background image

 

BM Series Actuators

 

Specification and Installation Instructions

 

 

BM-181119 

     

    

 

 

 

Technical 
Data 

BM

0

0

0

 

BM

0

6

0

 

BM

0

0

0

F

 

BM

0

6

0

F

 

BM

0

0

0

F

F

 

BM

0

6

0

F

F

 

BM

0

2

0

 

BM

0

8

0

 

BM

0

2

0

F

 

BM

0

8

0

F

 

BM

0

2

0

F

F

 

BM

0

8

0

F

F

 

Fail safe

1

 

No 

Yes 

No 

Yes 

No 

Yes 

No 

Yes 

No 

Yes 

No 

Yes 

Power 
consumption 

VA 

15VA 

Peak,6VA 

15 

VA 

24VA 

Peak,15VA 

15 

VA 

24VA 

Peak,15VA 

VA 

15VA 

Peak,6VA 

15 

VA 

24VA 

Peak,15VA 

15 

VA 

24VA 

Peak,15VA 

Torque 

50 in.lb. [5.6 Nm] 

at rated voltage 

35 in.lb. [3.9 Nm] at 

rated voltage 

25 in.lb. [2.8 Nm] at 

rated voltage 

50 in.lb. [5.6 Nm] 

at rated voltage 

35 in.lb. [3.9 Nm] at 

rated voltage 

25 in.lb. [2.8 Nm] at 

rated voltage 

Running time 
through 90º 

20 to 30 sec 

torque dependant 

3.5 to 4.5 sec 

torque dependant 

1.5 to 2.5 sec 

torque dependant 

20 to 30 sec 

torque dependant 

3.5 to 4.5 sec 

torque dependant 

1.5 to 2.5 sec 

torque dependant 

Auxiliary 
switches 

No 

Yes (2) 

Ingress 
protection 

IP22 equivalent to Nema type 2, 

IP54 equivalent to Nema type 3R if water tight inlet bushings 

(not supplied NEP617) are installed 

IP22 equivalent to Nema type 2 

Feedback 

4 to 20 mA or 2 to 10 Vdc adjustable 

Power supply 

22 to 26 Vac or 28 to 32 Vdc 

Electrical 
connection 

18 AWG [0.8 mm

2

] minimum 

Inlet bushing 

2 inlet bushings: 13/16” [20.6mm] 

Control signal 

Analog, Digital or Pulse with modulation (PWM) programmable (factory set with Analog control signal) 

Angle of 
rotation 

0 to 90 degrees, mechanically adjustable (factory set with 90º stroke) 

Direction of 
rotation 

Reversible, Clockwise (CW), or Counterclockwise (CCW) (factory set with CW direction) 

Ambient 
temperature 

-22ºF to 122ºF [-30ºC to 50ºC] 

Storage 
temperature 

-22ºF to 122ºF [-30ºC to 50ºC] 

Relative 
Humidity 

5 to 95 % non condensing. 

Weight 

3 lbs. [1.4 kg] 

Warning: Do not press the clutch when actuator is powered. 

 

Dimensions

 

 
 
 

 

Dimension 

Inches (in) 

Metric (mm) 

1.50 

38.1 

3.64 

92.5 

6.60 

167.5 

model 000 & 060 

3.02 

76.8 

model 020 & 080 

3.81 

96.8 

 

 

                                                 

1

 

Enerdrive System

 U.S.A. Patent #5,278,454

 

 

Features:

 

 

Mounts easy on round & square shaft (with option 

–8) 

 

External clutch for manual adjustments 

 

Maintenance free 

 

Position indicator 

 

Control signal fully programmable 

 

The fastest actuator of the world (model BM_ _ _FF) 

 

Fail safe by 

Enerdrive System

1

 

(on model 060 & 080) 

 

Auxiliary switches (on model 020 & 080) 

BM000 
BM020 
BM060 
BM080 

BM000F 
BM020F 
BM060F 
BM080F 

BM000FF 
BM020FF 
BM060FF 
BM080FF 

Содержание BM000

Страница 1: ... to 10 Vdc adjustable Power supply 22 to 26 Vac or 28 to 32 Vdc Electrical connection 18 AWG 0 8 mm2 minimum Inlet bushing 2 inlet bushings 13 16 20 6mm Control signal Analog Digital or Pulse with modulation PWM programmable factory set with Analog control signal Angle of rotation 0 to 90 degrees mechanically adjustable factory set with 90º stroke Direction of rotation Reversible Clockwise CW or C...

Страница 2: ...bracket pin must be placed in the mid distance of the slot 5 Fix the bracket to the ductwork with 8 self tapping screws Wiring Diagrams Analog For 4 to 20mA control signal connect supplied 500 Ohm resistor between pins 1 and 3 For 2 to 10Vdc feedback signal connect supplied 500 Ohm resistor between pins 1 and 5 PWM 3 wire Digital 2 positions 4 wire Digital 3 point floating Note In Digital Mode the...

Страница 3: ... reset button when it reaches the start position Once this process is complete the LED extinguishes Programming Change of control signal a Remove power and put all dip switches to OFF Default b Apply power and within 10 seconds press and release the reset button The LED should be blinking c Select the control signal with DIP switches DIP Switch Signal Move DS 1 to ON and then OFF Digital On Off or...

Страница 4: ...ibration process starts NOTE Do not hold the reset button for too long as it may cancel the process 3 Apply new minimum voltage It can be any value between 0 to 7 Vdc with an external 0 to 10 volt supply ex MEP 4 Press and release the reset button to memorize the new minimum voltage The LED flashes once and then remains illuminated 5 Apply new maximum voltage It can be any value between 3 to 10 Vd...

Отзывы: