The controller has 4 separate user-selectable sets of settings for configuring the RO. The factory default
settings are shown below. The settings are identical except for variations in the flush behavior.
• 

Program 1

High Pressure flush

• 

Program 2

No Flush

• 

Program 3

Permeate Flush, (low pressure, inlet valve closed)

• 

Program 4

Low Pressure, feed water flush

• See the previous page for instructions on how to access the menu for selecting these programs.
• See Appendix A for a detailed explanation of the Parameters and their affect on the RO’s operation.

  Table 2 - Controller Programming:  

ROC-2 Program Selections

Parameter

  

Value  

Program 1   Program 2   Program 3   Program 4

Tank Level Switch delay (actuation and de-actuation)  Seconds 

2 2 2 2

Pressure Switch delay (actuation and de-actuation)  

Seconds 

2 2 2 2

Pretreat Switch delay (actuation and de-actuation)  

Seconds  

2  

2  

2  

2

Pump start delay  

Seconds  

10  

10  

10  

10

Inlet Solenid stop delay  

Seconds  

1  

1  

1  

1

Pump start retry interval (restart delay after LP fault)   Seconds  

60  

60  

60  

60

Low pressure fault shutdown, # of faults  

Faults  

5  

5  

5  

5

Low pressure fault shutdown, time period to count faults  

Minutes  

10  

10  

10  

10

Low pressure fault shutdown, reset after shutdown  

Minutes  

60  

60  

60  

60

Low pressure timeout fault  

Seconds 

60 60 60 60

Flush Behavior

  

 

 

 

Extra 

Maximum 

 

 

   

 

Normal  

No Flush 

Flush 

Flush

Startup Flush: Minutes from last flush  

Minutes 

0

Startup Flush: Duration  

Seconds  

0  

0  

0  

30

Periodic Flush: Interval  

Minutes  

60  

0  

0  

0

Periodic Flush: Duration  

Seconds  

30  

0  

0  

0

Shutdown Flush: Time from last flush  

Minutes 

10 

0

Shutdown Flush: Minumum operation  

Minutes  

30  

0  

0

Shutdown Flush: Duration  

Seconds  

60  

0  

60  

60

Idle Flush: Interval *  

Minutes  

0  

0  

0  

0

Idle Flush: Duration *  

Seconds  

0  

0  

0  

0

Timed Manual Run  

Minutes  

5  

5  

5  

5

Timed Manual Flush  

Minutes  

5  

0  

5  

5

*  These features are disabled by default due to the potential for confusion on the part of end-users in the field. 

They can be enabled when needed via the OEM PC programming interface which allows changes to all of 

the values shown above.

Содержание NRO ROC-3HE

Страница 1: ...Nelsen NRO ROC 3HE System Controller Documentation Systems with 3 hp Motors and Above...

Страница 2: ...CPU 4 5 Controller Detail TB 6 6 Conductivity Probe Installation Figure 5 7 Controller Programming Accessing Hidden Menus Figure 6 8 System Start up w Permeate Flush 8 Controller Programming Program...

Страница 3: ...y Ratings relays are fused with a 6A fuse Feed Solenoid 0 5A Voltage is the same as motor supply voltage Flush Solenoid 0 5A Voltage is the same as motor supply voltage Motor Contactor Coil 0 5A Volta...

Страница 4: ...2 Figure 1 Simplified Schematic...

Страница 5: ...3 Figure 1 1 Field Wiring Diagram...

Страница 6: ...al Run Manual Flush Supply Power Connections Motor Connections Terminal Board CPU4 Board Conductivity Probe Connections Display 4 line 20 character Clear concise feedback on the RO s status Alarm Disp...

Страница 7: ...5 Typical Configuration Figure 3 Controller Detail CPU 4 Typical Configuration...

Страница 8: ...6 Figure 4 Controller Detail Terminal Board TB 1 See Fig 1 for schematic...

Страница 9: ...ductivity Probe Installation Install the Conductivity Probe in the Run of a Tee or equivalent location Orient the probe so that air can not become trapped in the area near the probe F L O W FLOW Condu...

Страница 10: ...m On Off button This will switch to the Hidden Menus as shown above 3 If not already on the RO Presets Program Press the Up or Down Arrows until you reach this screen 4 Once on the RO Presets Program...

Страница 11: ...stop delay Seconds 1 1 1 1 Pump start retry interval restart delay after LP fault Seconds 60 60 60 60 Low pressure fault shutdown of faults Faults 5 5 5 5 Low pressure fault shutdown time period to c...

Страница 12: ...ng against a closed suction as the pump spins down Low Inlet Pressure Behaviors Pump start retry interval restart delay after LP fault Seconds 60 When the inlet pressure switch opens the controller de...

Страница 13: ...ts the duration of the Idle Flush 0 disabled Timed Manual Run Duration of Manual Run Minutes 5 Timed Manual Flush Duration of Manual Flush Minutes 5 Conductivity Probe Sample Rate Seconds 2 Conductivi...

Страница 14: ...t If RO Not Working and Display Shows Tank Full or Tank Full Draw Down 1 If using a single point high level float switch the jumper in the wiring instructions must be installed This needs to be checke...

Страница 15: ...ing Programming Interface Overview The Programming interface is a Windows based tool for making changes to the ROC software This screen shows the RO settings available There are 4 field selectable set...

Страница 16: ...rvice 1 To obtain warranty service contact your selling dealer for a Return Material Authorization RMA 2 You will be required to provide a Your name and address b A description of the problem 3 Packag...

Отзывы: