2

  Table 1 - Specifications

Inputs

Tank level switches 

(2) Normally-Closed. Can be used with a single level switch.

Inlet pressure switch 

Normally-Open.

Pretreat lockout switch 

Normally-Open.

 

The Tank, Low Pressure and Pretreat inputs are 50% duty cycle square wave, 

10VDC peak @ 10mA max.

 

The switch inputs are dry contacts only. Applying voltage to these terminals 

will damage the controller.

Controller Power 

110-120/208-240 VAC, 60/50Hz (Range: 110-240 VAC)

Permeate Conductivity  

0-3000 PPM, 0-6000 μs (standard sensor, CP-1, K=.75)

Feed Conductivity (opt)  

0-3000 PPM, 0-6000 μs (standard sensor, CP-1, K=.75)

Output Circuit Ratings

Feed Solenoid 

1A. Voltage is the same as motor/supply voltage.

Flush Solenoid  

1A. Voltage is the same as motor/supply voltage.

Motor 

1.0 HP/110-120V, 2.0 HP/208-240V.

Circuit Protection

Relay Fuse  

F1 5x20mm   -   2 Amp   -   BelFuse 5ST 2-R

 

Note: The fuses shown above are for supplemental protection only. Branch 

circuit protection and disconnect means must be provided externally.

 

See Field Wiring Diagram for Branch Circuit protection requirements.

Other

Dimensions 

7" tall, 7" wide, 4" deep. Nema 4X Polycarbonate Hinged Enclosure.

Weight 

2.6 lb. (Basic Configuration, not including optional wire harness, etc.)

Environment 

0-50°C, 10-90%RH (non-condensing)

 

Note: After our modifications the enclosure rating is Nema 1.

Содержание NRO ROC2HE-UL

Страница 1: ...Nelsen NRO ROC2HE UL System Controller Documentation Systems w CPU 4 Control Board Manufactured after March 2020 Since 1954...

Страница 2: ......

Страница 3: ...Controller Detail TB 1 6 Conductivity Probe Installation Figure 5 7 Installation Instructions 7 Controller Programming Accessing Hidden Menus Figure 6 8 System Start up w Permeate Flush 8 Controller...

Страница 4: ...0 6000 s standard sensor CP 1 K 75 Output Circuit Ratings Feed Solenoid 1A Voltage is the same as motor supply voltage Flush Solenoid 1A Voltage is the same as motor supply voltage Motor 1 0 HP 110 12...

Страница 5: ...3 Figure 1 Simplified Schematic...

Страница 6: ...ard CPU 4 Conductivity Probe Connections Display 4 line 20 character Clear concise feedback on the RO s status Alarm Display backlight flashes along with audible beeper to indicate alarm condition Key...

Страница 7: ...5 Typical Configuration Permeate Conductivity Probe Shield White Black Cable to Terminal Board Figure 3 Controller Detail CPU 4 Typical Configuration...

Страница 8: ...6 Figure 4 Controller Detail Terminal Board TB 1 See Fig 1 for schematic...

Страница 9: ...the System On Off switch to turn the system ON 10 Program Mode 2 is default See Table 2 which is a general purpose setting without a flush valve NOTE The Program Settings can be customized to suit the...

Страница 10: ...ith the system on Press and Hold the Up and Down Arrows 2 With the Up and Down Arrows depressed Press the System On Off button This will switch to the Hidden Menus as shown above 3 If not already on t...

Страница 11: ...op delay Seconds 1 1 1 1 Pump start retry interval restart delay after LP fault Seconds 60 60 60 60 Low pressure fault shutdown of faults Faults 5 5 5 5 Low pressure fault shutdown time period to coun...

Страница 12: ...10 Figure 7 Controller Programming Menu Navigation...

Страница 13: ...d xxx uS Line 3 Alarm SP xxx ppm or Alarm SP xxx uS Line 4 To Reset Push OFF ON Feed Conductivity Fault Feed conductivity is higher than the alarm set point Line 1 Service Fault Line 2 Feed TDS xxx pp...

Страница 14: ...th a multi meter for correct on off operation Replace switch or level control if faulty 3 If someone connected 110v to the terminal strip connection for the high level shut off they could have fried t...

Страница 15: ...facturer s warranties on the Product or any parts therein subject to the conditions and exclusions in the manufacturer s warranty Buyer s exclusive remedy under such third party manufacturer s warrant...

Страница 16: ...ATION THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE NO REPRESENTATIONS OR WARRANTIES AT ANY TIME MADE BY ANY EMPLOYEE AGENT OR REPRESENTATIVE OF NELSEN SHALL BE EFFECT...

Отзывы: