MACE | INSTALLATION GUIDE
Connections
8/30
3.2.3
WIEGAND
The Wiegand and Magstripe ISO7811/2 (clock & data) interface share the same
connections. This means that only Wiegand or Magstripe can be used and not both
simulaneously.
Wiegand connections:
GRAY
D0
PINK
D1
BLACK
Ground (0V)
SHIELD
Shield connected to DC-ground.
Message format:
The Wiegand output format is determined by the programming format of the
credential. MACE Wiegand credentials will automatically generate a Wiegand
message. If the credential is not programmed in Wiegand format, you may configure
the message output format as described in chapter 4.5.2.
Make sure to order the correct credential programming format if you want to use the
Wiegand or Magstripe interface. See also the MACE how to order guide (HTOG) for
more information.
Wiegand Timing
In the figure below the Wiegand protocol timing is specified.
Tpw
5V
0V
D1
5V
0V
D0
Tpi
Tpi
Tpw
Figure 3: Wiegand protocol timing
Timing constants:
Tpi
Pulse interval time
1msec
Tpw
Pulse width time
50µsec
Note
Extending these
connections beyond the 5
meter pig tail length shall
ONLY be allowed using
shielded cable (4 x 0.25
mm2) as long as the total
length is shorter than 150
meters (500 feet).
The shield shall be
connected to the metal
case of the external device.