Networkable Fan Coil Controller 

Specification and Installation Instructions 

 

EFCB1xTUx-TFL2-TDF-191018-ESA

 

 

Page | 1 

Models 

EFCB10TU2 

(24Vac / 2 relays) 

EFCB10TU4 

(24Vac / 4 relays)

 

 

EFCB11TU2 

(120Vac / 2 relays)

 

EFCB11TU4

 

(120Vac / 4 relays)

 

 

EFCB12TU2

 

(240Vac / 2 relays)

 

EFCB12TU4 

(240Vac / 4 relays) 

TFL24 Series Digital Room Sensor 

TFL24 

     

(With temperature sensor)

 

TFLH24       

(

With temperature and humidity sensor) 

TFLG24

       

(With temperature and CO

sensor) 

TFLGH24    

(With temperature, CO

2

 and humidity    

 

 

 

 

 

sensors) 

TDF Series Digital Room Sensor 

TDF00

 

 

 

(Vertical Grey LCD, white enclosure)

 

TDF30

 

 

 

(Vertical Black LCD, black enclosure)

 

TDF60 

 

 

(Vertical Black LCD, white enclosure)

 

 
TDF10 

     

(Horizontal Grey LCD, white enclosure) 

TDF40 

     

(Horizontal Black LCD, black enclosure)

 

TDF70 

     

(Horizontal Black LCD, white enclosure) 

 

 

EFCB Series 

 

TFL24 Series 

 

TDF00 / TDF30 / 

TDF60 Series 

 

TDF10 / TDF40 / 

TDF70 Series 

Description 

The EFCB Series Networkable Fan Coil Controller, and 
TFL24 and TDF Series Digital Room Sensors are designed 
for simple and accurate control of any fan coil application. The 
BACnet Fan Coil Controller is mounted inside the fan coil 
cabinet and incorporates a configurable fan coil algorithm, 
variable three speed fan control and either modulating or 
digital heating and cooling outputs. All inputs and high/low 
voltage outputs are centralized at the control module in the 
fan coil cabinet. 

Applications 

 

Compatible with 2 or 4 pipe systems 

 

Fan coil unit (up to 3 speeds and/or analog 0-10 Vdc) 

 

Cooling signal (on/off, floating or modulating 0-10 Vdc) 

 

Heating signal (on/off, floating, pulse or modulating 0-10 
Vdc) 

 

Cool, Heat, Reheat, Reheat with fan, Changeover, Fan, 
Humidify and Dehumidify by cooling. 

Features 

 

Built-in configurable fan coil algorithms 

 

Up to 10 inputs and 15 outputs (configurable) 

 

Select direction on digital inputs and all outputs 

 

Selectable proportional control band and dead band 

 

Selectable fan speed contacts 

 

Independent cool/heat setpoint for NSB/OCC mode 

 

No occupancy and NSB override 

 

Selectable internal or external temperature sensor 
(10KΩ) 

 

Change over by contact or 

10KΩ temperature sensor 

 

Internal and external temperature sensor calibration 

 

Freeze protection 

 

Multi level lockable access menu and setpoint 

 

Removable, raising clamp, non-strip terminals 

Digital Room Sensor Features  

 

Backlit LCD with simple icon and text driven menus 

 

Select digital room sensor

’s default display 

 

BACnet service port via on-board mini USB connector 

 

Selectable Fahrenheit or Celsius scale  

 

3-wire connection to controller and 4 push buttons 

Network Communication 

 

BACnet

®

 MS/TP or Modbus communication port  

 

Select MAC address via DIP switch or via network 

 

Automatic baud rate detection 

BACnet MS/TP

®

 

 

Automatic device instance configuration 

 

Copy and broadcast configuration via digital room sensor 
menu or via BACnet to other controllers 

 

BACnet scheduler 

 

Firmware upgradeable via BACnet 

 

Support COV (change of value) 

Modbus 

 

Modbus @ 9600, 19200, 38400 or 57600 bps 

 

RTU Slave, 8 bits (configurable parity and stop bits) 

 

Connects to any Modbus master 

 
 

 

Содержание EFCB10TU2

Страница 1: ...oil unit up to 3 speeds and or analog 0 10 Vdc Cooling signal on off floating or modulating 0 10 Vdc Heating signal on off floating pulse or modulating 0 10 Vdc Cool Heat Reheat Reheat with fan Changeover Fan Humidify and Dehumidify by cooling Features Built in configurable fan coil algorithms Up to 10 inputs and 15 outputs configurable Select direction on digital inputs and all outputs Selectable...

Страница 2: ...esistive ratings 7 Amp 1680 W at 240 Vac Maximum configurable up to 3 speeds 2 or 4 configurable digital outputs changeover cooling heating humidity 3A dry contact Power supply 24 Vac 120 Vac 240 Vac Power consumption 8 VA max 24 Vac thermal fused BACnet BACnet MS TP 9600 19200 38400 or 76800 bps BAS C Modbus Modbus RTU slave 9600 19200 38400 or 57600 Selectable parity and stop bit configuration N...

Страница 3: ...Principle Passive Infrared PIR Detection Angle 100 Detection Distance 4m 13ft Detection Area 100º 4m 13ft VOC Sensor TDF00 TDF30 TDF60 Series models with VOC Sensor Operating Principle Self calibrating Non Dispersive Infrared NDIR Sensor Range 0 1000 ppb isobutylene equivalent tVOCs Response Time 5 seconds for tVOC Start up Time 15 mintues Other Electrical connection 3 wires to EFCB controller and...

Страница 4: ...mm E 3 27 83mm TDF10 TDF40 TDF70 Series A 5 24 133mm B 2 87 73mm C 3 74 95mm D 1 22 31mm E 0 75 19mm F 2 00 51mm G 2 18 55mm TDF00 TDF30 TDF60 Series A 4 88 124mm B 3 25 83mm C 1 75 44mm D 0 96 24mm E 2 07 53mm F 2 36 60mm G 3 28 83mm H 0 78 20mm without CO2 0 95 24mm with CO2 E D B A C PIR Sensor Optional G F H A B C D E ºF º C A B C D E F G R 095 TYP R6 542 TYP ...

Страница 5: ...TDF70 101 TDF10 102 TDF40 102 TDF70 102 TDF10 103 TDF40 103 TDF70 103 TDF10 Series TDF40 Series TDF70 Series Vertical Model Temp RH CO2 PIR VOC TDF00 100 TDF30 100 TDF60 100 TDF00 101 TDF30 101 TDF60 101 TDF00 102 TDF30 102 TDF60 102 TDF00 104 TDF30 104 TDF60 104 TDF00 105 TDF30 105 TDF60 105 TDF00 106 TDF30 106 TDF60 106 TDF00 107 TDF30 107 TDF60 107 TDF00 Series TDF30 Series TDF60 Series ...

Страница 6: ...DF40 TDF70 Series Network Communication User Lock Programming Mode Technician Setting Alarm Status Energy Saving Mode NSB OCC Schedule Time ppm Parts Per Million C F RH ºC Celsius Scale ºF Fahrenheit Scale RH Humidity A Automatic Mode Cooling Heating Fan Humidify De humidify TDF00 TDF30 TDF60 Series AM PM F C RH Network Communication User Lock Programming Mode Technician Setting Alarm Status Energ...

Страница 7: ... back of the digital room sensor B Install the mounting plate on the gang box C Pull the wires through the base hole and make the appropriate connections D Mount the digital room sensor onto the wall plate To mount it correctly place the top of the digital room sensor on the mounting plate first and push it into the grooves to snap it into place E Secure the digital room sensor using the screw sup...

Страница 8: ...ding to the MAC address Note Avoid using addresses above 246 when selecting Modbus MAC address MAC Address DS 1 1 DS 2 2 DS 3 4 DS 4 8 DS 5 16 DS 6 32 DS 7 64 DS 8 128 Default Device Instance 0 OFF OFF OFF OFF OFF OFF OFF OFF 153000 1 ON OFF OFF OFF OFF OFF OFF OFF 153001 2 OFF ON OFF OFF OFF OFF OFF OFF 153002 3 ON ON OFF OFF OFF OFF OFF OFF 153003 4 OFF OFF ON OFF OFF OFF OFF OFF 153004 126 OFF ...

Страница 9: ...Cool heat reheat changeover fan humidify dehumidify by cooling 0 10Vdc configurable min max Direct or reverse 4 analog inputs config 0 10Vdc or 10kOhms via DIP switch NSB or OCC Sensor 0 3 speed fan 4 3 2 1 RET DO4 3A 4 digital outputs config Cool heat reheat changeover humidify dehumidify by cooling Configurable close open percent Direct or reverse LD3 TX LD4 RX 4 TRIAC outputs config Cool heat r...

Страница 10: ...er PGM Digital Room Sensor is set in Programming Mode Refer to the following sections for more details TDF00 TDF30 TDF60 Series 3 wire cable TB1 1 2 3 Connect TB1 6 A 7 B to EFCB to enable the BACnet service port VOC sensor models with VOC JP1 PGM RUN CO2 sensor models with CO2 1 2 3 4 7 6 5 B A COM PWR DATA Avoid touching the CO2 and VOC sensors as this may cause incorrect readings Mode Selection...

Страница 11: ...s is different in the digital room sensors Use the following menu overviews with the appropriate action button as per your digital room sensor Action Buttons on Digital Room Sensor Action Button Task TFL24 TDF TDU Press to access the programming menus and save any changes Press to return to the previous step without saving Note If the EFCB controller is being configured using a TDU digital room se...

Страница 12: ...5 RH AV 72 Go to AI5 Go to AI5 0 10 Vdc Sensor 2 10 Vdc Sensor Ai4 extern temp type OFF Ai4 minimum Temp 0 0 C 32 F 40 0 0 C 40 32 F Ai4 maximum Temp 50 C 122 F 50 100 C 122 212 F MSV 38 AV 7 AV 8 Go to AI5 HUM humidity sensor CO2 EtS ext temp sensor Ai4 Signal type OFF select set value AI4 MSV 101 CO2 maximum range 2000 100 5000PPM AV 160 CO2 setpoint 800 100 CO2RangePPM AV 159 Yes Co2 display No...

Страница 13: ...low switch OFF OVHt override heat dFt dirty filter select set value DI2 Delay Seconds 120 0 to 3600 DI2 Contact NO normally open Go to DI3 DI2 BV 46 AV 91 select set value OCC Minimum Time Minutes 30 0 240 nSbc night set back closed nSbo night set back open OCCc occupancy closed OCCo occupancy open NSB OCC Contact OFF Go to DI4 NSBOveride delay Minutes 120 0 180 No OCC Overide Delay Min 120 0 180 ...

Страница 14: ...04 ALRM alarm TO2 DIR REV DIR direct REV reverse PuLs pulsed LI light rHt reheat without fan rHt reheat with fan HEAt COOl COr changeover TO2 Ramp OFF TO2 Close Percent 50 15 80 TO2 Signal Type OnOf on off Go to TO3 Only if HEAt or rHt is selected TO2 Open Percent 25 0 to tO2 Close pos 4 TO3 DIR REV DIR direct REV reverse PuLs pulsed FLt floating LI light rHt reheat without fan rHt reheat with fan...

Страница 15: ...er AO2 Ramp ALRM alarm OFF select set value AO2 Minimum Voltage 0 0 0 max Go to AO3 AO2 Maximum Voltage 10 0 min 10 AO2 Hu humidity AO3 DIR REV DIR direct REV reverse rHt reheat without fan rHt reheat with fan HEAt COOl ALRM alarm COr changeover AO3 Ramp OFF select set value AO3 Minimum Voltage 0 0 0 max Go to AO4 AO3 Maximum Voltage 10 0 min 10 AO3 Hu humidity AO4 DIR REV DIR direct REV reverse r...

Страница 16: ... Ramp ALRM alarm OFF select set value DO1 Close Percent 25 15 80 Go to DO2 DO1 Open Percent 0 0 to dO1 Close pos 4 dO1 Hu humidity rHt reheat without fan rHt reheat with fan HEAt COOl COr changeover DO2 Ramp ALRM alarm OFF select set value Go to DO3 dO2 Hu humidity rHt reheat without fan rHt reheat with fan HEAt COOl COr changeover DO3 Ramp OFF ALRM alarm select set value Go to DO4 dO3 Hu humidity...

Страница 17: ...onds 120 0 255 COOl Temp Control Mode Auto automatic HEAt select set value Go to SEtc Enable onoff Control Mode No Disabled Yes Enabled StP C setpoints T C Display Info T C C H StP C C H Freeze Protect No Disabled Yes Enabled Cooling anti cycle minutes 0 0 15 clht switch timer 0 0 120 Heating Intgral time in Seconds 0 0 250 Cooling Intgral time in Seconds 0 0 250 Go to rMp CHOver Prop Band 2 C 4 F...

Страница 18: ...S2 DIP switches are set to OFF 0153000 0 device instance Go to CPYc MSTP MAX Master 127 1 127 OP1s odd parity 1 stop bit Modbus Comport Config NP2s no parity 2 stop bits EP1s even parity 1 stop bit Modbus Address 1 1 246 Modifiable only if all DS2 DIP switches are set to OFF Go to HrS End Address 0 0 254 start address 63 Confirm Copy Config No cancel Yes confirm Copy Config Go to HrS Copy Config S...

Страница 19: ... value AI5 analog input 5 AI4 analog input 4 AI3 analog input 3 Extern Humidty Sensor Input OFF OFF selection only appears if irH was selected in the previous step Extern humidty SensorOffset Actual RH 5 RH Skip this step if irH and OFF were selected User Setpnt Minimum 30 10 90 User Setpnt Maximum 65 10 90 User Setpnt Locked No unlocked Yes locked User Setpnt 40 min to max 10 90 Humidty Prop Band...

Страница 20: ...etwork Settings End exit menu CPYc copy config bAC BACnet mOd Modbus Network Config tYPe Type scroll menu items Network Choice bAC BACnet mOd Modbus select set value Modbus Auto Baud Rate No Manual Yes Automatic select set value BACnet Auto Baud Rate No Manual Yes Automatic select set value select set value Start Address 0 0 254 If type bAC menu contains tYpe bAC and CPYc If type mOd menu contains...

Страница 21: ...ors with Humidity and Humidity Mode must not be OFF Press once to display Fan Speed Mode Exits after 5 sec Exits after 5 sec Press to change mode Auto Off Cool only Heat only CO2 reading in ppm CO2 display option must be enabled in programming mode Press any arrow key twice to display Setpoint Mode Press to change mode Auto OFF low medium High Press once to display Control Mode Press both keys for...

Страница 22: ... Control Mode appears for 5 seconds Press the key to scroll through the following control modes These options can vary depending on the options selected Auto Automatic Cooling or Heating Cooling only on with cooling symbol Heating only on with heating symbol OFF if it is not disabled in Programming Mode Fan Speed Selection Mode To access the Fan Speed selection mode press the key The mode appears ...

Страница 23: ...e button to go to the previous step without saving select set value Hours 12 0 23 or 1 12 am pm Minutes 00 00 59 Year 15 15 99 Set Time Display format 24 24 hour format 12 AM PM format Month 1 1 12 Day 1 1 31 Exits and returns to RUN mode Local Time Local Date Local Time Local Date Local Date To save any changes press on TFL and on TDF To return to the previous step without saving press on TFL and...

Страница 24: ... need to find the nearest Neptronic authorized distributor please consult www neptronic com 400 Lebeau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm Eastern time ...

Отзывы: