background image

Troubleshooting

48

NCR 4072 UPS Site Preparation, Installation, and Operation Manual

S

05147374 Rev C

Uncontrolled Copy

NCR Limited Warranty

This warranty applies to uninterruptible power system (UPS) products you purchase from NCR

Corporation (“NCR”) and use in the United States, unless you have another applicable written agreement

with NCR. You indicate your acceptance of this NCR Limited Warranty by your initial use of your NCR

products. Any software warranties are contained in the “break seal” license agreement shipped with the

software or any other applicable written agreement you may have with NCR.

What Is Covered

The failure of any NCR UPS to operate in accordance with its specifications during the period of this

warranty.

What We Will Do

If your NCR product becomes defective within 3 years of the date of purchase, we will repair it or, at our

option, replace it at no charge to you. You may call the number listed below for dispatch of an NCR

service representative for on-site repair or replacement. All warranty service will be subject to NCR’s

standard policies.
If we repair your NCR product, we may use new or reconditioned parts. If we choose to replace your NCR

product, we may replace it with a new or reconditioned one of the same or similar design. The repair or

replacement will be warranted for either (a) 90 days or (b) the remainder of the original warranty period,

whichever is longer.

Limitations

IF YOU ARE A CONSUMER UNDER APPLICABLE LAW, ALL EXPRESS AND IMPLIED WARRANTIES,

INCLUDING THOSE OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY (AN

UNWRITTEN WARRANTY THAT THE PRODUCT IS FIT FOR ORIGINAL USE) ARE LIMITED TO ONE

YEAR FROM THE DATE YOU PURCHASED YOUR NCR PRODUCT. IF YOU ARE NOT A CONSUMER,

THERE ARE NO IMPLIED WARRANTIES, INCLUDING THOSE OF FITNESS FOR A PARTICULAR

PURPOSE AND MERCHANTABILITY. WE WILL NOT PAY FOR LOSS OF TIME, INCONVENIENCE,

LOSS OF DATA, LOSS OF USE OF YOUR NCR PRODUCT, OR PROPERTY DAMAGE CAUSED BY YOUR

NCR PRODUCT OR ITS FAILURE TO WORK, OR ANY OTHER DIRECT, INCIDENTAL, OR

CONSEQUENTIAL DAMAGES.
Some states do not allow limitations on how long an implied warranty lasts, or the exclusion or limitation

of incidental or consequential damages, so those aspects of the above limitations or exclusions may not

apply to you.

What We Ask You To Do

To get warranty service for your NCR product, you must provide proof of the date of purchase. Call us

toll free at the number below to report problems or for the address of an authorized service location. If

you ship your NCR product to the authorized service location, you must prepay all shipping costs. We

suggest you retain your original packing material in the event you need to ship your NCR product. When

sending your NCR product to a service location, include you name, address, phone number, proof of date

of purchase, and a description of the operating problem. After repairing or replacing your NCR product,

we will ship it to your business or home (if you are a consumer) in the United States at no cost to you.

Содержание 4072

Страница 1: ...NCR 4072 500 1400 VA Uninterruptible Power Systems UPS Site Preparation Installation and Operation Manual...

Страница 2: ...be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase...

Страница 3: ...rective on equipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC 89 336 EEC Council Directive relating to electromagnetic compatibility 92 31 EEC Amending Dir...

Страница 4: ...ur operator s manual for additional information such as important operating and maintenance instructions SAFETY EARTHING TERMINAL Indicates the primary safety ground LOAD ON OFF Press the button with...

Страница 5: ...Rear Panels 22 4 Operation 27 Turning the UPS On 27 Starting the UPS on Battery 27 Turning the UPS Off 27 Standby Mode 28 UPS Front Panel 28 Initiating the Self Test 28 5 Additional UPS Features 29 V...

Страница 6: ...ration Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy 7 Specifications 39 8 Troubleshooting 43 Audible Alarms and UPS Conditions 43 Silencing an Audible Alarm 44 Site Wiring Faul...

Страница 7: ...when you least expect it and power quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardware causing hours of lost produ...

Страница 8: ...sures consistent voltage to your load by correcting voltage fluctuations Hot swappable batteries simplify maintenance by allowing you to replace batteries safely without powering down the critical loa...

Страница 9: ...ted to an AC supply For 220 240V models the output receptacles may remain electrically live If the input power source in your application is wired line to neutral as in most European applications the...

Страница 10: ...r other metal objects 2 Use tools with insulated handles 3 Do not lay tools or metal parts on top of batteries 4 Disconnect charging source prior to connecting or disconnecting battery terminals Prope...

Страница 11: ...rolleret indend rsmilj frit for ledende forureningsstoffer for at formindske risikoen for brand og elektrisk st d Rumtemperaturen m ikke overstige 40 C UPS en b r ikke betjenes n r vand eller h j fugt...

Страница 12: ...e kans op brand of elektrische schok te verminderen dient deze UPS in een gebouw met temperatuur en vochtigheidregeling te worden ge nstalleerd waar geen geleidende verontreinigingen aanwezig zijn De...

Страница 13: ...palon ja s hk iskun vaaraa asenna t m UPS sis tiloihin joissa l mp tila ja kosteus on s dett viss ja joissa ei ole virtaa johtavia ep puhtauksia Ymp rist n l mp tila ei saa ylitt 40 C l k yt l hell ve...

Страница 14: ...ler l onduleur uniquement l int rieur dans un lieu d pourvu de mat riaux conducteurs o la temp rature et l humidit ambiantes sont contr l es La temp rature ambiante ne doit pas d passer 40 C Ne pas ut...

Страница 15: ...llierter Temperatur und Luftfeuchtigkeit installieren in denen keine leitenden Schmutzstoffen vorhanden sind Die Umgebungstemperatur darf 40 C nicht bersteigen Die USV nicht in der N he von Wasser ode...

Страница 16: ...Safety Warnings 10 NCR 4072 UPS Site Preparation Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy UPS UPS UPS UPS AC UPS UPS UPS UPS 40 C UPS 95 UPS 1 5 mA...

Страница 17: ...disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuit e dell apparecchiatura ad esso collegata Per ridurre il rischio di incendio o di scossa elettrica installare il gru...

Страница 18: ...som er forbundet med den For redusere fare for brann eller elektriske st t b r denne UPS en installeres i et innend rs milj med kontrollert temperatur og luftfuktighet som er fritt for ledende foruren...

Страница 19: ...uzir o risco de inc ndios ou choques el tricos instale a UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condut veis A temperatura ambiente n o deve exceder 40...

Страница 20: ...Safety Warnings 14 NCR 4072 UPS Site Preparation Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy 40 95 1 5...

Страница 21: ...dio o de choque el ctrico instale este SIE en un lugar cubierto con temperatura y humedad controladas libre de contaminantes conductores La temperatura ambiente no debe exceder los 40 C No trabaje cer...

Страница 22: ...en Minska risken f r brand eller elektriska st tar genom att installera denna UPS enhet inomhus d r temperatur och luftfuktighet r kontrollerade och d r inga ledande f roreningar f rekommer Omgivande...

Страница 23: ...rials for the carrier or place of purchase and file a claim for shipping damage If you discover damage after acceptance file a claim for concealed damage To file a claim for shipping damage or conceal...

Страница 24: ...ernal Battery Connection Use the following procedure to ensure proper battery operation before installing the UPS 1 Verify that the UPS is off and unplugged 2 Remove the UPS front panel Figure 2 Remov...

Страница 25: ...al battery connector Figure 4 Removing the Protective Label 5 Connect the red wire to the battery connector NOTE A small amount of arcing may occur when connecting the batteries This is normal and doe...

Страница 26: ...llowing steps explain how to install the UPS Figure 8 shows a typical installation only See UPS Rear Panels on page 22 for the rear panel of each model 1 If you are installing power management softwar...

Страница 27: ...s or 10A for 230V models 4 Plug the equipment to be protected into the UPS output receptacles NOTE DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of th...

Страница 28: ...rt Four 5 15 Receptacles 6 ft Power Cord with 5 15 Plug DIP Switches Network Transient Protector Site Wiring Fault Indicator USB Port Input Overcurrent Protector Figure 9 500 VA 120V Rear Panel Four 5...

Страница 29: ...es 6 ft Power Cord with 5 15 Plug Fan Communication Port DIP Switches Site Wiring Fault Indicator USB Port Input Overcurrent Protector Figure 11 1000 VA 120V Rear Panel Six 5 15 Receptacles 6 ft Power...

Страница 30: ...munication Port Four 10A IEC 320 Receptacles DIP Switches Network Transient Protector 10A IEC 320 Input Connector USB Port Figure 13 500 VA 230V Rear Panel Four 10A IEC 320 Receptacles DIP Switches Ne...

Страница 31: ...ptacles Four 10A IEC 320 Receptacles 10A IEC 320 Input Connector Fan DIP Switches Network Transient Protector Communication Port USB Port Figure 15 1000 VA 230V Rear Panel Six 10A IEC 320 Receptacles...

Страница 32: ...Installation 26 NCR 4072 UPS Site Preparation Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy...

Страница 33: ...test and enters Normal mode The indicator illuminates indicating that power is available from the UPS output receptacles Starting the UPS on Battery NOTE The UPS does not auto detect the input freque...

Страница 34: ...l indicates the UPS status and also identifies potential power problems Figure 17 shows the UPS front panel indicators and controls On Off Button Test Alarm Reset Button Power On Indicator Green On Ba...

Страница 35: ...rear panel of each unit see Figure 18 are used to configure the output voltage and input voltage range 1 The UPS must be completely shutdown To turn off the UPS press and hold the button for two seco...

Страница 36: ...V 216V 254V ON ON Default position Communication Options The UPS is equipped with a USB and a DB 9 communication port Either the USB port or the DB 9 communication port may be used to monitor the UPS...

Страница 37: ...nitiates the saving of all data and an orderly shutdown of the equipment The cable pins are identified in Figure 20 and the pin functions are described in Table 2 3 8 7 9 1 6 2 4 5 UPS Rear Panel Figu...

Страница 38: ...ector that provides protection for modems fax machines or other telecommunications equipment As with most modem equipment it is not advisable to use this jack in digital PBX Private Branch Exchange en...

Страница 39: ...ient temperature of 25 C 77 F NOTE If the UPS requires any type of transportation in the future disconnect the UPS internal battery connector using the steps in UPS Internal Battery Connection on page...

Страница 40: ...ing batteries W A R N I N G Batteries can present a risk of electrical shock or burn from high short circuit current The following precautions should be observed 1 Remove watches rings or other metal...

Страница 41: ...Operation Manual S 05147374 Rev C Uncontrolled Copy 2 Slide up and remove the metal battery cover 1400 VA 500 1000 VA 3 500 VA models Disconnect the red battery cable and then disconnect the black bat...

Страница 42: ...ttery cable and then pull the battery out onto a flat stable surface Disconnect the black battery cable to the UPS as shown 750 1000 VA 5 1400 VA models Disconnect the red battery cable and then pull...

Страница 43: ...tteries to charge for 6 to 24 hours before testing Press and hold the button for three seconds to initiate a self test The 15 second test automatically distributes the load to the batteries and tests...

Страница 44: ...attery or batteries in a fire Batteries may explode Proper disposal of batteries is required Refer to your local codes for disposal requirements Do not open or mutilate the battery or batteries Releas...

Страница 45: ...Dimensions WxHxD 500 VA 15 0 x 19 3 x 27 0 cm 5 9 x 7 6 x 10 6 750 1000 VA 15 0 x 19 3 x 33 5 cm 5 9 x 7 6 x 13 2 1400 VA 15 0 x 19 3 x 39 0 cm 5 9 x 7 6 x 15 4 UPS Weights 500 VA 7 8 kg 17 2 lb 750 V...

Страница 46: ...utput Receptacles 500 750 VA 4 5 15 1000 1400 VA 6 5 15 500 750 VA 4 10A IEC 320 1000 1400 VA 6 10A IEC 320 Table 6 Environmental and Safety 120V Models 230V Models Operating Temperature Up to 1 500 m...

Страница 47: ...ree valve regulated lead acid Charging Advanced charging for faster recovery approximately 3 hours to 90 usable capacity at nominal line and no supplementary power supply load Monitoring Advanced moni...

Страница 48: ...Specifications 42 NCR 4072 UPS Site Preparation Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy...

Страница 49: ...lt on 120V models Service and support Audible Alarms and UPS Conditions The UPS has an audible alarm feature to alert you of potential power problems Use Table 9 to determine and resolve the UPS alarm...

Страница 50: ...ession Table 9 Troubleshooting Alarm or Condition Possible Cause Action The indicator is not on the UPS does not start The power cord is not connected correctly Check the power cord connections the UP...

Страница 51: ...rected or the battery is completely discharged If the condition persists the input voltage in your area may differ from the UPS nominal Change the UPS input voltage to match your local voltage see Vol...

Страница 52: ...ork and turn off your equipment Turn off the UPS Contact Customer Service 3 beeps every 10 seconds Failed attempt to start the UPS on battery Plug the UPS into a power outlet for 24 hours to charge th...

Страница 53: ...blem Customer return address and contact information If repair is required you will be given a Returned Material Authorization RMA Number This number must appear on the outside of the package and on t...

Страница 54: ...imitations IF YOU ARE A CONSUMER UNDER APPLICABLE LAW ALL EXPRESS AND IMPLIED WARRANTIES INCLUDING THOSE OF FITNESS FOR A PARTICULAR PURPOSE AND MERCHANTABILITY AN UNWRITTEN WARRANTY THAT THE PRODUCT...

Страница 55: ...sign The repair or replacement will be warranted for 90 days or the remainder of the original warranty period whichever is longer This limited warranty is the only one we give on your NCR product and...

Страница 56: ...Troubleshooting 50 NCR 4072 UPS Site Preparation Installation and Operation Manual S 05147374 Rev C Uncontrolled Copy...

Отзывы: