1.

 

Open the wiring compartment after loosening the two screws on the front. 

2.

 

Enter the mains cable through the left wire gland. 

3.

 

Connect L and N wire to corresponding terminals, no earth connection required. 

4.

 

If applicable, connect the switched mains line to the Sensor input. 

5.

 

Enter the sensor and/or switch cable using the smaller two cable glands. 

6.

 

Connect the wires to the correct I/O terminals, see section 5 for details.  

7.

 

Mount the wiring compartment cover. 

8.

 

Unused cable glands can be closed using a blind plug. 

 

 
4.  

Quick test 

 

   

Testing power supply and testing correct operation of connected sensor and/or switch. 

 

 

1.

 

Switch on the mains power 

2.

 

The green led (mounted internally) must light up 

3.

 

Trigger the sensor, the green led must flash three times 

4.

 

Operate the switch, the green led must flash three times. 

5.

 

If applicable, operate the mains switch, the green led must flash three times. 

 
 

5.  

Compatible sensors and switches 

 

   

 

Overview of compatible sensors and switches and their connections

 

For possible sensors see Luxon Portal: https://portal.nedap-luxon.com. 

 

 

 

 Connection →  Signal wire 

24V Supply 

wire 

0V wire 

Device ↓ 

 

 

 

Nedap motion 

sensor 

C1  

--- 

0V 

Commercial 

24V motion 

sensor 

C1  

C2  

0V 

Light sensor 

C1  

 

C2  

0V 

Switch, low 

voltage 

C1  

C2  

0V 

Switch, mains 

voltage 

Sensor (ac sensor 

input, reference to 

mains N, max. 347Vac) 

-- 

-- 

 

 

In case a second low voltage sensor or switch shall be connected, use C3 and C4 terminals. 

Report which sensor is connected to which I/O port, this information is required during commissioning. 

 