NCF
15
EN
NCF 30/15
NCF 30/20
NCF 30/25
NCF 40/25
NCF 50/25
NCF 80/20
NCF 120/15 NCF 120/25 NCF 160/25
Ambient
temperature (°C)
30 to +40
30 to +40
30 to +40
30 to +40
30 to +40
30 to +40
30 to +40
30 to +40
-30 ºC to
+40 ºC
See Figure 2.
3.1.3
Technical data 60 Hz fans, 380 V (metric)
Table 3-3: Technical data 60 Hz fans (metric)
NCF 30/15
NCF 30/20
NCF 30/25
NCF 40/25
NCF 50/25
NCF 80/20 NCF 120/25 NCF 120/25 NCF 160/25
Capacity (m
3
/h)
830 - 6000
910 - 6550
800 - 5600
1600 - 8540 2340 - 11650
2650 - 17140
Total pressure
(Pa)
2540 - 870
3640 - 1320 4540 - 1570 3170 - 1020 5260 - 1700
5060 - 1870
Motor power
(kW)
4,0
5,5
5,5
7,5
15
18,5
Speed (r/min)
3535
3510
3520
3550
3550
3560
Voltage (V)
Current (A)
380∆
8,2
380∆
10,8
380∆
10,8
380∆
14,5
380∆
27,9
380∆
34
Frequency (Hz)
60
60
60
60
60
60
Phase
3 phase
3 phase
3 phase
3 phase
3 phase
3 phase
Starting
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
6-7 x rated
current
Protection
IP 55
IP 55
IP 55
IP 55
IP 55
IP 55
Weight (kg)
105
110
112
150
232
292
Working
temperature (°C)
Maximum
+ 60
Maximum
+ 60
Maximum
+ 60
Maximum
+ 60
Maximum
+ 60
Maximum
+ 60
Ambient
temperature (°C)
-30 to +40
-30 to +40
-30 to +40
-30 to +40
-30 to +40
-30 to +40
See Figure 2.
3.1.4
Technical data 60 Hz fans (imperial)
Table 3-4: Technical data 60 Hz fans (imperial)
NCF 30/15
NCF 30/20
NCF 30/25
NCF 40/25
NCF 50/25
NCF 80/20 NCF 120/15 NCF 120/25 NCF 160/25
Capacity (cfm)
315 -
2466
410 -
2540
490 -
3535
535 -
3855
470 -
3300
940 -
5025
1530 -
8230
1375 -
6855
1560 -
10090
Total pressure
(in w.g.)
7.9 - 2.3
11.6 - 3.8
in w.g
10.2 - 3.5
14.6 - 5.3
18.2 - 6.3
12.7 - 4.1
14.4 - 4.7
21.1 - 6.8
20.3 - 7.5
Motor power
(hp)
3.0 hp
4.0 hp
5.5 hp
7.5 hp
7.5 hp
10 hp
15 hp
20 hp
25 hp
Speed (r/min)
3500 r/min
3515 r/min
3535 r/min
3510 r/min
3520 r/min
3550 r/min
3540 r/min
3550 r/min
3560 r/min
Voltage (V)
Current (A)
208
8.6
208
11.5
208
15.1
208
18.7
208
18.7
208
26.2
208
38.4
208
52
208
66.4
Voltage (V)
Current (A)
230YY/460Y
7.8/3.9
230YY/460Y
10.4/5.2
230ΔΔ/460Δ
13.6/6.8
230ΔΔ/460Δ
17/8.5
230ΔΔ/460Δ
17/8.5
230ΔΔ/460Δ
23.8/11.9
230ΔΔ/460Δ
34.8/17.4
230ΔΔ/460Δ
46.8/23.4
230ΔΔ/460Δ
60/30
Voltage (V)
Current (A)
575 V
3.1 A
575 V
4.2 A
575 V
5.5 A
575 V
6.8 A
575 V
6.8 A
575 V
9.5 A
575 V
11.0 A
575 V
19.4 A
575 V
24 A
See Figure 2.
Содержание NCF
Страница 2: ...NCF 2 ...
Страница 3: ...NCF 3 Declaration of conformity 4 Figures 5 English 9 ...
Страница 6: ...NCF 6 4 Standard outlet position 5 ...
Страница 7: ...NCF 7 Example of lifting NCF fans Minimum installation distances with intake pipe 6 7 ...
Страница 24: ......
Страница 25: ...www nederman com ...