CV135-CV146 -
Custom Startup Table
(Note: this if for the technically inclined)
The custom startup table provides a programmable method to pulse the track power on and
off several times before the AR10 tests for over current. You can program the on and off
times in increments of 1mS. Generally you will not use this table with most boosters but it
may be useful with a booster that has weak startup capability.
An "off" time of 0 indicates the last entry of table. With the factory default of CV144 = 0
indicates the AR10 will not try to use the 6th "on" time.
If CV135 = 0 the table is disabled.
CV135 default = 0 Custom startup table initial "on" time
CV136 default = 4 Custom startup table initial "off" time
CV137 default = 8 Custom startup table 2nd "on" time
CV138 default = 4 Custom startup table 2nd "off" time
CV139 default = 16 Custom startup table 3rd "on" time
CV140 default = 4 Custom startup table 3rd "off" time
CV141 default = 32 Custom startup table 4th "on" time
CV142 default = 4 Custom startup table 4th "off" time
CV143 default = 80 Custom startup table 5th "on" time
CV144 default = 0 Custom startup table 5th "off" time
CV145 default = 0 Custom startup table 6th "on" time
CV146 default = 0 Custom startup table 6th "off" time
CV147 Factory reset
This will reset the AR10 to its original factory settings
Set CV147 = 85 to do a factory reset of the AR10 to the following values.
CV129 default = 1 16mS allowable short circuit
CV130 default = 128 2 seconds power off time
CV131 default = 0 Manual reset off
CV135 default = 0 Custom startup table disabled
CV136 default = 4
CV137 default = 8
CV138 default = 4
CV139 default = 16
CV140 default = 4
CV141 default = 32
CV142 default = 4
CV143 default = 80
CV144 default = 0
CV145 default = 0
CV146 default = 0
CV148 default = 204 (8 Amps)
**Last revised: 3 May 2020
Page 6