Testing

1. Notes:

• 

Installation MUST be complete prior to testing.

• 

System MUST be tested prior to operation.

2. Leakage Test

• 

Use standard A/C practices to properly check refrigeration tubes and connections for any 

leaks prior to system start up.

3. Pressure Testing

• 

Remove bonnet (cover) of gas valve on outdoor unit.

 

Charge system with Nitrogen to 100 PSI and check for 

leaks. Evacuate Nitrogen.

• 

Connect the gas valves of a vacuum guage, vacuum 

pump, and outdoor unit. (see diagram)

• 

Start the vacuum pump and allow to run for at least 30 

minutes at a level of 500 microns or less.

• 

Shut off the vacuum and continue to monitor vacuum 

guage for another 15 minutes. The pressure should not 
rise above 800 microns.

• 

If a vacumm of 500 microns cannot be obtained, or if it 

rises above 800 microns during the 15-minute monitoring 
period, pressurize the system with nitrogen and look for 
leaks. Repair any leaks that are found and repeat the vacuum testing.

• 

Close the valves to the vacuum pump and guage and disconnect from the outdoor unit.

• 

Tighten bonnet (cover) of gas valve and open gas and liquid valves completely.

4. System Testing

• 

Before testing the system, ensure that cut-off valves of the connection pipes are opened 

and that all debris (such as packing scraps, thrums, etc.) are cleared from the unit.

• 

Switch on power to the system and press the “ON/OFF” button on the remote control to 

activate the indoor unit.

• 

Press “MODE” button repeatedly, taking a moment on each setting to ensure that system 

functions in all modes. (Note: HEAT mode will only function on 
heat pump models.)

• 

If the remote control is lost, emergency run operation can be 

initiated by pressing the the button in the upper right corner of 
the indoor unit under the cover panel. (see diagram)

5. Installation Verification

• 

Have both units been securely and firmly installed?

• 

Are all piping connections secure?

• 

Have the refrigeration lines been sufficiently insulated?

• 

Have you verified the length of the connection pipes and the refrigerant capacity?

• 

Have you conducted all leakage and system tests?

• 

Does the unit drain properly?

• 

Are all electrical connections in compliance with local standards?

• 

Has the unit been properly grounded?

• 

Is the power cord specified?

• 

Are all air inlets and outlets free from obstruction?

Vacuum gauge

Bonnet

Liquid pipe

Gas pipe

Vacuum pump

Emergency 

button

10

Содержание S115A-10K10

Страница 1: ...allation Instructions Mini Split Air Conditioning or Heat Pump Systems Air Conditioning S115A 10K10 S115A 13K10 S240A 13K11 Heat Pump S115HP 10K10 S115HP 13K10 S240HP 13K11 950 0004 Rev 7 28 October 2...

Страница 2: ...Contents Specifications 1 Unit Parts Features 2 Installation Dimension Diagram 3 Safety Warnings 4 Select Installation Locations 5 Indoor Unit Installation 7 Outdoor Unit Installation 8 Testing 10 War...

Страница 3: ...40A 13K11 Indoor replacement S240A 13K11 I Outdoor replacement S240A 13K11 O 12 500 BTU 11 Seer Heat Pump S115HP 10K10 9 500 BTU 10 5 Seer Indoor replacement S115HP 10K10 I Outdoor replacement S115HP...

Страница 4: ...HR Air in Panel Air filter Indoor Unit Outdoor Unit Air out Louver Wiring cover Cover plate of electric box Remote control Drain hose Connecting pipe Cooling indicator Heating indicator On Off indicat...

Страница 5: ...in deep 21 3 in high Distance to ceiling should be 6 inches or more Distance to wall should be 6 inches or more Distance to floor should be 80 inches or more Distance to wall should be 6 inches or mor...

Страница 6: ...Electrical installation must be done by a qualified technician according to instruction manual and in accordance with local electrical standards Certified power supply conductors must be used INSTALL...

Страница 7: ...uch as televi sions radios etc Keep unit and remote out of direct sunlight and or flourscent lighting and away from any excessive heat source steam or flammable materials Outdoor Unit Allow sufficient...

Страница 8: ...se extension is included with unit for use if attached drainage line is not long enough for your application Please note that the extension can be installed after existing drainage pipe is fed through...

Страница 9: ...Wire Table para 4 for wire sizes 5 L N G 4 5 6 way terminal board Outdoor Unit 2 3 2 3 L N G N 1 N 1 3 way terminal board Indoor Unit Power Supply Connections 115 VAC Air Conditioner Wiring See Wire T...

Страница 10: ...tion pipes to the proper pipes of the bundled lines coming through the wall from the indoor unit Tighten the flare nut of the connection pipes using a spanner and torque wrench see diagram Note Do not...

Страница 11: ...tdoor Unit Remove valve caps on outdoor unit Use standard A C practices to attach the refrigeration lines bundled in Step 2 to the outdoor unit Tighten the flare nut of the connection pipes using a sp...

Страница 12: ...n gas and liquid valves completely 4 System Testing Before testing the system ensure that cut off valves of the connection pipes are opened and that all debris such as packing scraps thrums etc are cl...

Страница 13: ...place the unit free of charge within a reasonable time after the unit is returned This warranty DOES NOT cover Damage accidental or otherwise to the unit while in possession of the consumer that is no...

Страница 14: ...Indoor Unit Catalog Number S115A 10K10 O S115A 10K10 I N A 1070 1000 930 0 065HP 0 9A 0 008HP 0 18A 55 32 35 38 Hitachi SG453EA1NC N A 40A N A 8 8A N A 313 Psig 313 Psig 144 Psig 144 Psig N A MP24GA 3...

Страница 15: ...Number S240A 13K11 O S240A 13K11 I N A 1100 1200 1350 0 064HP 0 56 Amps 0 03HP 0 16 Amps 57 39 41 44 PANISONIC 2P19S236A1J N A 33 A N A 5 7 A N A 384 Psig 384 Psig 144Psig 144 Psig N A MP24GA 33 x 12...

Страница 16: ...og Number S115A 13K10 O S115A 13K10 I 1100 1200 1350 0 064 HP 0 9 Amps 0 29 HP 0 2 Amps 57 39 41 44 Panasonic 2P19S126B1F N A 62 A N A 10 6 A N A 313 Psig 313 Psig 144 Psig 144 Psig N A MP24GA 33 x 12...

Отзывы: