background image

SETTINGS: SETTINGS PROCEDURE 

1. Hold down the SET key to enter the settings menu. If password protection is active, enter the correct password. The group of 
settings displays on the display.  
2. Select the group by using the up and down keys and press the SET key to view the selected group. 
3. Using the up and down keys select the parameter you wish to adjust and press the SET key to view the selected parameter. The 
adjustable parameter blinks. 
4. With the up and down keys, adjust the parameter value. Press SET to enter the new value and move to the next parameter. 
5. Exiting the settings menu: hold down the SET key to move back one level.   
    The anemometer also returns to the main screen after 2 minutes of inactivity. 

 
SETTINGS: SETTINGS LIST 

Max Alarm     

select to set Max Alarm parameters 

Pre Alarm 2 

select to set Pre Alarm 2 parameters 

Pre Alarm 1 

select to set Pre Alarm 1 parameters 

No Signal/WD alarm 

select to set No Signal or Wind Direction alarm parameters 

General 

select to set general parameters 

Wi-Fi* 

select to set Wi-Fi parameters 
* applicable only for W410XW/D and W410XL/D models 

SD Logging* 

select to set SD Logging parameters 
* applicable only for W410XL/D model 

 

Settings: Max Alarm (Relay 1, RED ALARM LIGHT, continuous sound)    

 

Factory preset: 

Setting range: 

Description: 

Wind Speed:    

72 km/h 

1 - 50 m/s 

Max Alarm limit  

ON Delay: 

0 s 

0 - 600 s 

Minimum time of excess wind speed to activate the Max alarm 

OFF Delay: 

0 min 

0 - 60 min 

Alarm switch OFF delay after wind speed drops below preset level 

Relay: 

Normal 

Normal/Inverted 

Inverted operation of relay 

 
Settings: Pre Alarm 2 (Relay 2, YELOW ALARM LIGHT, interrupted sound)    

 

Factory preset: 

Setting range: 

Description: 

Wind Speed:    

52 km/h 

1 - 50 m/s 

Pre Alarm 2 limit  

ON Delay: 

0 s 

0 - 600 s 

Minimum time of exceed Wind speed to activate the Pre Alarm 2 

OFF Delay: 

0 min 

0 - 60 min 

Alarm switch OFF delay after wind speed drop below preset level 

Relay: 

Normal 

Normal/Inverted 

Inverted operation of relay 

 
Settings: Pre Alarm 1 (Relay 3) 

 

Factory preset: 

Setting range: 

Description: 

Wind Speed:    

42 km/h 

1 - 50 m/s 

Pre Alarm 1 limit 

ON Delay: 

0 s 

0 - 600 s 

Minimum time of exceed Wind speed to activate the Pre Alarm 1 

OFF Delay: 

0 min 

0 - 60 min 

Alarm switch OFF delay after wind speed drop below preset level 

Relay: 

Normal 

Normal/Inverted 

Inverted operation of relay 

 
Settings: No Signal / Wind Direction Alarm (Relay 4) 

 

Factory preset: 

Setting range: 

Description: 

Alarm:    

No Signal 

No Signal/Direction 

Type of Alarm: No signal alarm or wind direction alarm  

Relay: 

Normal 

Normal/Inverted 

Inverted operation of relay 

Zone1: 

From 315

0  

to 45

0     

0

- 359

0

 

Zone of wind direction alarm ON.  *In clockwise direction. 

Zone2: 

From 135

0  

to

 

225

 * 

0

- 359

0

 

Zone of wind direction alarm ON.  *In clockwise direction. 

ON Delay: 

0 s 

0 - 600 s 

Minimum time of wind direction inside the alarm zone to activate the alarm 

OFF Delay: 

0 min 

0 - 60 min 

Alarm switch OFF delay after wind direction leaves the alarm zone 

 
Settings: General  

 

Factory preset: 

Setting range: 

Description: 

Sensor Address:   

Enclosed sensor 

1 - 255   

Set the sensor address of wind sensor 

WS Averaging: 

2 s 

2, 10 or 30 s 

Averaging period for displayed wind speed 

WS units: 

km/h 

m/s, km/h, mph, knot 

Unit for displaying wind speed 

Temperature units: 

0

 

0

C or 

0

Unit for displaying Temperature 

20 mA Output* 

180 km/h 

 10 - 50 m/s 

Wind speed at 20 mA output 
4 mA = 0 km/h 
20 mA =  set wind speed value  
* applicable only for W410XB/D, W410XW/D and W410XL/D models 

Password:  

NO 

NO /  
YES - 0000 to 9999 

Activation of password protection and setting the password 

Sound Alarm: 

ON 

ON/OFF 

Switching sound alarm ON and OFF 

Language: 

English 

English/French 

Language selection  

WS Cal. Factor 

+0,0% 

 

Calibration factor for wind speed (-15,0 ...+15,0% in 0,5% steps) 

WD Cal.: 

0

° 

-180

°

  

… +180° 

Calibration angle for wind direction (-180

° ...+180° in 1° steps) 

Bluetooth* 

ON 

ON/OFF 

Power ON/OFF Bluetooth transmitter  
* applicable only for W410XB/D and W410XL/D models 

 

Settings: Wi-Fi (applicable only for W410XW/D and W410XL/D models) 

 

Factory preset: 

Setting range: 

Description: 

Scan for Wi-Fi:    

 

 

Scan for nearby Wi-Fi 

Wi-Fi:    

 

 

Enter Wi-Fi network manually 

S/N 

 

 

Wi-Fi serial number of display unit 

 

Settings: SD Logging (applicable only for W410XL/D model) 

 

Factory preset: 

Setting range: 

Description: 

Time:  

01:58     

00.00 

– 23.59 

Time setting  - 24 h time format 

Date:  

01/01/2019 

 

Date setting  - day/month/year 

Logging int:  

1 min 

10 s, 1 min, 10 min, 
60 min 

Selectable SD logging interval  

Отзывы: