Networkable Fan Coil Controller
Specification and Installation Instructions
www.neptronic.com
Page | 18
Network and Calendar
– Menu Overview (7 of 8) | Network, Time, Buttons and Options
OPt
(Options)
Only available with
CO
2
sensor models
in
(in progress)
CPYc
(copy config)
bAC
mOd
Network Config
tYPe
(Type)
= scroll menu items
rm
P
(Ramps)
nEt
(Network)
btN
(But tons)
HrS
(Hours
– Time & Date)
Hu
(Humidity)
Only available with
Humidity sensor models
SEt
c
(Set tings)
FAN
tm
P
(Temperature)
Out
P
(Out put s)
Main Menu
InPt
(Inputs)
= scroll menu items
Main Menu
Sub Menu
Configuration
Network Choice
bAC
(BACnet)
mOd
(Modbus)
= select / set value
Modbus Auto Baud Rate
No
(Manual)
Yes
(Aut omatic)
= select / set value
bacnet Auto Baud Rate
No
(Manual)
Yes
(Aut omatic)
= select / set value
= select / set value
Start Address
0
(0-254)
Go to "bAC"
Go to "mO d"
If type = bAC, menu
contains “tYpe”, “bAC”
and “CPYc”
If type = mOd, menu
contains “tYpe and
“mOd”
Modbus Baud Rate
57.6k
(9.6k, 19.2k, 38.4, 57.6k)
Bacnet Baud Rate
76.8k
(9.6k, 19.2k, 38.4, 76.8k)
MSTP MAC Address
0
(0-254)
Modif iable only if Auto Baud Rate
set to “No”.
Modif iable only if Auto Baud Rate
set to “No”.
Modif iable only if all DS2 DIP
switches are set to O FF.
0153000
0
(device instance)
Go to
"CPYc"
MSTP MAX Master
127
(1-127)
OP1s
(odd parity, 1 stop bit )
Modbus Comport Config
NP2s
(no parity, 2 st op bits)
EP1s
(even parity, 1 stop bit )
Modbus Address
1
(1-246)
Modif iable only if all DS2 DIP
switches are set to O FF.
Go to "HrS"
End Address
0
(0-254, start 63)
Confirm Copy Config
No
(cancel)
Yes
(confirm)
Copy Config
Go to "HrS"
Copy Config Succeed
(done)
Go to
"HrS"
= select / set value
Hours
12
(0-23 or 1-12 am/pm)
Minutes
00
(00-59)
Year
15
(15-99)
Set Time Display format
24
(24-hour format)
12
(AM/PM format)
Month
1
(1-12)
Day
1
(1-31)
1000
1001
AV.165
AV.166
BV.90
Local Time
AV.167
Local Time
Local Date
Local Date
Local Date
*** To save any changes, press on TFL and on TDF ***
*** To return to the previous step without saving, press on TFL and on TDF ***
NO
CO2 DISPLAY
YES
BV.65
When set to YES, t he unit will not display
the t ime when in O peration Mode
G
o to “Hu”
= select / set value
Bottom Left key locked
NO
YES
Upper Left key locked
NO
YES
Arrows key locked
NO
YES
G
o to “btN”
G
o to “InPt”
Co2 control source
ANLG
trL
occ control source
DI1
Int
CO2 SetPoint
800
(100-CO2RangePPM)
AV.159
BV.93
BV.34
Occ minimum time in minutes
30
(0-240)
AV.88
No occ heating setpoint
16°C/61°F
(10°C-AV.12/50°F-AV.12)
AV.13
No occ Cooling setpoint
28°C/82°F
(AV. 13-40°C/AV.13-104° F)
AV.12