background image

 

EFCB Thermostat

 

Specification & Installation Instructions

 

 

TFL(H)5x-180322.doc/111031 

 

 

 

                  

1

 

 

 
Technical Data

 

TFL54 

TFLH54-xxx 

Electrical connection 

3 wire cable 

3 wire cable 

Setpoint range 

10ºC to 40ºC [50ºF to 104ºF] 

Temperature: 10ºC to 40ºC [50ºF to 104ºF] 

Humidity: 10 to 65%RH 

Control accuracy 

Temperature: ±0.5ºC [0.9ºF] @ 22ºC [71.6ºF] 

typical calibrated 

Temperature: ±0.5ºC [0.9ºF] @ 22ºC [71.6ºF] 

typical calibrated, Humidity ±3.5% 

Power supply 

From EFCB 

Power consumption 

1 VA 

Display resolution 

±0.1ºC [0.2ºF] 

Proportional band 

0.5ºC to 5ºC [1ºF to 10ºF] adjustable 

Operating temperature 

0ºC to 50ºC [32ºF to 122ºF] 

Storage temperature 

-30ºC to 50ºC [-22ºF to 122ºF] 

Relative humidity 

5 to 95 % non condensing 

Housing degree of protection 

IP 30 (EN 60529) 

Weight 

80 g. [0.15 lb] 

Note 

The TFL(H)5x can only work with the EFC. All the inputs/outputs are located on the EFC except 
for the temperature sensor built-in the TFL(H)5x. 

 

Interface

 

 

Display Symbols 

 

Cooling ON 
100% output 
A: Automatic 

 

Menu set-up lock 

 

Energy saving mode 

 

Heating ON 
100% output 
A: Automatic 

 

Programming mode 
(Technician setting) 

or 

 

ºC: Celsius scale 
ºF: Fahrenheit scale 

 

Fan ON 
100% output 
A: Automatic 

 

Alarm status 

 

Minimum/Maximum 
setpoints  

  

 

Dimensions 

A

B

C

D

 

Dimension 

Imperial (in) 

Metric (mm) 

3.00 

78 

3.00 

78 

1.00 

24 

2.36 

60 

 

 

 

Features: 

 

Used to program/configure the EFCB Fan Coil controller 

 

Attractive modern look with large LCD and backlight 

 

Icon-driven information and 1 line of text information 

 

3 wire cable between thermostat and EFCB controller 

 

Selectable Fahrenheit or Celsius scale  

 

Multi-level lockable access menu 

 

Selectable internal or external temperature sensor 

TFL54 

TFLH54-xxx 

 
 
 

 
 
 

 
 

Отзывы: