7. WIRING AND FUSES
In order to properly dimension wiring and fuses, an
analysis of distances and loads must be carried out. It is
not possible to provide a unique figure valid for every
installation, the following examples are purely
indicative.
10
MAXIMUM
ESTIMATED
CONSUMPTION
MAXIMUM CABLE SECTION
FUSE
Length
<=2m
Length
da 2m a 4m
Length
>4m
20 A
(refrigerator,
lights, water
pump)
4 mm
2
6 mm
2
10 mm
2
40 A
130 A (inverter
with coffee
machine,
hairdryer)
25 mm
2
35 mm
2
50 mm
2
150 A
200 A (inverter
air conditioner)
35 mm
2
50 mm
2
70 mm
2
200 A