1. INTRODUCTION 

 

1.1  Greeting

 

Thank you for choosing the BDM-500 micro inverter from NEP. This product will 

maximize  your  inversion  bene

t  with  the  minimal  amount  of  design  and 

installa

on  complexity.  This  document  should  provide  you  with  all  of  the 

necessary steps to correctly install  the NEP-500 dual module  micro  inverter in 

sites located in North America.  However, should you have addi

onal ques

ons 

please contact NEP’s technical representa

ve at [email protected]

1.2  System Compatibility

 

The BDM-500 is designed to support either one or two 60 or 72 cell modules in 

grid-

ed PV system consists of PV panels, grid-

ed inverter and junc

on boxes. 

The DC output from the PV panels is converted into AC energy and fedback to the 

grid  through  the  BDM-500.  The  BDM-500  also  provides  e

ec

ve  an

-islanding 

isola

on between the PV module and AC grid output.   

1.3 How to Use This Manual 

 

This manual provides detailed product informa

on and installa

on instruc

ons 

for  the  BDM-500micro  solar  inverter.  Please  read  through  this  manual  before 

installa

on and opera

on. 

 

WARNING:

  This  indicates  a  situa

on  where  failure  to  follow  instruc

ons 

may be a safety hazard or cause equipment malfunc

on. Use extreme cau

on 

and follow instruc

ons carefully.   

1.4 Label  

 

A label is located on the side of the inverter which includes technical data as well 

as  type  and  serial  number  of  the  device.  Safety  instruc

ons  are  listed  and 

explained below: 

 

Danger!     

The term “danger” describes an issue which, if ignored can cause 

personal injury.

 

 

A

en

on!     

With  the  term  “a

en

on”  a  circumstance  is  listed  which  may 

cause property damage if disregarded.

 

 

Instruc

ons for use! 

Under “Instruc

ons for Use“, it is pointed out that installa

on and 

opera

ng  instruc

ons  are  to  be  read  and  understood  before 

installa

on or repair. 

 

Cau

on, hot surface!     

Under “Cau

on, hot surface”, it should be noted that surfaces of 

equipment may be hot and create a burn hazard. 

 

Special disposal instruc

ons! 

With “Note Separate Disposal”, it is pointed out that this product 

may  not  be  disposed  of  with  normal  garbage.  An  improperly 

conducted disposal can lead to damage to the environment.

 

 

ETL Cer

�fi

ca

on 

This  marks  cer

�fi

es  that  the  product  complies  with  all  relevant   

UL requirements for sale in North America. 

2. SAFETY INSTRUCTION

 

WARNING:

 

PLEASE READ THIS MANUAL PRIOR TO INSTALLATION. PRODUCT DAMAGE RESULTING FROM FAILURE 

TOFOLLOW THIS MANUAL IS NOT COVERED BY THE WARRANTEE.   

INSTALLATIONS SHOULD BE DONE ONLY BY CERTIFIED ELECTRICIANS. 

NOTHING INSIDE THE INVERTER SHOULD BE MODIFIED 

ONLY NEP APPROVED CABLING SHOULD BE USED TO CONNECT MICROINVERTERS   
ALL  INSTALLATIONS  SHOULD  FOLLOW  THE  LOCAL  ELECTRICAL  CODES.  ADDITIONAL  PROTECTION  FOR  THE  AC 

WIRING FROM THE INVERTERS SHOULD BE PROVIDED AND MAY BE REQUIRED BY LOCAL AND NATIONAL WIRING 

REGULATIONS. THIS PROTECTION IS LIKELY TO INCLUDE RESIDUAL CURRENT DEVICES, EARTH FAULT MONITORS 

AND  CIRCUIT  BREAKERS.  THIS  PRODUCT  MAY  CAUSE  AC  CURRENT  WITH  A  DC  COMPONENT.  IF  A  RESIDUAL 

CURRENT-OPERATED PROTECTIVE DEVICE (RCD) OR A MONITORING DEVICE (RCM) IS USED FOR PROTECTION IN 

CASE OF DIRECT OR INDIRECT CONTACT, ONLY AN RCD OR RCM OF TYPE B IS ALLOWED ON THE AC SIDE OF THIS 

PRODUCT

 

NEVER DISCONNECT THE PV MODULES FROM THE MICRO-INVERTER WITHOUT FIRST ISOLATING THE AC MAINS.   

ALL PV AND AC CONNECTORS ARE NOT TO BE DISCONNECTED UNDER LOAD. THE AC BRANCH CIRCUIT BREAKERS 

MUST BE FIRST SWITCHED OFF. 
PLEASE CONTACT AUTHORIZED SERVICE AGENTS FOR ANY SERVICE WORK. 

BDM-500 IS A GRID-TIED SOLAR INVERTER.  IT MAY REQUIRE APPROVAL FROM THE LOCAL UTILITY COMPANY 

PRIOR TO CONNECTION TO THE POWER GRID. 

THE BDM-500 DOES NOT INCLUDE ANY USER SERVICABLE COMPONENTS. 

WARNING: 

THE PV ARRAY SUPPLIES A DC VOLTAGE TO THE MICROINVERTER WHEN EXPOSED TO 

LIGHT.

 

3. FCC COMPLIANCE

 

This  equipment  has  been  tested  and  found  to  comply  with  the  limits  for  a  Class  B  digital 

device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable 

protec

on against harmful interference in a residen

al installa

on. This equipment generates 

uses and can radiate radio frequency energy and, if not installed and used in accordance with 

the instruc

ons, may cause harmful interference to radio communica

ons. However, there is 

no  guarantee  that  interference  will  not  occur  in  a  par

�c

ular  installa

on.  If  this  equipment 

does cause harmful interference to radio or television recep

on, which can be determined by 

turning the equipment o

 and on, the user is encouraged to try to correct the interference by 

one or more of the following measures:     

 Reorient or relocate the receiving antenna.   

 Increase the separa

on between the equipment and the receiver.   

 Connect the equipment into an outlet on a circuit di

erent from that to   

which the receiver is connected.   

 Consult the dealer or an experienced radio/TV technician for help.   

Changes or modi

fic

a

ons not expressly approved by the party responsible for compliance may 

void the user’s authority to operate the equipment.   

 

02 

Содержание BDM-500

Страница 1: ...TEL 81 092 433 3252 FAX 81 092 433 3171 China Address No 1 Anhe Rd Tsingtao Export Processing Zone Tsingtao China 266113 TEL 86 532 87963900 FAX 86 532 81100917 Email info northernep com Web h p www northernep com h p www nep japan com h p www micro inverter jp Rev 2017 01 12 Dual Module Macroinverter BDM 500 Installation and Operation Manual ...

Страница 2: ...Shipping Information 05 6 INSTALLATION 05 6 1 Pre installation 05 6 2 Installation Steps 06 Step 1 System Layout 06 Step 2 Connect theWiring Harnesses 07 Step 3 Install the AC Branch Circuit Junction Box 08 Step 4 Ground the System 08 Step 5 Complete the Connection Map 09 Step 6 Connect the PV Modules 09 Step 7 Install the BDG 256 Monitoring Gateway 09 7 COMMISSIONING 10 8 OPERATING INSTRUCTIONS 1...

Страница 3: ... fields of power electronics automa c control signal processing and communica ons each holding mul ple U S and world patents in their specialty areas NEP has a complete product line of grid ed solar inverters including 180W 600W micro inverters 1 5kW 5kW single phase solar inverters 10kW 500kW three phase solar inverters and rapid shutdown devices Field deployment results demonstrated high system e...

Страница 4: ...OW THIS MANUAL IS NOT COVERED BY THE WARRANTEE INSTALLATIONS SHOULD BE DONE ONLY BY CERTIFIED ELECTRICIANS NOTHING INSIDE THE INVERTER SHOULD BE MODIFIED ONLY NEP APPROVED CABLING SHOULD BE USED TO CONNECT MICROINVERTERS ALL INSTALLATIONS SHOULD FOLLOW THE LOCAL ELECTRICAL CODES ADDITIONAL PROTECTION FOR THE AC WIRING FROM THE INVERTERS SHOULD BE PROVIDED AND MAY BE REQUIRED BY LOCAL AND NATIONAL ...

Страница 5: ... parts MLPE rail or frame a ach clamps 2 per microinverter AC junc on boxes mul ple op ons possible Cordgrip with locknut or strain relief fi ng one per branch circuit A subpanel may be required for systems with mul ple branch circuits Cable clips Sockets wrenches torque wrench mul meter small flat head screwdriver and mirror with extension rod Lightning and surge suppressor recommended 5 3 Lightnin...

Страница 6: ... PROTECTIVE END CAPS HAVE BEEN INSTALLED ON ALL UNUSED AC CONNECTORS UNUSED AC BDM 500 WIRE HARNESS CONNECTORS ARE LIVE WHEN THE SYSTEM IS ENERGIZED The AC branch circuit should look as pictured below 7 6 2 Installation Steps WARNING CONNECT BDM 500S TO THE ELECTRICAL UTILITY GRID ONLY AFTER RECEIVING PRIOR APPROVAL FROM THE UTILITY COMPANYAND LOCAL AHJ WARNING BE AWARE THAT ONLY QUALIFIED PERSONN...

Страница 7: ...ay from the map you create Step6 Connect the PV Modules Connect all AC all system inter wiring connec ons prior to installing the PV modules 1 Mount the PV modules in the posi ons corresponding to their associated BDM 500 microinverter Each BDM 500 comes with two sets of oppositely sexed DC connectors 2 Connect the posi ve DC wire from the first PV module to the nega vely marked DC connector male p...

Страница 8: ...ommunica ng to the BDG 256 Green communica ng to the BDG 256 11 Status grounding fault The LED light is in solid red color In case of a fault the BDM 500 enters a protec ve mode and stops output ng power The fault message is usually sent to a connected BDG 256 gateway through the power line communica on The error message is then displayed on the screen of BDG 256 gateway by a 16 bit error code The...

Страница 9: ...may be installed to reduce the interference to PLC communica on If there are two or more separate BDM systems close by it is highly recommended to install LCF for each micro inverter system to block interference from adjacent other systems 7 If the problem persists please call customer support at NEP WARNING DO NOT ATTEMPT TO REPAIR THE BDM 500 IT CONTAINS NO USER SERVICEABLE PARTS IF TROUBLESHOOT...

Страница 10: ...3 at rated power 3 at rated power 3 at rated power Power Factor 0 99 at rated power 0 99 at rated power 0 99 at rated power SYSTEM EFFICIENCY CEC Efficiency 95 5 95 5 95 5 Night Time Tire Loss W 0 11 0 11 0 11 PROTECTION FUNCTIONS Over Under Voltage Protec on Yes Yes Yes Over Under Frequency Protec on Yes Yes Yes An Islanding Protec on Yes Yes Yes Over Current Protec on Yes Yes Yes Reverse DC Polari...

Страница 11: ...n biological infesta ons or input voltage that creates opera ng condi ons beyond the maximum or minimum limits listed in the NEP product specifica ons including high input voltage from generators and lightning strikes c the product if repairs have been done to it other than by NEP or its authorized service centers herea er ASCs d the product if it is used as a component part of a product expressly ...

Страница 12: ... s or Code s Brief Fault Descrip on and Photos monitoring gateway is required for verifica on Installa on Informa on Modules Used Modules Quan ty Inverters quan ty per string Installa on Company Name Installer Name For the informa on on our warranty terms and condi ons please see our website www northernep com en All fields must be completed in order to process claim Customer Signature Date All righ...

Страница 13: ...12 0011 福岡市博多区博多駅前 3 10 24 藤井ビル 1F TEL 81 092 433 3252 FAX 81 092 433 3171 China Address No 1 Anhe Rd Tsingtao Export Processing Zone Tsingtao China 266113 TEL 86 532 87963900 FAX 86 532 81100917 Email info northernep com Web h p www northernep com h p www nep japan com h p www micro inverter jp ...

Отзывы: