Neptronic TRO24-EXT1 Скачать руководство пользователя страница 12

 

VAV Thermostat Controller 

Specification and Installation Instructions 

 

www.neptronic.com

 

 

Page | 12

 

Air Flow Program Mode (Operation Mode) 

This menu is accessible through normal operation mode. 

1.  The Mode Selector DIP switch (DS1) must be set to the “OFF” position (Operation Mode). Refer to Wiring on page 2.  

2.  Press the

 and

ºF / º C

 keys for 5 seconds. The 

“Enter Password”

 screen appears. 

3.  Enter the password (

637

) within 1 minute. Use

 

the   and  arrow keys to increase or decrease the value and the 

 

 

buttons to toggle between the digits. If

 

you enter the wrong password, the thermostat displays “

Eror

” and returns to Operation 

Mode.  

4.  Use the same menu operations as described in Programming Mode on page 3. 

 

The thermostat will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not 

press any key for 5 minutes. The changed values will be saved automatically. 

53.

 

“Inside Temp Sensor Offset” 

 

 

Range:   

Offset: 

Increment: 

-30 to 90ºC  [-22 to 194ºF]  

Max ± 5ºC    

0.1ºC      [0.2ºF] 

Compare the displayed temperature reading with a known value from a thermometer. To offset or calibrate the sensor, use the 

arrows key to set the desired temperature reading. This is useful for thermostats installed in areas where the temperature read 

is slightly different than the room’s actual temperature. For example, a thermostat placed right under the air diffuser. 
If the thermostat is set to use an external temperature sensor (EtS at Step 32, 33 or 34 of programming mode on page 9), the 

thermostat displays “OFF”.  

54.

 

“Extern Temper Sensor Offset” 

 

 

Range:   

Offset: 

Increment: 

-30 to 90ºC  [-22 to 194ºF]  

Max  ± 5ºC 

0.1ºC      [0.2ºF] 

This option appears if you’ve set one of the analog inputs to 

EtS

 (External temperature sensor) in Step 32, 33 or 34 of 

programming mode on page 9. When the thermostat is connected to the appropriate analog input (AI1, AI2, or AI3), the display 

shows the temperature read by the external temperature sensor. Adjust the offset by comparing it with a known value (e.g. 

thermometer). If the sensor is not connected or short circuited, the display is blank “Error“.  

55.

 

“Pressure Filter Time in Seconds” 

 

 

Default: 

Range:   

Increment: 

2 seconds 

1 to 10 seconds 

1 second 

This option appears if you have set one of the analog inputs to 

PrSd

 or 

PrSa

 in Step 32, 33, or 34. Set the time in seconds of 

the numeric filter applied to the pressure analog input. The numeric filter stabilizes the reading and slows down the answer of 

the system. 

56.

 

“air flow Intgral time in Seconds” 

 

 

Default: 

Range:   

Increment: 

0 minutes 

0 to 60 minutes 

1 minute 

Set the time in minutes for the integration factor compensation. 

57.

 

“Adjust Airflow KFactor Vnom” 

 

 

Default: 

Range:   

Increment: 

1200 

100 to 9995 

Set the value of the K-Factor or the V nominal according to your pressure sensor selection (

PrSd

 or 

PrSa

 in Step 32, 33 or 34 

or programming mode on page 9). 

 

If Differential Pressure Sensor 

(PrSd)

:  V = k

√∆P when ∆P=1 (10.00V)

 

 

If Velocity Pressure Snesor 

(PrSa)

: V

nom =10.00V

 

58.

 

“Minimum Cooling Airflow” 

 

 

Default: 

Range:   

Increment: 

100 

0 to “maximum cooling airflow” 

Select the desired value of the minimum airflow in cooling. The minimum value is restricted by the maximum value (Step 59). 

Содержание TRO24-EXT1

Страница 1: ...program Selectable proportional control band and dead band TRO24 EXT1 Typical Application VAV applications incorporate a central unit that delivers a controlled volume of air which can be cooled or h...

Страница 2: ...open 7 External 24 Vac for TO1 TO2 if JP2 set to B C 8 TRIAC output 2 TO2 9 TRIAC output 3 TO3 Floating 2 applies to pins 9 11 if set to Flt at step 16 TO3 close TO4 open 10 External 24 Vac for TO3 TO...

Страница 3: ...using wall anchors and screws supplied Make the appropriate connections E Mount the control module on the base and secure using the screw A E D C B Programming Mode The Mode Selector DIP switch DS1 mu...

Страница 4: ...value set as the maximum user point The maximum value is restricted by the minimum value set in Step 2 In other words the value that is set as the maximum cannot be less than the minimum value 4 User...

Страница 5: ...ou selected PULs at Step 8 or OFF at this step go to Step 13 Cooling Ramp 1 Cooling Ramp 2 Heating Ramp 1 Heating Ramp 2 Changeover Ramp Off 10 Set Floating Time in Seconds Default Range Increment 100...

Страница 6: ...ramp TO3 will be used for TO4 TO3 ramp will be set to close and TO4 will be set to open If you select PULs only the Heating 1 and Heating 2 ramps will be available at Step 9 17 Select TO3 Signal Ramp...

Страница 7: ...Hr2 Heating ramp 2 Cr1 Cr2 Hr1 Hr2 COr OFF Select the desired ramp from the available options If you selected PULs at Step 21 only Heating Ramp 1 and Heating Ramp 2 will be available If you selected...

Страница 8: ...minimum value Step 26 In other words the maximum value should not be less than the minimum value 28 Min Pos AO1 Output Percent Default Range Increment 0 0 to 100 5 This option does not appear if the...

Страница 9: ...ure Sensor 10k Differential Pressure Sensor 0 10Vdc PrSd 1 V if P 1 Velocity Pressure Sensor 0 10Vdc PrSa 10V Vnom Night Set Back Contact 33 Select AI2 Input Signal Default Range OFF OFF SENs NoCl NoH...

Страница 10: ...33 or 34 Set the heating setpoint that will be used when the system is Night Set Back Mode The setpoint value is restricted by the Night Setback Cooling Setpnt value Step 39 The moon and heating symb...

Страница 11: ...d 1 Heating Default Range Increment 0 3 C 0 6 F 0 to 5 0 C 0 to 10 F 0 1 C 0 2 F Select the desired dead band value of the heating ramp 1 The heating symbol is also displayed 48 Control Dead Band 2 He...

Страница 12: ...ing mode on page 9 the thermostat displays OFF 54 Extern Temper Sensor Offset Range Offset Increment 30 to 90 C 22 to 194 F Max 5 C 0 1 C 0 2 F This option appears if you ve set one of the analog inpu...

Страница 13: ...action occurs for 30 minutes changed values will be saved and the thermostat will exit the Air Flow Setup menu and return to operation mode 63 Minimum Airflow Range Offset Increment 0 to K Factor or...

Страница 14: ...between C and F press the F C key Setpoint To display the setpoint press the or key twice The setpoint appears for 5 seconds To adjust the setpoint press the arrow keys while the temperature is displa...

Страница 15: ...ation Instructions www neptronic com Page 15 Notes Recycling at end of life please return this product to your Neptronic local distributor for recycling If you need to find the nearest Neptronic autho...

Страница 16: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Отзывы: