BT-X8/060303
1
Actuator for smoke damper
Specification
& Installation instruction
Technical Data
BT060X8 BT160X8 BT260X8 BT080X8 BT180X8 BT280X8
Power supply
22 to 26VAC
50/60Hz or 24VDC
110 to 130 VAC
50/60Hz
220 to 250 VAC
50/60Hz
22 to 26VAC
50/60Hz or 24VDC
110 to 130 VAC
50/60Hz
220 to 250 VAC
50/60Hz
Auxiliary switches
No
2 switches rated 250VAC, 5A
switching points: 5˚ & 85˚ +/-5˚
Torque
70 in.lb. [8 Nm] at rated voltage
Fail safe - Enerdrive
Yes
Power consumption
Running 15VA, Holding 5VA
Control signal
2 wire / 2 position
Running time through 90º
20 to 30 sec Torque dependant
Fail safe: 15 sec. max at rated torque.
Electrical connection
18 AWG [0.8mm
2
] minimum
Inlet bushing
2 inlet bushing of 5/8 in [15.9 mm] & 7/8 in [22.2 mm]
Angle of rotation
0 to 90 degrees, mechanically adjustable (factory set with 90º stroke)
Direction of rotation
Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction)
Ambient temperature
Operation
0ºF to +122ºF [-18º C to +50º C]
3 cycles at +250˚F [+121º C]
Storage temperature
-22ºF to +122ºF [-30º C to +50º C]
Relative Humidity
5 to 95 % non condensing.
Enclosure type
NEMA type 2 / IP42
Weight
3 lbs. [1.4 kg]
Warning: Do not press the clutch when actuator is powered
Warning for BT160/260/180/280X8: High Voltage. Risk of electric chock.
Dimensions
A
B
C
D
Dimension Inches
Metric
(mm)
A
1.50 38.1
B
3.26 82.8
C
6.60 167.5
D
3.72 94.5
Caution
We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will
prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
1
Enerdrive System
U.S.A. Patent #5,278,454
BT060X8
BT160X8
BT260X8
BT080X8
BT180X8
BT280X8
Feature:
•
Designed to operate reliably in smoke control systems requiring
Underwriter’s Laboratories UL555S (rated at 250˚F).
•
Mounts easy on round & square shaft (optional).
•
External clutch for manual adjustments.
•
Maintenance
free.
•
Position
indicator.
•
Fail safe by
Enerdrive System
1
•
2 auxiliary switches (only on models 080, 180 & 280)