VAV Thermostat Controller 

Specification and Installation Instructions 

 

TRO24-EXT1-Ext Setpnt-140922-ESA 

 

Page | 1

 

Model 

TRO24-EXT1 

Extended Setpoint Range  

Description 

The TRO24-EXT1 is a combination controller and thermostat . 

The VAV Thermostat Controller is designed for simple and 

accurate control of any variable air volume box in a number of 

zone control configurations. Its field configurable algorithms 

enable versatile implementation of required control sequences.   

Applications 

  Cooling only with or without terminal reheat 

  Heating/cooling with or without auto-changeover and 

terminal reheat 

  Pressure dependent or pressure independent 

  Single duct or dual duct 

  Serial or parallel fan power boxes (on/off or ECM) 

  Supply and exhaust applications  

  Auxiliary heating sources, such as electric baseboards, can 

also be applied 

Features 

  Backlit LCD with simple icon and text driven menus  

  Configurable inputs and outputs 

  Precise temperature control with programmable PI function 

  Selectable Fahrenheit or Celsius scale 

  Extended setpoint range 

  Manual night set back override 

  Multi level lockable access menu and setpoint 

  Selectable intern

al or external temperature sensor (10 KΩ)

 

  Changeover by contact or external temperature sensor 

  Pressure sensor input with air flow program 

  Selectable proportional control band and dead band 

 

  

 

 

 

 

 

TRO24-EXT1 

Typical Application 

VAV applications incorporate a central unit that delivers a 

controlled volume of air, which can be cooled or heated, to 

multiple zones. Each zone incorporates a VAV control box with 

a motorized damper to adjust the flow of air to the controlled 

zone based on the demand. Some configurations include one or 

more of the following: air flow pressure sensor, fan, duct heater, 

duct temperature sensor, and auxiliary heat (e.g. baseboard).  

 

 

 

* Consult www.neptronic.com for details on these Neptronic products. 

Technical Specifications 

Description 

TRO24-EXT1 

Inputs 

3 Universal analog inputs: 0-10Vdc, Thermistor (10k Type 3), or digital input (dry contact) 

Available for sensors: external temperature, changeover, night set back or pressure 

Outputs

 

2 Analog outputs: 0-10Vdc or 2-10Vdc selectable (2mA max.) 

4 TRIAC outputs: on/off, pulse 0 or 24Vac (250 mA max.), or 2 floating outputs 

Power supply 

22 to 26Vac 50/60Hz 

Power consumption 

1VA 

Setpoint range 

-30ºC to 90ºC [-22ºF to 194ºF] with external sensor 

External sensor range  

-40ºC to 100ºC [-40ºF to 212ºF] 

Control accuracy 

Temperature: ±0.4ºC [0.8ºF] 

Proportional band 

0.5ºC to 5ºC [1ºF to 10ºF] adjustable 

Electrical connection 

0.8 mm

[18 AWG] minimum 

Operating temperature 

0ºC to 50ºC [32ºF to 122ºF] 

Storage temperature 

-30ºC to 50ºC [-22ºF to 122ºF] 

Relative Humidity 

5 to 95% non condensing 

Degree of protection of housing 

IP 30 (EN 60529) 

Weight 

160 g. [0.36 lb] 

Содержание TRO24-EXT1

Страница 1: ...program Selectable proportional control band and dead band TRO24 EXT1 Typical Application VAV applications incorporate a central unit that delivers a controlled volume of air which can be cooled or h...

Страница 2: ...open 7 External 24 Vac for TO1 TO2 if JP2 set to B C 8 TRIAC output 2 TO2 9 TRIAC output 3 TO3 Floating 2 applies to pins 9 11 if set to Flt at step 16 TO3 close TO4 open 10 External 24 Vac for TO3 TO...

Страница 3: ...using wall anchors and screws supplied Make the appropriate connections E Mount the control module on the base and secure using the screw A E D C B Programming Mode The Mode Selector DIP switch DS1 mu...

Страница 4: ...value set as the maximum user point The maximum value is restricted by the minimum value set in Step 2 In other words the value that is set as the maximum cannot be less than the minimum value 4 User...

Страница 5: ...ou selected PULs at Step 8 or OFF at this step go to Step 13 Cooling Ramp 1 Cooling Ramp 2 Heating Ramp 1 Heating Ramp 2 Changeover Ramp Off 10 Set Floating Time in Seconds Default Range Increment 100...

Страница 6: ...ramp TO3 will be used for TO4 TO3 ramp will be set to close and TO4 will be set to open If you select PULs only the Heating 1 and Heating 2 ramps will be available at Step 9 17 Select TO3 Signal Ramp...

Страница 7: ...Hr2 Heating ramp 2 Cr1 Cr2 Hr1 Hr2 COr OFF Select the desired ramp from the available options If you selected PULs at Step 21 only Heating Ramp 1 and Heating Ramp 2 will be available If you selected...

Страница 8: ...minimum value Step 26 In other words the maximum value should not be less than the minimum value 28 Min Pos AO1 Output Percent Default Range Increment 0 0 to 100 5 This option does not appear if the...

Страница 9: ...ure Sensor 10k Differential Pressure Sensor 0 10Vdc PrSd 1 V if P 1 Velocity Pressure Sensor 0 10Vdc PrSa 10V Vnom Night Set Back Contact 33 Select AI2 Input Signal Default Range OFF OFF SENs NoCl NoH...

Страница 10: ...33 or 34 Set the heating setpoint that will be used when the system is Night Set Back Mode The setpoint value is restricted by the Night Setback Cooling Setpnt value Step 39 The moon and heating symb...

Страница 11: ...d 1 Heating Default Range Increment 0 3 C 0 6 F 0 to 5 0 C 0 to 10 F 0 1 C 0 2 F Select the desired dead band value of the heating ramp 1 The heating symbol is also displayed 48 Control Dead Band 2 He...

Страница 12: ...ing mode on page 9 the thermostat displays OFF 54 Extern Temper Sensor Offset Range Offset Increment 30 to 90 C 22 to 194 F Max 5 C 0 1 C 0 2 F This option appears if you ve set one of the analog inpu...

Страница 13: ...action occurs for 30 minutes changed values will be saved and the thermostat will exit the Air Flow Setup menu and return to operation mode 63 Minimum Airflow Range Offset Increment 0 to K Factor or...

Страница 14: ...between C and F press the F C key Setpoint To display the setpoint press the or key twice The setpoint appears for 5 seconds To adjust the setpoint press the arrow keys while the temperature is displa...

Страница 15: ...ation Instructions www neptronic com Page 15 Notes Recycling at end of life please return this product to your Neptronic local distributor for recycling If you need to find the nearest Neptronic autho...

Страница 16: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Отзывы: