Thermostat (Make-Up Air)

 

Specification & Installation Instructions

 

 

TMA54-EXT-131217-ESA.docx

 

         

1

 

 

Technical Data 

TMA54-EXT1 

Outputs 

2 Analog Cooling outputs (0-10Vdc) 
2 Analog Heating outputs (0-10Vdc) 
0 or 22 Vdc, TPM, (Time proportional modulation) 250 mA max. 

Power supply 

22 to 26 Vac 50/60Hz  

Power consumption 

2 VA 

Set point range 

0ºC to +60ºC [32ºF to +140ºF] 

Internal Temperature Sensor 

Range: 0ºC to +50ºC [32ºF to +122ºF] 

External Temperature Sensor 

10k 

 type 3 | Range: -40ºC to +100ºC [-40ºF to +212ºF]  

Control accuracy 

Temperature: +/-0.2ºC [0.4ºF] 

Proportional band 

0.5 ºC to 20ºC [1 ºC to 40ºF] adjustable 

Electrical connection 

0.8 mm

[18 AWG] minimum 

Operating temperature 

0ºC to +50ºC [32ºF to +122ºF] 

Storage temperature 

-30ºC to +50ºC [-22ºF to +122ºF] 

Relative Humidity 

5 to 95 % non condensing 

Degree of protection of housing 

IP 30 to EN 60529 

Weight 

85 g. [0.2 lb] 

Dimensions 
 
A = 3.00” | 78mm 
B = 3.00” | 78mm 
C = 1.00” | 24mm 
D = 2.36” | 60mm 

 

Presentation 

 

Legend 

 

Cooling ON 
A: Automatic 

Menu set-up Lock ON 

 

Heating ON 
A: Automatic 

 

Programming mode 

 

Energy saving mode ON 

Minimum/Maximum 
set points  

 or 

ºC: Celsius scale 
ºF: Fahrenheit scale 

 

 

  

 
 

A

B

C

D

Thermostat for controlling an electric heater in a Make-Up Air unit. 

 

 

Features: 

 Selectable 

analog 

output 

 

Selectable Fahrenheit or Celsius scale 

 

Manual Night Set Back override 

 

Multi level lockable access menu 

 

Lockable Set point 

 

Selectable internal or external temperature sensor 
(10k 

 type 3) 

 

Selectable proportional control band 

 Proportional-integral-derivative

 

(PID)

 

controller

 

TMA54-EXT1

 
 
 
 

 
 
 
 
 

Содержание TMA54-EXT1

Страница 1: ...temperature 0ºC to 50ºC 32ºF to 122ºF Storage temperature 30ºC to 50ºC 22ºF to 122ºF Relative Humidity 5 to 95 non condensing Degree of protection of housing IP 30 to EN 60529 Weight 85 g 0 2 lb Dimensions A 3 00 78mm B 3 00 78mm C 1 00 24mm D 2 36 60mm Presentation Legend Cooling ON A Automatic Menu set up Lock ON Heating ON A Automatic Programming mode Energy saving mode ON Minimum Maximum set p...

Страница 2: ...ust be set in this mode to operate properly If not locked set point and control mode Heating Cooling ON Cooling only ON or Heating only ON may be modified by the end user Jumper JP1 on PGM Thermostat is set in Programming mode Refer to the following section more details Programming Mode When in this mode this symbol is displayed Please press on button to advance to the next program function and pr...

Страница 3: ...l time in seconds Set the desired value for the integration factor compensation Range 0 to 250 seconds Increment 5 seconds Default value 0 8 Differential time Display switches between dif and the value of the differential time in seconds Set the desired value for the differential time Range 0 to 250 seconds Increment 5 seconds Default value 0 9 Minimum position of 1st cooling ramp Display switches...

Страница 4: ...is in night set back mode NSB symbol is displayed so set point for cooling and or heating are increased as per the setting made in programming mode If not locked night set back can be derogated for a predetermined period by pressing onto any of the 3 buttons During period of NSB derogation the symbol will flash If NSB does not flash the derogation period is finished or the Night set back derogatio...

Отзывы: