Room Control Switch
Specification and Installation Instructions
Specification and Installation Instructions
IMC10-201116
www.neptronic.com
Page | 1
Models
IMC10
Features
•
Press push button to switch between off, continuous and intermittent
operation modes.
•
In intermittent mode, the operation type is alternated based on the time
interval selected by the DIP switches (15, 30, 45 or 60 minutes).
•
LED status indications for operation mode and power.
•
Three wire connection between switch and CMU.
IMC10
Technical Data
Specification
IMC10
Description
Push button room control switch that can be used with the CMU series compact make-up
air units.
Electrical Connection
3 wires 0.8 mm
2
[18 AWG] minimum
Power Supply
24Vac
Power Consumption
1VA
Operating and Storage Temperature
0ºC to 50ºC (32ºF to 122ºF)
Relative Humidity
5 to 95 % non condensing
Ingress Protection
IP 30 (EN 60529)
Weight
60 g. [0.13 lb]
Power LED (left)
Turns green if the device is powered on.
Turns OFF if the device is powered off.
Operation Mode LED (right)
Turns green if the device is in continuous operation mode.
Turns white if the device is in intermittent operation mode.
Dimensions
A = 3.00
” | 78mm
B = 3.00” | 78mm
C = 1.00” | 24mm
D = 2.36” | 60mm
Wiring
1
2
3
COM
OUTPUT
24V
Connect to
CMU
ON
DS1
Intermittent Operation Mode | DS1
3
4
Result
OFF
OFF
15 mins On / 15 mins Off
ON
OFF
30 mins On / 30 mins Off
OFF ON
45 mins On / 45 mins Off
ON
ON
60 mins On / 60 mins Off
TB1
1 2 3 4
Not
Used
A
B
C
D