background image

Operating modes

2

Safe operation is possible provided that the
underpressure in the room where the
burner is installed does not exceed 4 Pa
(0.04 mbar).

This can be achieved if combustion air can
flow through non-lockable openings, e.g. in
doors, windows and via the air-
intake/exhaust-air wall box or by other
technical measures, such as reciprocal
interlocking, etc.

If the air intake is inadequate, there is a
risk of poisoning from combustion gases
which are drawn back into the room.

An air-intake/exhaust-air wall box by itself
is no guarantee that the limiting value will
not be exceeded.

Note: When assessing the overall
requirement, the combined ventilation
system for the entire household must be
taken into consideration. This rule does not
apply to the use of cooking appliances,
such as hobs and ovens.

Unrestricted operation is possible if the
extractor hood is used in recirculating
mode – with activated carbon filter.

If no activated carbon filter is installed, 

it is not possible to bind the odorous 
substances in the cooking vapours.

Exhaust-air mode:

The extractor-hood fan extracts the kit-
chen vapours and conveys them
through the grease filter into the atmos-
phere.

The grease filter absorbs the solid 
particles in the kitchen vapours.

The kitchen is kept almost free of grease
and odours.

Circulating-air mode

An activated carbon filter must be fitted
for this operating mode (see Filters and
maintenance).

Activated carbon filters can be 
purchased from specialist outlets 

(see Optional accessories on the last 
page).

The ventilator fan draws the vapours
produced during cooking into the 
extractor hood, where they pass
through the grease filter and the activa-
ted carbon filter before the clean air is
discharged back into the kitchen.

The grease filter absorbs the grease
contained in the vapours produced
during cooking.

The activated carbon filter absorbs any
odorous substances.

D

When the extractor hood is operated

in exhaust-air mode simultaneously
with a different burner which also
makes use of the same chimney

(such as gas, oil or coal-fired heaters,
continuous-flow heaters, hot-water boi-
lers) care must be taken to

ensure that

there is an adequate supply of fresh
air 

which will be needed by the burner

for combustion.

Operation Instructions

5750.197 475-en  28.09.2004  8:09 Uhr  Seite 2

Содержание D5625

Страница 1: ...Installation instructions and how to use and look after your built in cooker hoods D5625 22 45 and D5855 NEFF UK Ltd...

Страница 2: ...ing vapours Exhaust air mode The extractor hood fan extracts the kit chen vapours and conveys them through the grease filter into the atmos phere The grease filter absorbs the solid particles in the k...

Страница 3: ...you are cooking with fat or oil e g chips etc never leave the cooker unattended Do not flamb food directly under the extractor hood Risk of grease filter catching fire due to flames Before using your...

Страница 4: ...er the filter becomes increasingly inflammable The efficiency of the extractor hood can also be adversely affected Important Renewing the fleece filter at appropriate intervals prevents the possibilit...

Страница 5: ...filter Under normal operating conditions 1 to 2 hours per day the metal grease filter will require cleaning after 8 to 10 weeks The filter can be cleaned in a dishwasher This can however cause slight...

Страница 6: ...ease filter by pulling it towards yourself 2 Clean the grease filters 3 Re insert the clean grease filters Removing and installing the activa ted carbon filter Extractor hoods with a filter mat 1 Remo...

Страница 7: ...ssories on the last page Use original filters only This will ensure optimum performance Disposing of the old activated carbon filter Activated carbon filters do not contain any pollutants They can be...

Страница 8: ...off with a damp cloth Do not use scouring agents Warning Clean the control buttons with a mild detergent solution and a soft damp cloth only Painted aluminium and plastic surfaces Do not use scouring...

Страница 9: ...ff there is still a risk of burns 2 Remove the bulb ring with a screwdriver or similar tool 3 Replace the halogen light bulb conventional halogen bulb 12 Volt max 20 Watt G4 cap Caution Refer to for p...

Страница 10: ...d must not be installed over a solid fuel cooker a potential fire hazard e g flying sparks unless the cooker features a closed non removable cover and all national regulations are observed The smaller...

Страница 11: ...ow through non closeable openings such as in doors windows wall ventilation boxes or by alternative technical measures such as reci procally shutting the other device off etc If the air intake is inad...

Страница 12: ...page into the air pipe connector and then attach the exhaust air pipe 120 mm extraction pipe Attach the exhaust air pipe directly to the air pipe connector Extractor hoods with 150 mm air outlet 150 m...

Страница 13: ...d person in order to prevent a hazardous situation Improper repairs may put the user at considerable risk Length of connection cable 1 20 m Electrical specifications The electrical specifications can...

Страница 14: ...48 100 35 225 min 15 m in 15 500 3 16 352 3 Extractor hood with slide control 73 cm wide 1 and 2 motor 9 346 160 55 95 150 120 348 348 100 35 225 380 730 min 15 m in 15 16 352 3 700 3 Installation 310...

Страница 15: ...s 1 Loosen the screws 2 Hold the underside of the extractor hood Hold the underside of the extrac tor hood 3 Lower the extractor hood and remove Installation Installation spring Weight in kg Width 53...

Страница 16: ...280 530 280 530 380 530 730 380 530 730 280 530 380 530 730 380 530 730 380 530 730 380 530 730 Z 5154X0 Z 5155X0 461423 481051 095660 5750 197475 Printed in Germany 1004 Hi...

Отзывы: