alarm
0x0002
low alarm tripped
RTUstat_high_alarm
0x0004
high alarm tripped
RTUstat_low_alarm_latched
0x0008
low alarm latched
RTUstat_high_alarm_latched
0x0010
high alarm latched
RTUstat_powerUp
0x0080
power up delay
RTUstat_cal_cycle
0x0100
calibration cycle in progress
RTUstat_zeroing
0x0200
RTUstat_apply_span_gas
0x0400
RTUstat_calibrating
0x0800
RTUstat_remove_gas
0x1000
RTUstat_cal_complete
0x2000
RTUstat_mem_error
0x4000
memory error