background image

 

Networkable Fan Coil Controller 

Specification and Installation Instructions 

 

EFCB-OE1-TFL2-TDU-180501

 

 

Page | 1 

Controller Models 

EFCB10T-OE1  

(24Vac / 0 relays) 

EFCB12T-OE1 

 

(240Vac / 0 relays) 

EFCB10TU4-OE1 

(24Vac / 4 relays) 

EFCB12TU2-OE1  

(240Vac / 2 relays)

 

EFCB12TU4-OE1

  (240Vac / 4 relays)

 

 

TFL Series Thermostat 

TFL24

 

 

      

(Thermostat)

 

TFLH24

   

 

 

(Thermostat with humidity sensor) 

TFLG24

   

 

 

(Thermostat with CO

2

TFLGH24 

 

 

(Thermostat with CO

2

 and Humidity) 

 

TDU Series Thermostat 

TDU10   

 

 

 (Grey LCD, white enclosure) 

TDU40   

 

 

(Black LCD, black enclosure)

 

TDU70   

 

 

(Black LCD, white enclosure)

 

 

 

EFCB-OE1 Series 

 

TFL24 Series 

 

TDU10 / TDU40 / TDU70 Series

 

 

Description 

The EFCB-OE1 Series Networkable Fan Coil Controller, 
and TFL24 and TDU Series LCD Thermostats are designed 
for simple and accurate control of any fan coil application. 
The Networkable Fan Coil Controller is mounted inside the 
fan coil cabinet and incorporates a configurable fan coil 
algorithm, variable three speed fan control and either 
modulating or digital heating and cooling outputs. All inputs 
and high/low voltage outputs are centralized at the control 
module in the fan coil cabinet. 

Applications 

 

Compatible with 2 or 4 pipe systems 

 

Fan coil unit (up to 3 speeds and/or analog 0-10 Vdc) 

 

Cooling signal (on/off, floating or modulating 0-10 Vdc) 

 

Heating signal (on/off, floating, pulse or modulating 0-10 Vdc) 

 

Cool, Heat, Reheat, Reheat with fan, Changeover, Fan, 
Humidify and Dehumidify by cooling 

Features 

 

Built-in configurable fan coil algorithms 

 

Up to 10 inputs and 15 outputs (configurable) 

 

Select direction on digital inputs and all outputs 

 

Selectable proportional control band and dead band 

 

Selectable fan speed contacts 

 

No occupancy and NSB override 

 

Independent cool/heat setpoint for NSB/OCC mode 

 

Independent fan speed for NSB or OCC mode 

 

Selectable internal or external temperature sensor 
(10KΩ) 

 

Change over by contact or 10KΩ temperature sensor 

 

Internal and external temperature sensor calibration 

 

Freeze protection 

 

Multi level lockable access menu and setpoint 

 

Removable, raising clamp, non-strip terminals 

Thermostat Features  

 

Backlit LCD with simple icon and text driven menus 

 

Select thermostat’s default display 

 

BACnet service port via on-board mini USB connector 

 

Selectable Fahrenheit or Celsius scale  

 

3-wire connection to controller and 4 push buttons 

Network Communication 

 

BACnet

®

 MS/TP or Modbus communication port  

 

Select MAC address via DIP switch or via network 

 

Automatic baud rate detection 

BACnet MS/TP

®

 

 

Automatic device instance configuration 

 

Copy & broadcast configuration via thermostat menu or via 
BACnet to other controllers 

 

BACnet scheduler 

 

Firmware upgradeable via BACnet 

 

Support COV (change of value) 

Modbus 

 

Modbus @ 9600, 19200, 38400 or 57600 bps 

 

RTU Slave, 8 bits (configurable parity and stop bits) 

 

Connects to any Modbus master 

 
 
 
 
 
 
 
 
 
 
 

 

Содержание TFL24

Страница 1: ...floating pulse or modulating 0 10 Vdc Cool Heat Reheat Reheat with fan Changeover Fan Humidify and Dehumidify by cooling Features Built in configurable fan coil algorithms Up to 10 inputs and 15 outputs configurable Select direction on digital inputs and all outputs Selectable proportional control band and dead band Selectable fan speed contacts No occupancy and NSB override Independent cool heat ...

Страница 2: ...ature 0ºC to 50ºC 32ºF to 122ºF Storage temperature 30ºC to 50ºC 22ºF to 122ºF Relative Humidity 5 to 95 non condensing Enclosure protection IP 30 EN 60529 Weight 635 g 1 4 lb Dimensions A 6 30 160mm B 5 00 126mm C 2 25 57mm Thermostat Specifications Description TFL24 and TDU Series Temperature Sensor TFL24 and TDU Setpoint Range 10ºC to 40ºC 50ºF to 104ºF Control Accuracy 0 5ºC 0 9ºF 22ºC 71 6ºF ...

Страница 3: ... Temp RH CO2 PIR Color TDU10 100 grey LCD white enclosure TDU10 101 TDU10 102 TDU10 103 TDU10 104 TDU10 105 TDU10 106 TDU10 107 TDU10 Series Model Temp RH CO2 PIR Color TDU40 100 black LCD black enclosure TDU40 101 TDU40 102 TDU40 103 TDU40 104 TDU40 105 TDU40 106 TDU40 107 TDU40 Series Model Temp RH CO2 PIR Color TDU70 100 black LCD white enclosure TDU70 101 TDU70 102 TDU70 103 TDU70 104 TDU70 10...

Страница 4: ...Saving Mode NSB OCC Schedule Time ppm Parts Per Million C F RH ºC Celsius Scale ºF Fahrenheit Scale RH Humidity A Automatic Mode Cooling Heating Fan Humidify De humidify Mounting Instructions TFL24 CAUTION Remove power to avoid a risk of malfunction A Remove the captive screw that s holding the base and the front cover of the unit together B Lift the front cover of the unit to separate it from the...

Страница 5: ...ostat using the screw supplied BACnet or Modbus Address DIP Switch DS2 MAC address for communication are selectable by DIP switch using binary logic If you do not change device instance in program mode it will be automatically modified according to the MAC address Note Avoid using addresses above 246 when selecting Modbus MAC address MAC Address DS 1 1 DS 2 2 DS 3 4 DS 4 8 DS 5 16 DS 6 32 DS 7 64 ...

Страница 6: ... 10Vdc configurable min max Direct or reverse 4 analog inputs config 0 10Vdc or 10kOhms via DIP switch NSB or OCC Sensor Power Input 24 or 240Vac Applies to all relays and digital outputs 3 speed fan 4 3 2 1 RET DO4 3A 4 digital outputs config Cool heat reheat changeover humidify dehumidify by cooling Configurable close open percent Direct or reverse LD3 TX LD4 RX 4 TRIAC outputs config Cool heat ...

Страница 7: ...r the action button or the button used to access the menus and save changes is different in the thermostats Use the following menu overviews with the appropriate action button as per your thermostat Action Buttons on Thermostat Action Button Task TFL24 TDU Press to access the programming menus and save any changes Press to return to the previous step without saving Mode Selector Jumper RUN Operati...

Страница 8: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 8 Analog Inputs Menu Overview 1 of 8 AI1 and AI3 ...

Страница 9: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 9 Digital Inputs Menu Overview 2 of 8 DI1 to DI4 ...

Страница 10: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 10 TRIAC Outputs Menu Overview 3 of 8 TO1 to TO4 ...

Страница 11: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 11 Analog Outputs Menu Overview 4 of 8 AO1 to AO4 ...

Страница 12: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 12 Digital Outputs Menu Overview 5 of 8 DO1 to DO4 ...

Страница 13: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 13 Settings Menu Overview 6 of 8 Temp Fan Settings and Ramps ...

Страница 14: ...Networkable Fan Coil Controller Specification and Installation Instructions www neptronic com Page 14 Network and Calendar Menu Overview 7 of 8 Network Time and Options ...

Страница 15: ...le Fan Coil Controller Specification and Installation Instructions www neptronic com Page 15 Humidity Menu Overview 8 of 8 Humidity Only available when a humidity sensor thermostat is connected to the controller ...

Страница 16: ...nd Fan speed Low Low Fan speed Low Fan speed Low Medium Fan speed Medium Fan speed Medium High Fan speed High Fan speed High Cool Auto Speed Fan speed cool demand Fan speed Low Low Fan speed Low Fan speed Low Medium Fan speed Medium Fan speed Medium High Fan speed High Fan speed High Auto H C Auto Speed Fan speed heat cool demand Fan speed Low Low Fan speed Low Fan speed Low Medium Fan speed Mediu...

Страница 17: ...Menu b Password 637 Network Settings Menu 4 If you enter the wrong password the thermostat displays Eror and returns to Operation Mode The thermostat will return to normal mode if you navigate through the entire menu and do not make any selection or if you do not press any key for 5 minutes The changed values will be saved automatically Menu 372 Sensor Offset Menu 637 Network Settings Reset to Fac...

Страница 18: ... press both the and keys for 3 seconds To display the setpoint press the or key twice The setpoint appears for 5 seconds To adjust the setpoint press the arrow keys while the temperature is displayed If the setpoint adjustment has been locked the lock symbol appears C Actual demand Room temperature Appears if in Night Setback NSB or Occupancy OCC mode Flashes if overridden by user RH Alternates be...

Страница 19: ...n Automatic speed Available only if enabled in Programming Mode Low speed Medium speed High speed Off Off is not selectable by the user it appears only if the Control Mode is Off and it indicates that the user can not change the speed of the fan Night Setback NSB This function is only available if you ve set DI3 to nSb Night setback contact If the DI3 contact is triggered the thermostat enters NSB...

Страница 20: ... need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm Eastern time ...

Отзывы: