AROB-BACnet Guide_170920 

 

 

Universal Room Controller

 

AROB Series 

BACnet Communication Module User Guide  

 

AROB24T (Temperature sensor) 

AROB24TH (Temperature and Humidity sensors) 

AROB24TGH (Temperature, Humidity, and CO2 sensors) 

AROB24TGVH (Temperature, Humidity, VOC, and CO2 sensors) 

 

 

 

 

Содержание AROB24T

Страница 1: ... Room Controller AROB Series BACnet Communication Module User Guide AROB24T Temperature sensor AROB24TH Temperature and Humidity sensors AROB24TGH Temperature Humidity and CO2 sensors AROB24TGVH Temperature Humidity VOC and CO2 sensors ...

Страница 2: ...roperties Configuration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 6 Object Table Information 7 Analog Input AI 7 Analog Output AO 7 Analog Value AV 8 Binary Input BI 14 Binary Output BO 14 Binary Value BV 14 Multi State Value MSV 18 Notes 22 ...

Страница 3: ...usage_delay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to the device object through BACnet WriteProperty service or the device s Programming Mode The MAC address and the MS TP baud rate setting of 9600 19200 38400 57600 and 76800 are also set throug...

Страница 4: ...lly through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 Therefore its decimal or hexadecimal representation tends to be incomprehensible For example the Device_Instance 1000 has an equivalent Object_Identifier of 0x020003E8 hexadecimal or 33555432 decimal Baud Rate 0 Auto ...

Страница 5: ...t operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing units to occasionally poll for other masters based on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not presen...

Страница 6: ...arting at MAC address 0 and having Max_Master the maximum MAC address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the system Network Reset Reset the controller through BACnet using the Reinitialize Device service The Reinitialize Device service can be accessed using the following pass...

Страница 7: ...gth_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 3000 W Number_of_APDU_Retries Always 3 Protocol_Services_Supported readProperty readPropertyMultiple WriteProperty writePropertyMultiple deviceCommunicationControl reinitializeDevice who Has who Is Protocol_Object_Types_Supported analog input analog output analog value binary input binary output binary value device multi...

Страница 8: ...e Object in Table 2 Device Object Properties Analog Output Description Reliability Min Pres Value Max Pres Value Resolution Present_Value Binary Input Reliability Active_Text Inactive_Text Description Out_of_Service If Out_of_Service is true Present_Value and Status_Flag become writable properties Refer to Out_of_Service Property section on page 6 for more information The object will automatically...

Страница 9: ...reading value on analog input 1 in millivolts Status AI 1 m V is only available for App Profile 0 No Profile manual configuration Read Only 0 to 10 000 millivolts Resolution 1mV AI 4 Status PCB Temp m V Represents the temperature of the printed circuit board in millivolts Read Only 0 to 3 300 millivolts Resolution 1mV AI 5 Status Micro Temp m V Represents the measured temperature of the on board m...

Страница 10: ...Value 32 F to 257 F or 0 C to 125 C AV 6 AV 91 to 257 F 125 C Resolution 0 2 F 0 1 C AV 6 User Heating Unocc Setpoint Configuration value used to set the actual user heating setpoint of the zone in unoccupied operation mode The unoccupied heating setpoint values are restricted by the temperature deadband and unoccupied cooling setpoint Only appears if MSV 18 or MSV 19 is set to OCC or NSB Present ...

Страница 11: ...file 0 No Profile manual configuration is selected Read Only 0 to 100 Resolution 1 AV 25 Status BO 1 Demand Represents the status of the value of binary output 1 value in percentage based on demand Read Only 0 to 100 Resolution 1 AV 26 Status BO 2 Demand Represents the status of the value of binary output 2 value in percentage based on demand The Status BO 2 Demand is available only when App Profi...

Страница 12: ...1 output will no longer modulate and remain at its minimum voltage default 0Vdc Only appears if MSV 18 is set to OAT Sensor Present Value 40 F to 257 F or 40 C to 125 C 40 F 40 C to AV 37 Resolution 0 2 F 0 1 C AV 39 Cfg AO2 Hi OAT Lockout Select the desired high temperature limit for outside air temperature on analog output 2 If the temperature read from the Outside Air Temperature sensor connect...

Страница 13: ... 0 to 100 Resolution 1 AV 54 Cfg BO 1 Hysteresis Low Limit Configuration value that represents the desired binary output 1 hysteresis low percentage The low limit value is restricted by the high limit value The Cfg BO 1 Hysteresis Low Limit only appears if MSV 24 is set to Hysteresis Mode Present Value 0 to 100 0 to AV 55 Resolution 1 AV 55 Cfg BO 1 Hysteresis Hi Limit Configuration value that rep...

Страница 14: ...lue 32 F to 257 F or 0 C to 125 C AV 70 to 257 F 125 C Resolution 0 2 F 0 1 C AV 72 Cfg Cooling Unocc setpoint min Configuration value that represents the minimum cooling setpoint value used during no occupancy The minimum cooling setpoint during no occupancy value is restricted by the maximum cooling setpoint during no occupancy value Only appears if MSV 18 or MSV 19 is set to OCC or NSB Present ...

Страница 15: ...t min requires a functioning VOC sensor installed Present Value 0 to 1 000 PPB 0 PPB to AV 85 Resolution 1 PPB AV 85 Cfg VOC Setpoint max Configuration value that represents the value set as the maximum VOC setpoint The maximum VOC setpoint is restricted by the minimum VOC setpoint The Cfg VOC Setpoint max requires a functioning VOC sensor installed Present Value 0 to 1 000 PPB AV 84 to 1 000 PPB ...

Страница 16: ...t 2 0 Open 1 Close The Status BO 2 is only available for App Profile 0 No Profile manual configuration Present Value Relinquish Default 0 Open 1 Close Binary Value BV Table 9 Object Table Information Binary Value BV ID Name Description W Notes Integrator BV 1 Status Occupancy Status Represents the occupancy status based on AI1 or BI1 set to Occupancy or Night Setback 0 No 1 Yes Read Only 0 No 1 Ye...

Страница 17: ...s BV 11 CfgDisplayTempLevel Display Temp in RUN mode 0 No 1 Yes Present Value 0 No 1 Yes BV 12 CfgDisplayHumidityLevel Display RH in RUN mode 0 No 1 Yes The CfgDisplayHumidityLevel requires a functioning humidity sensor installed Present Value 0 No 1 Yes BV 16 Cfg Enable Backlight Represents the desired status of LCD backlight 0 Off 1 On Present Value 0 Off 1 On BV 17 Cfg Enable Auto Scroll Repres...

Страница 18: ...sent Value 0 No 1 Yes BV 28 Cfg FAN Command AO 1 Represents the status of the fan command for Analog Output 1 0 No 1 Yes If you select No Profile as the App Profile the Cfg FAN Command AO 1 becomes writable Present Value 0 No 1 Yes BV 29 Cfg Cooling Command AO 2 Represents the status of the cooling command for Analog Output 2 0 No 1 Yes The Cfg Cooling Command AO 2 is only available for App Profil...

Страница 19: ...inary Output 1 0 No 1 Yes If you select No Profile as the App Profile the Cfg Humidification Command BO 1 becomes writable The Cfg Humidification Command BO 1 requires a functioning humidity sensor installed Present Value 0 No 1 Yes BV 40 Cfg CO 2 Command BO 1 Represents the status of the CO2 command for Binary Output 1 0 No 1 Yes If you select No Profile as the App Profile the Cfg CO 2 Command BO...

Страница 20: ... of the fan command for Binary Output 2 0 No 1 Yes The Cfg FAN Command BO 2 is only available for App Profile 0 No Profile manual configuration Present Value 0 No 1 Yes Multi State Value MSV Table 10 Object Table Information Multi State Value MSV ID Name Description W Notes Integrator MSV 1 User main system mode Status of the actual mode selected This value can be changed via AROB and or BACnet Of...

Страница 21: ...alue is 0 to 10 Vdc unless the minimum and maximum values were changed at AV 33 and AV 34 Present Value Highest Average MSV 9 Cfg AO 2 Control Mode Configuration value used to set the Analog Output 2 control mode Highest Controller compares all the assigned input values and uses the highest value to calculate the AO2 ramp output value Average Controller compares all the assigned input values and u...

Страница 22: ...Controller activates an alarm to indicate that there is no airflow Air Flow Lockout Controller activates an alarm to indicate that there is no airflow The controller shuts off all outputs Present Value Off OAT Sensor Occupancy Night Setback Dirty Filter Air Flow Switch Air Flow Lockout MSV 19 Cfg BI 1 config Configuration value to select the input signal type for Binary Input 1 BI1 OFF Controller ...

Страница 23: ...h 8 cycles per hour such that 1 cycle 7 5 minutes TPM CPH 4 The Time Proportional Modulation is achieved with 4 cycles per hour such that 1 cycle 15 minutes TPM CPH 3 The Time Proportional Modulation is achieved with 3 cycles per hour such that 1 cycle 20 minutes Present Value TPM CPH 8 TPM CPH 4 TPM CPH 3 MSV 27 Cfg BO 2 TPM CPH Configuration value used to set the desired binary output 2 TPM cycl...

Страница 24: ...ebeau Blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm Eastern time ...