www.nedap-luxon.com
1.
Open the wiring compartment after loosening the two screws on the front.
2.
Enter the mains cable through the left wire gland.
3.
Connect L and N wire to corresponding terminals, no earth connection required.
4.
If applicable, connect the switched mains line to the Sensor input.
5.
Enter the sensor and/or switch cable using the smaller two cable glands.
6.
Connect the wires to the correct I/O terminals, see section 5 for details.
7.
Mount the wiring compartment cover.
8.
Unused cable glands can be closed using a blind plug.
4.
Quick test
Testing power supply and testing correct operation of connected sensor and/or switch.
1.
Switch on the mains power
2.
The green led (mounted internally) must light up
3.
Trigger the sensor, the green led must flash three times
4.
Operate the switch, the green led must flash three times.
5.
If applicable, operate the mains switch, the green led must flash three times.
5.
Compatible sensors and switches
Overview of compatible sensors and switches and their connections
For possible sensors see Luxon Portal: https://portal.nedap-luxon.com.
Connection → Signal wire
24V Supply
wire
0V wire
Device ↓
Nedap motion
sensor
C1
---
0V
Commercial
24V motion
sensor
C1
C2
0V
Light sensor
C1
C2
0V
Switch, low
voltage
C1
C2
0V
Switch, mains
voltage
Sensor (ac sensor
input, reference to
mains N, max. 347Vac)
--
--
In case a second low voltage sensor or switch shall be connected, use C3 and C4 terminals.
Report which sensor is connected to which I/O port, this information is required during commissioning.