Neptronic BT000F Скачать руководство пользователя страница 2

BT000F/020F/060F/080F 

Specification & Installation instruction 

 

 

 

Mechanical installation

 

 

1. 

Manually  close  the  damper  blades  and  positioned  the 
actuator at 0º or 90º.

 

2. 

Slide the actuator onto the shaft. 

 

3. 

Tighten  the  nuts  on  the  “U”  bolt  to  the  shaft  with  a  8mm 
wrench to a torque of 60 in.lb. [6,7 Nm].

 

4. 

Slide the mounting bracket under the actuator. Ensure free 
movement  of  the  slot  at  the  base  of  the  actuator.  The 
bracket pin must be placed in the mid distance of the slot.

 

5. 

Fix the bracket to the ductwork with #8 self-tapping screws.

 

 

Wiring Diagrams 

Models BT000F & 020F 

Models BT060F & 080F 

3 wire / 2 position

 

(ON-OFF) 

 

2 wire / 2 position 

(ON-OFF)

 

 

3 wire / 3 point floating

  

 

4 wire / 3 point floating 

 

 

PC Board 

BBT1060A

Dip switch

Reset button

LED

Terminal

1     2     3     4

ON

1  2  3

 

Dip switch settings 
 

 

 

 

Stroke adjustment 

To adjust the stroke, press and release the reset button to start the auto-stroke process. The LED should be illuminated. 

 

First option: 

The actuator will then travel in both directions to find it's limit. 
The LED will extinguish, the process is complete. 

 

Second option:

 

When the desired end position is reached, press and release the reset button. The actuator will now return back to its 
origin position. (you can also press and release the reset button when It's reaches the origin position)  
The LED will extinguish, the process is complete.

 

 

CLUTCH

MOUNTING
BRACKET

COMMON (-)

SUPPLY (+)

DRIVE

CW

1

2

3

4

DRIVE
CCW

COMMON (-)

SUPPLY (+)

DRIVE CW

1

2

3

4

COMMON (-)

SUPPLY (+)

DRIVE

CW

1

2

3

4

DRIVE
CCW

COMMON (-)

SUPPLY (+)

DRIVE

CW

1

2

3

4

DRIVE
CCW

ON

1     2     3

Rotation: CCW

Fail safe return at 90º

Not used

ON

1     2     3

Rotation: CW

Fail safe return at 0º

Not used