Fan Coil Thermostat

 

Specification & Installation Instructions

 

 

TFCB24F3XYZ1.doc/100204

 

         

1

 

Fan Coil Thermostat with BACnet

®

 Communication Port

 

 

Technical Data 

TFCB24F3XYZ1 

Inputs 

1 Digital input (24Vac or dry contact) 

1 Analog input (external temperature sensor 10K

1 Analog input (change over 10K

 or dry contact) 

Outputs

 

1 Fan analog or 3 Fan speed dry contracts 24Vac, 1A max 3A in-rush 

2 Analog outputs (cooling and/or heating 0-10Vdc) 

1 Analog output (local reheat 0-10Vdc ) 

2 Triacs output (cooling and/or heating) 24Vac, 0.3A max fused / triac 

1 Triacs output (local reheat) 24Vac, 0.3A max fused / triac 

Power supply 

22 to 26 Vac 50/60Hz 

Power consumption 

1 VA max 

Set point range 

10ºC to 40ºC [50ºF to 104ºF] 

Control accuracy 

Temperature: ±0.4ºC [0.8ºF] 

Proportional band 

0.5ºC to 5ºC [1ºF to 10ºF] adjustable (heat/cool/reheat independent) 

Dead band 

0.3ºC to 5ºC [0.6ºF to 10ºF] adjustable (heat/cool/reheat independent) 

Electrical connection 

0.8 mm

2

 [18 AWG] minimum 

Operating temperature 

0ºC to 50ºC [32ºF to 122ºF] 

Storage temperature 

-30ºC to 50ºC [-22ºF to 122ºF] 

Relative Humidity 

5 to 95 % non condensing 

Degree of protection of housing 

IP 30 (EN 60529) 

Weight 

160 g. [0.36 lb] 

Presentation

 

SEC

VDC

HR

C

F

%RH

..,

..

MAX

V

MIN

V

AM

PM

 

Symbols on display 

 

Cooling ON 
33,66,100% output 
A: Automatic 

 

Communication 
Status 

 

Alarm status 

 

Heating ON 
33,66,100% output 
A: Automatic 

 

Menu set-up Lock 

 

Energy saving mode 

 

Fan ON 
3

rd

 speed activated 

A: Automatic 

 

Programming mode
(Technician setting) 

C

or 

F

 

ºC: Celsius scale 
ºF: Fahrenheit scale 

  

Dimensions 

A

B

C

D

E

 

Dimension

Inches Metric 

(mm)

A

2.85 73 

B

4.85 123 

C

1.00 24 

D

2.36 60 

E

3.27 83 

 

 

 

Features: 

 

Attractive modern look with large LCD and backlight 

 

Icons driven information and 1 line of text information 

 

2 Pipes Analog, ON/OFF or Floating  
4 Pipes Analog, ON/OFF with local re-heat function 

 

Auto fan and ON/OFF function enable or disable 

 

Precise achieve temperature control with programmable PI function 

 

Independent cooling & heating no occupancy set point 

 

Lockable Set point / Control mode 

 

Selectable internal or external temperature sensor 

 

Change over by contact or external temperature sensor 

 

Celsius or Fahrenheit scale selectable 

 Anti-freeze 

protection 

 BACnet

®

 MS/TP @ 9600,19200,38400,76800bps 

 

Selectable device instance and MAC address via technician menu 

TFCB24F3XYZ1 

 
 
 
 
 
 
 
 

 

Содержание TFCB24F3XYZ1

Страница 1: ...2 F Relative Humidity 5 to 95 non condensing Degree of protection of housing IP 30 EN 60529 Weight 160 g 0 36 lb Presentation SEC VDC HR C F RH MAX V MIN V AM PM Symbols on display Cooling ON 33 66 10...

Страница 2: ...on off or pulse heat 4 Pipe on off or pulse heat 6 Triac output 3 TO3 Reheat Local reheat optional on off or pulse Local reheat optional on off or pulse Local reheat optional on off or pulse Local re...

Страница 3: ...y the minimum value step 2 Maximum range 10 0 to 40 0 C 50 to 104 F Increment 0 5 C 1 F Default value 30 0 C 86 F 4 Locking the set point Display shows user setpnt locked and the status of the functio...

Страница 4: ...y cool or NoHt change over contact normally heat When normally cool NoCL is selected if contact is closed heating mode will be activated if contact is opened cooling mode will be activated When normal...

Страница 5: ...minimum value step 19 Range 0 0 to 10 0 Volt Increment 0 1 Volt Default value 10 0 Volt 21 Set local reheat signal Display shows set local reheat signal Heating symbols is also displayed Select which...

Страница 6: ...splay shows control dead band cooling and the value of the cooling dead band cooling symbol is also displayed Please select the desired value of cooling dead band Dead band range 0 3 to 5 0 C 0 6 to 1...

Страница 7: ...d Please select the desired value of the automatic shutoff delay Range 0 to 15 min Increment 1 min Default value 2 min 38 External sensor selection Display shows extern sensor temper Please select whi...

Страница 8: ...isplay shows enable anti freeze protect You can enable or disable the Anti freeze function When enabled if temperature drop to 4 C 39 F heat and reheat will start even if thermostat is in OFF mode Hea...

Страница 9: ...e increased as per the setting made in programming mode If not locked no occupancy mode can be derogated for a predetermined period by pressing onto any of the 3 buttons During period of derogation th...

Отзывы: