background image

 

Actuators

 

Specification & Installation Instructions

 

 

TM-RM-210819

 

         

 

 

Technical Data 

TM000 

TM020 

TM060 

TM080 

RM000 

RM020 

RM060 

RM080 

Power supply 

28 to 32 Vdc or 22 to 26 Vac 

Power consumption 

8 VA 

30 VA Peak, 8VA 

10 VA 

30 VA Peak, 10VA 

Torque 

180 in.lb. [20 Nm] at rated voltage 

360 in.lb. [40 Nm] at rated voltage 

Running time through 90º 

60 to 85 sec torque dependant 

Fail safe - Enerdrive 

No 

Yes 

No 

Yes 

Feedback 

4 to 20 mA or 2 to 10 Vdc adjustable 

Auxiliary switches 

No 

Yes (2) 

No 

Yes (2) 

No 

Yes (2) 

No 

Yes (2) 

Electrical connection 

18 AWG [0.8 mm

2

] minimum 

Inlet bushing 

2 inlet bushing of 7/8 in [22.2 mm] 

Control signal 

Analog, Digital or Pulse with modulation (PWM) programmable (factory set with Analog control signal) 

Angle of rotation 

0 to 90 degrees, electronically adjustable (factory set with 90º stroke) 

Direction of rotation 

Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction) 

Operating temperature 

0ºF to 122ºF [-18º C to 50ºC] 

Storage temperature 

-22ºF to 122ºF [-30º C to 50ºC] 

Relative Humidity 

5 to 95 % non condensing 

Weight 

4.5 lbs. [2 kg] 

7 lbs. [3.2 kg] 

Warning: Do not press the clutch when actuator is powered 

 

Dimensions

 

 

 
 

Dimension 

Imperial (in)  Metric (mm) 

5.20 

132.1 

1.33 

33.8 

9.13 

231.9 

3.55 

90.2 

 

 

Caution 

We  strongly  recommend  that  all  Neptronic

®

  products  be  wired  to  a  separate  transformer  and  that  transformer  shall  service  only  Neptronic

®

  products.  This  precaution  will 

prevent interference with, and/or possible damage to incompatible equipment. 
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance. 

 

1

 

Enerdrive System

 U.S.A. Patent #5,278,454

 

 

 

Features:

 

 

Clutch for manual adjustments 

 

Maintenance free 

 

Position indicator 

 

Control signal fully programmable 

 

Fail safe by 

Enerdrive System 

1

 

(on model 060 & 080) 

 

Auxiliary switches  
(on model 020 & 080) 

 

 

 

TM000 

 

TM020 

 

TM060 

 

TM080 

 

RM000 

 

RM020 

 

RM060 

 

RM080 

 

 

 

 

Отзывы: