Specification & Installation Instructions

 

 

Mounting Instructions 

CAUTION: Risk of malfunction. Remove power prior to separate thermostat cover from its base. 
A.  Remove the screw (captive) holding the base and the front cover of the thermostat. 
B.  Lift the front cover of the thermostat to separate it from the base. 
C.  Pull wire through the base hole. 
D.  Secure the base to the wall using wall anchors and screws (supplied). Make the appropriate connections. 
E.  Mount the control module on the base and secure using the screw.

 

 

Terminal Descriptions 

Terminals TMA54-EXT1 

1

Common 

2

24 Vac 

3

Exterior temperature sensor 

4

Night set back input* 

5

Heating 1

st

 ramp 

6

Heating 2

nd

 ramp

 

7

Cooling 1

st

 ramp 

8

Cooling 2

nd

 ramp  

9

TPM (time proportional modulation) 

* For a replacement in an existing night set back (NSB) loop with thermostat PTA, the NSB input, terminal #4, of the TMA should be 
isolated for a good performance. 
 

 For controlling an electric heater with a modulating signal (0-10Vdc), use terminal 6 (Heating 2

nd

 ramp)

 

 

Settings on PC Board 

Mode Selection 

 

Jumper (JP1) on RUN: 

Thermostat is in 

Operation mode

Thermostat must be set in this mode to operate 
properly. 
If not locked, set point and control mode (Heating & 
Cooling ON, Cooling only ON or Heating only ON) 
may be modified by the end user. 

 

Jumper (JP1) on PGM:

 

Thermostat is set in 

Programming mode

Refer to the following section more details 

 

Programming Mode 

When in this mode this symbol 

 is displayed. Please press on 

button to advance to the next program function and press on 

 or 

 

to change value. You can exit programming mode at any time, changed values will be recorded.

 

Step Display 

Description 

Values 

 

Internal temperature sensor Calibration: 

Display switches between “

tS1

” and temperature read by internal 

temperature sensor. 
You can adjust the calibration of the sensor by comparison with a known 
thermometer. For example if thermostat has been installed in an area where 
temperature is slightly different than the room typical temperature 
(thermostat place right under the air diffuser). 

 

Range : 10 to 35ºC [50 to 95ºF] 
Increment:1ºC [1ºF]  
 

NOTE: This thermostat has been 
calibrated at factory 

2A 

 

Locking the set point :

 

Display switches between “

LO

C

” and “

Stp

”. 

You can lock or unlock the set point adjustment by end user. If locked the 
lock symbol will appear. 
If you do not want to lock set point adjustment by end user, go directly to 
step #3. 

 

Default value: Unlocked 

 

 

A

E

D

C

B

PGM

RUN

PGM

RUN

Содержание TMA54-EXT1

Страница 1: ...temperature 0ºC to 50ºC 32ºF to 122ºF Storage temperature 30ºC to 50ºC 22ºF to 122ºF Relative Humidity 5 to 95 non condensing Degree of protection of housing IP 30 to EN 60529 Weight 85 g 0 2 lb Dimensions A 3 00 78mm B 3 00 78mm C 1 00 24mm D 2 36 60mm Presentation Legend Cooling ON A Automatic Menu set up Lock ON Heating ON A Automatic Programming mode Energy saving mode ON Minimum Maximum set p...

Страница 2: ...ust be set in this mode to operate properly If not locked set point and control mode Heating Cooling ON Cooling only ON or Heating only ON may be modified by the end user Jumper JP1 on PGM Thermostat is set in Programming mode Refer to the following section more details Programming Mode When in this mode this symbol is displayed Please press on button to advance to the next program function and pr...

Страница 3: ...l time in seconds Set the desired value for the integration factor compensation Range 0 to 250 seconds Increment 5 seconds Default value 0 8 Differential time Display switches between dif and the value of the differential time in seconds Set the desired value for the differential time Range 0 to 250 seconds Increment 5 seconds Default value 0 9 Minimum position of 1st cooling ramp Display switches...

Страница 4: ...is in night set back mode NSB symbol is displayed so set point for cooling and or heating are increased as per the setting made in programming mode If not locked night set back can be derogated for a predetermined period by pressing onto any of the 3 buttons During period of NSB derogation the symbol will flash If NSB does not flash the derogation period is finished or the Night set back derogatio...

Отзывы: