13
Operating the Boiler
3.4 Resetting the Boiler
If an error message appears during boiler operation,
reset the boiler to resolve the problem. Press the
Back button (
) on the front panel to reset the
boiler.
If resetting the boiler does not solve the problem,
refer to the Troubleshooting section of this manual
or contact Technical Support at 1-800-519-8794.
Item
Description
22. Flow control
valve status
100 - Close state
23. Mixing valve
status
0 - Close state
24. Exhaust Temp
Exhaust temperature (°F)
25. Outdoor Reset
Outdoor reset status (Enable
/ Disable)
26. Outdoor Reset
Curve
Outdoor reset curve load
type (displayed when the
outdoor reset option “25.
Outdoor Reset” is enabled)
1: Finned Tube Baseboard
2: FAN Coil
3: Cast Iron Baseboard
4: Low Mass Radiant
5: High Mass Radiant
6: Radiator
7: Custom (set by installer)
27. Boost Interval
Time
Boost interval set time (min)
28. High Altitude
Sea Level (0 - 2,000 ft)
Level 1 (2,000 - 5,400 ft)
Level 2 (5,400 - 7,700 ft)
Level 3 (7,700 - 10,100 ft)
29. Well pump
Well pump status
OFF - Unused, ON - Used
30. Model
Model type
31. Gas
Fuel type (NG/LPG)
32. Main F/W Ver
Main firmware version
33. Panel F/W Ver
Controller panel firmware
version