
Page 4
Setting the Data Bus Address and Enrolling Device(s) into the System
All devices that operate on the RS-485 4-wire data bus must have a unique address setting from 1 to 16 within their device TYPE.
Keypads and Access Modules are device TYPE 1, input (zone) expanders TYPE 2, output expanders TYPE 3, etc. The purpose of device
types is so that the address numbers can be re-used in each different device type. It is OK to have a Keypad, a Zone Expander, and a
Output Expander all set to address 2 and on the same data bus since each device is a different device type.
It is NOT OK to have
duplications of addresses within the same device type. I.E. Multiple keypads on the same control cannot be set to 'like' addresses.
Setting the Data Bus Address of the M1KAM Access Module:
The address setting is very important because it establishes the Zone
ID of the Door Status Input AND the Output ID of the on-board relay that is used to operate the locking device. Refer to Table 1 below.
Since the Access Module is the same device "type" as a Keypad, its bus address must be unique among any of the possible 16 keypad
addresses. If more than 1 Keypad or Access Module is installed, each one MUST be set to a unique address (2, 3, etc). The maxi-
mum number of keypad addresses is 16.
Duplicate addresses MUST NOT EXIST. I.E. Multiple keypads and/or Access Modules must
each have a unique address.
1. There are 4 white switches located in the top right hand corner of the M1KAM board. Each switch has a position of OFF or ON
(binary value 0 or 1) and a decimal equivalent value of (1, 2, 4, or 8). The total decimal value of the "ON" switches equates to the data
bus address.
2. Proceed to the ENROLLING process to make the Access Module operational.
Switch Settings
Input ID Output ID
S1
S2
S3
S4
(Zone)
(Relay)
ON Off Off Off
193
193
Off ON Off Off
194
194
ON ON Off Off
195
195
Off Off ON Off
196
196
ON Off ON Off
197
197
Off ON ON Off
198
198
ON ON ON Off
199
199
Off Off Off ON
200
200
ON Off Off ON
201
201
Off ON Off ON
202
202
ON ON Off ON
203
203
Off Off ON ON
204
204
ON Off ON ON
205
205
Off ON ON ON
206
206
ON ON ON ON
207
207
Off Off Off Off
208
208
Data Bus
Address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Table 1: Data Bus Address Switches
The Zone Input and Relay Output ID is determined by
the Data Bus Address setting.
Jumper Settings for RTE (Request to Exit) &
DHO (Door Held Open) Times
NOTE: Jumper JP1 located in the middle left
side of the board is used to engage a 120
Ohm resistor for terminating the M1 Data
Bus. Please see Data bus wiring
instructions before using this jumper.
Other Jumper Settings
S2 S1
Door Time
S2 S1
Door Time
S2 S1
Door Time
S2 S1
Door Time
These two jumpers select the time values
assigned to Request to Exit (RTE) and
Door Hold Open (DHO) functionality.
00 > RTE Time = 10 Seconds
DHO Time = 20 Seconds
10 > RTE Time = 20 Seconds
DHO Time = 40 Seconds
01 > RTE Time = 30 Seconds
DHO Time = 60 Seconds
11 > RTE Time = 45 Seconds
DHO Time = 90 Seconds
Enrolling the M1KAM with the control:
Once the address is set and the M1KAM powered up it will be necessary to manually ENROLL
the new device so that the M1 Control knows it is present. This is accomplished either from keypad programming "Menu 1 - Bus
Module Enrollement" or from the NessRP Remote Programming Software. Proceed to the ENROLLING process to enroll the device
and make it operational.
(This step requires an LCD Keypad or the ElkRP software)
1.
Press the ELK key, then press 9 (or scroll up) to display 9 - Installation Programming. Press the
RIGHT arrow key to select this menu. The Installer Program Code (PIN) must be entered to access
this menu.
2.
Enter the Installer Program Code. (See M1 Manual for the default Code)
3.
The first Installer Programming menu displayed will be "Bus Module Enrollment"
4.
Press the RIGHT arrow key to select this menu. "Enrolling Bus Modules" will display
5.
The M1 will transmit an enrollment message to all data bus devices, following by a display showing the
total Bus Modules that are enrolled. To view the enrolled devices and/or remove a device press the
RIGHT arrow key to select Edit mode.
6.
Press the * or Exit keys to exit Installer Programming.
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
Auth. Required
Enter Valid Pin
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
01-Bus Module
Enrollment
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
12345678901234567890123456
XX Bus Modules
Enrolled, Edit
r
Jumper Settings for RTE and DHO Time Values
The M1KAM has four possible jumper settings that adjusts the amount of time on the Request To Exit (RTE) and Door Held Open
(DHO) features. The time values for RTE and DHO are adjusted together. See Table 1 for the time adjustments.
Request To Exit (RTE) refers to the amount of time that the Door Lock will remain Unlocked by the action of the RTE device.
Door Held Open (DHO) refers to the amount of "Delay" time the door status may remain open before the
Out1 Alrm
output becomes
active. The timer starts upon a valid access, when a RTE occurs, and/or when the
IN2DR
input (door status) is tripped. The
Out1
Alrm
can be connected to activate a relay or a low current sounder device as a local alert. The output stays on until the door is
physically restored to a closed/secure state.
Содержание M1KAM
Страница 3: ...Page 3 ...