Neptronic TFCB24F3XYZ1 Скачать руководство пользователя страница 3

TFCB24F3XYZ1 

Specification & Installation Instructions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Programming Mode 

When in this mode this symbol 

 is displayed. Please press on button 

 to advance to the next program function, press on button 

 to return to preceding stage and press on button   or   to change value. You can leave the programming mode at any time, 

changed values will be recorded.  

Step Display 

Description 

Values 

C

 

Internal temperature sensor calibration: 

Display shows 

“inside temper sensor offset”

 and temperature read by 

internal temperature sensor. 
You can adjust the calibration of the sensor by comparison with a known 
thermometer. For example if thermostat has been installed in an area 
where temperature is slightly different than the room typical temperature 
(thermostat place right under the air diffuser). 

Range:  

10.0 to 40.0ºC [50.0 to 104.0ºF] 
(max. offset ± 5 ºC) 

Increment: 0.1ºC [0.2ºF] 

C

 

Minimum set point:

 

Display shows 

“adjust minimum user setpnt”

 and the minimum set point 

temperature. 
Please select the desired minimum set point temperature. 
 
The minimum value is restricted by the maximum value. (step #3) 
 

Minimum range: 

10.0 to 40.0ºC [50 to 104ºF] 

Increment: 0.5ºC [1ºF] 

Default value: 15.0ºC [59ºF] 

C

 

Maximum set point:

 

Display shows 

“adjust maximum user setpnt”

 and the maximum set point 

temperature. 
Please select the desired maximum set point temperature. 
 
The maximum value is restricted by the minimum value. (step #2) 

Maximum range: 

10.0 to 40.0ºC [50 to 104ºF] 

Increment: 0.5ºC [1ºF] 

Default value: 30.0ºC [86ºF]

 

 

Locking the set point:

 

Display shows 

“user setpnt locked” 

and the status of the function. 

You can lock or unlock the set point adjustment by end user. If locked, 

“yes” 

and lock symbol will appear.  

 

Default value: 
Unlocked (NO) 

C

Adjust internal set point:

 

Display shows 

“adjust intern setpnt”

 and the set point temperature. 

Select the desired set point temperature; this one should be within the 
temperature range. 
Lock symbol will appear if the set point was locked at the previous step. 
 
Set point value is restricted by the minimum and maximum value. (step 
#2 & 3) 

Set point range:  

10.0 to 40.0ºC [50 to 104ºF] 

Increment: 0.5ºC [1ºF] 

Default value: 22.0ºC [72ºF] 

 

Adjust the control mode:

 

Display shows 

“adjust temper control mode”

.

 Cooling and heating 

symbols are also displayed.

 

Select which control mode you want to authorize: 
Automatic

 cooling and heating

, cooling or heating, heating only or cooling 

only. 
 
If you want to authorize this entire mode, choose Automatic mode. 

 

 

 

Default value: 
Automatic cooling and heating

 

Set On/Off  function enable or disable:

 

Display shows 

“enable on off control mode”

.

 

You can enable or disable the On/Off function in control mode 
adjustment by end user. 

 

Default value: 
Enable (YES) 

 

Set 2 pipe or 4 pipe:

 

Display shows 

“select 2 pipe 4 pipe system”

.

 Cooling and heating 

symbols are also displayed.

 

Select which number of pipes you want to use: 2 pipes or 4 pipes. 
 

If you have selected the 4 pipes, go directly to step #15.

 

 

Default value: 2 pipe

 

Содержание TFCB24F3XYZ1

Страница 1: ...2 F Relative Humidity 5 to 95 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Presentation SEC VDC HR C F RH MAX V MIN V AM PM Symbols on display Cooling ON 33 66 10...

Страница 2: ...on off or pulse heat 4 Pipe on off or pulse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local re...

Страница 3: ...y the minimum value step 2 Maximum range 10 0 to 40 0 C 50 to 104 F Increment 0 5 C 1 F Default value 30 0 C 86 F 4 Locking the set point Display shows user setpnt locked and the status of the functio...

Страница 4: ...y cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normal...

Страница 5: ...minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which...

Страница 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0 C 0 6 to 1...

Страница 7: ...d Please select the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 External sensor selection Display shows extern sensor temper Please select whi...

Страница 8: ...isplay shows enable anti freeze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4 C 39 F heat and reheat will start even if thermostat is in OFF mode Hea...

Страница 9: ...e increased as per the setting made in programming mode If not locked no occupancy mode can be derogated for a predetermined period by pressing onto any of the 3 buttons During period of derogation th...

Отзывы: