A E - 1 5 0 s y s t e m – U s e r M a n u a l
6
Overview
General overview
The AE-150 is designed to localize partial discharge in power transformers by
correlating data from its acoustic and high frequency sensors. The AE-150 has
many acquisition modes, each used for either detecting, locating or monitoring
partial discharge activity in an oil-filled power transformer.
The AE-150 main unit is mounted on the transformer tank using its powerful
magnets that will hold the four acoustic sensors firmly against the tank wall.
Partial discharge activity is measured by all four acoustic sensors and by the AE-
150 PD channel, through an HFCT clamp, UHF antenna or other type of electric
coupling device.
Acquired signals are correlated with power line Phase using the wireless AC-
Sync module or from the output of a coupler.
Acquired data is sent to Mirador Tx software where all advanced positioning and
monitoring functions are implemented. This software also allows easy data
manipulation and reporting.