Networkable VAV Controller
Specification and Installation Instructions
www.neptronic.com
EVCB14NIT4X
Page | 6
Pressure & Applications
– Menu (1 of 7)
For a description of the default settings for each application refer to Annex A: Control Apps on page 17.
Main Menu
APPS
(Applications)
PrSs
(Pressure)
CO2
(carbon dioxide)
CHrh
(cool, heat, & reheat)
iTOS
(ITOS)
rMp
(Ramps)
NET
(Network)
HrS
(Time & Date)
dEP
(dependent)
Pressur Mode
Ind
(independent)
Setc
(Settings)
Mot
(Motor)
tMp
(Temperature)
OutP
(Outputs)
InPt
(Inputs)
= scroll menu items
OPt
(Options)
= scroll menu items
Main Menu
Sub Menu
Configuration
Motor Minimum Pos Cooling
10%
(0-100)
Motor Minimum Pos Heating
10%
(0-100)
ClHt
(cool & heat)
Control Apps
Cl
(cool only)
= scroll menu items
APPS
APPS
YES
(confirm)
Confirm Control apps
NO
(cancel)
The APPS represent pre-defined default settings
for selected applications. If you select Yes, the
settings in Annex A will be applied and override
any values already configured .
BV.50
AV.90
AV.91
InPt
*** You must press the button to save any changes ***
*** Pressing the button returns to the previous step without saving ***
We recommend selecting the `Control Apps` before changing any other configurations. Once selected, certain
configurations, such as NSB, proportional bands, and deadbands, will be erased and reset to factory default values.
FPbo
(fan powered box ON)
FPbA
(fan powered box Auto)