Networkable VAV Controller
Specification and Installation Instructions
www.neptronic.com
EVCB14NIT4X
Page | 12
Settings
– Menu (7 of 7) |
Ramps, Network, Time, and Options
OPt
(Options)
CPYc
(copy config)
bAC
mOd
Network Config
tYPe
(Type)
= scroll menu items
Main Menu
Sub Menu
Configuration
Network Choice
bAC
(BACnet)
mOd
(Modbus)
= select / set value
Modbus Auto Baud Rate
No
(Manual)
Yes
(Automatic)
= select / set value
BACnet Auto Baud Rate
No
(Manual)
Yes
(Automatic)
= select / set value
= select / set value
Start Address
0
(0-254)
Go to “BACnet Auto Baud Rate"
Go to “Modbus Auto Baud Rate"
If type = bAC, menu
contains “tYpe”, “bAC”
and “CPYc”
If type = mOd, menu
contains “tYpe and
“mOd”
Modbus Baud Rate
57.6k
(9.6k, 19.2k, 38.4, 57.6k)
Bacnet Baud Rate
76.8k
(9.6k, 19.2k, 38.4, 76.8k)
MSTP MAC Address
0
(0-254)
Modifiable only if Auto Baud Rate
set to “No”.
Modifiable only if Auto Baud Rate
set to “No”.
Modifiable only if all DS1 DIP
switches are set to OFF.
0153000
0
(device instance)
Go to
“CPYc"
MSTP MAX Master
127
(1-127)
OP1s
(odd parity, 1 stop bit)
Modbus Comport Config
NP2s
(no parity, 2 stop bits)
EP1s
(even parity, 1 stop bit)
Modbus Address
1
(1-246)
Modifiable only if all DS1 DIP
switches are set to OFF.
Go to “HrS"
End Address
0
(0-254: max=start + 63)
Confirm Copy Config
No
(cancel)
Yes
(confirm)
Copy Config
in
(in progress)
Go to “HrS"
Copy Config Result
Succeed
Go to
“HrS"
= select / set value
Hours
12
(0-23 or 1-12 am/pm)
Minutes
00
(00-59)
Year
15
(15-99)
Set Time Display format
24
(24-hour format)
12
(AM/PM format)
Month
1
(1-12)
Day
1
(1-31)
Go to “OPt"
= scroll menu items
1001
AV.166
AV.165
1000
BV.90
AV.167
Local Time
Local Date
Local Time
Local Date
Local Date
Refer to Copy Config Annnex for
a complete list of messages and
error codes.
*** You must press the button to save any changes ***
*** Pressing the button returns to the previous step without saving ***
Main Menu
APPS
(Applications)
PrSs
(Pressure)
rMp
(Ramps)
NET
(Network)
HrS
(Time & Date)
Setc
(Settings)
Mot
(Motor)
tMp
(Temperature)
OutP
(Outputs)
InPt
(Inputs)
Hr2
(heating ramp 2)
CH Over Prop Band
2.0°C / 4.0°F
(0.5-5
°
C / 1-9
°
F)
CH Over Dead Band
0.3°C / 0.6°F
(0-5
°
C / 0-9
°
F)
Hr1
(heating ramp 1)
Cr2
(cooling ramp 2)
Cr1
(cooling ramp 1)
Ramp Setting
COr
(changeover)
= scroll menu items
CR1 Prop Band
2.0°C / 4.0°F
(0.5-5
°
C / 1-9
°
F)
CR1 Dead Band
0.3°C / 0.6°F
(0-5
°
C / 0-9
°
F)
CR2 Prop Band
2.0°C / 4.0°F
(0.5-5
°
C / 1-9
°
F)
CR2 Dead Band
0.3°C / 0.6°F
(0-5
°
C / 0-9
°
F)
Hr1 Prop Band
2.0°C / 4.0°F
(0.5-5
°
C / 1-9
°
F)
Hr1 Dead Band
0.3°C / 0.6°F
(0-5
°
C / 0-9
°
F)
Go to “Cr1"
Go to “Cr2"
Go to “Hr1"
Go to “Hr2"
Hr2 Prop Band
2.0°C / 4.0°F
(0.5-5
°
C / 1-9
°
F)
Hr2 Dead Band
0.3°C / 0.6°F
(0-5
°
C / 0-9
°
F)
Go to “NEt"
AV.56
AV.41
AV.46
AV.21
AV.24
AV.57
AV.42
AV.47
AV.22
AV.25
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
CO2 Setpnt
800 ppm
AV.141
ANLg
CO2 Control Source
trL
BV.66
NO
CO2 DISPLAY
YES
BV.65
Go to “PrSs"
NO
DISPLAY Humidty
YES
BV.60
Appears only if using TRLG or TRLGH
For TRL and TRLH go to “InPt” menu.
Appears only if using TRLG or TRLGH
For TRL and TRLH go to “InPt” menu.
Appears only if using TRLG or TRLGH
Appears only if using TRLH or TRLGH
To display CO2 without generating
an alarm, use a setpoint higher than
2000ppm or the CO2 Maximum
Range (highest of the 2).
When set to YES, the unit will not display
the time when in Operation Mode