background image

 

NEC Corporation 

Revision 2.1, October 2011 

6

 

Unit Configuration 

1  Enclosure 

Product Name / Description 

Part Number 

Consolidated PSU 

1U height enclosure 
Including 
2 x 650 Watt 80 PLUS® Gold certified hot plug PSU 

N8142-36F 

2  Power Supply Module 

Available bays: 2 

Product Name / Description 

Part Number 

Power Supply Module 

650 Watt 80 PLUS® Gold certified hot plug PSU 

N8181-76F

 

Maximum Installable Servers 

See the table below for maximum installable server in accordance with number of power supply modules. 

Please consult our sales representative if other estimation is needed. 

E110b-M 

Server Configuration 

Number of Power 
Supply Modules 

Number of 
Installable Server 

Remark 

1 GB memory, no-HDD 

20 

508 Watt total 

 

40 

985 Watt total 

 

80 

1,938 Watt total 

2 GB memory, no-HDD 

20 

567 Watt total 

 

40 

1,104 Watt total 

 

74 

2,041 Watt total 

1 GB memory, 1 x HDD 

20 

597 Watt total 

 

40 

1,163 Watt total 

 

70 

2,031 Watt total 

2 GB memory, 1 x HDD 

20 

657 Watt total 

 

40 

1,282 Watt total 

 

63 

2,050 Watt total 

1 GB memory, 1 x SSD 

20 

508 Watt total 

 

40 

985 Watt total 

 

80 

1,938 Watt total 

2 GB memory, 1 x SSD 

20 

567 Watt total 

 

40 

1,104 Watt total 

 

74 

2,041 Watt total 

Содержание Consolidated Power Supply Unit

Страница 1: ...ration Guide Introduction This document contains product and configuration information that will enable you to configure your system The guide will ensure fast and proper configuration of your unit October 2011 Revision 2 1 NEC Corporation ...

Страница 2: ...CHNICAL SPECIFICATION 3 Key Features 3 Specification 3 EXTERNAL VIEWS 4 Front and Rear Views 4 Dimensions mm 5 CONFIGURATION DIAGRAM 5 UNIT CONFIGURATION 6 1 Enclosure 6 2 Power Supply Module 6 3 DC Power Cable 7 REFERENCES 8 Unit Management 8 Copyright Notice and Liability Disclaimer 9 REVISION HISTORY 10 ...

Страница 3: ...Module Standard 2 Maximum 4 Redundant PSU Supported 1 hot plug Type 650 Watt 80 PLUS Gold certified hot plug PSU 100 240 VAC 10 50 60 Hz 3 Hz Output DC Power Connector 4 x Propriety 12VDC Connector Max Output 1 700 Watt 2 Power Consumption Operating 2 091 VA 2 063 Watt Dimensions W x D x H 444 0 x 671 x 43 5 mm 17 5 x 26 4 x 1 7 in 1U Weight Minimum Maximum 13 kg 15 kg 28 66 lbs 33 07 lbs Temperat...

Страница 4: ...C UID LED I USB Connectors D UID LED Button J VGA Connector E System Status LED K Pull out Tab F Maintenance LED Button Rear View Legend A Power Supply Bays F UID LED B Power Supply Module G AC Inlet C DC Output LED H DC Outlet D DC Output Button I Pull out Tab E UID LED Button J Management LAN Connector K H A B C D E F I J G A G B B D G H J I E F C D C D C D C ...

Страница 5: ...ber 2011 5 Dimensions mm Configuration Diagram Legend Standard components 444 0 465 6 671 0 718 0 43 5 CHASSIS FRONT CHASSIS REAR Power Supply Bay 1 Power Supply Module Power Supply Module Power Supply Bay 2 DC out DC out DC out DC out ...

Страница 6: ...er supply modules Please consult our sales representative if other estimation is needed E110b M Server Configuration Number of Power Supply Modules Number of Installable Server Remark 1 GB memory no HDD 2 20 508 Watt total 3 40 985 Watt total 4 80 1 938 Watt total 2 GB memory no HDD 2 20 567 Watt total 3 40 1 104 Watt total 4 74 2 041 Watt total 1 GB memory 1 x HDD 2 20 597 Watt total 3 40 1 163 W...

Страница 7: ... Watt total 4 7 1 918 Watt total 8 2 032 Watt total Up to 4x HDD can be installed Xeon L5640 2 2 788 Watt total 3 4 1 421 Watt total 4 6 2 048 Watt total 3 DC Power Cable Available DC outlet ports 4 Product Name Description Part Number DC Power Cable Y splitter 80cm 1 x DC output to 2 x DC input NOTE The maximum DC output per 1 DC connector cannot exceed 840 Watt K410 213 1A ...

Страница 8: ...itoring BIOS POST stall monitoring Alerting HW error and Boot error by SNMP E Mail Remote console POST BIOS setup DOS utility via LAN Boot screen Remote control via LAN Remote reset power supply management controller power on off System Management Command Line Protocol DMTF compliant Remote control via Web browser without dedicated app Remote batch Scheduling without UPS Others Set automatic IP ad...

Страница 9: ...The information contained herein is subject to change without notice All other products brands or trade names used in this document are trademarks or registered trademarks of their respective holders NEC shall not be liable for technical or editorial errors or omissions contained herein ...

Страница 10: ...tory Revision Date Description 2 1 October 18th 2011 Other Correct incorrect information in Specification 3 DC Power Cable and References 2 0 April 8th 2011 Other Added section of maximum installable servers for E120b 1 1 0 September 6th 2010 Initial release ...

Отзывы: