  Venting

  

>

  

  Electrical Connections

  

>

  

Vent Termination Options

Horizontal vent termination

Interior view

Intake Air

Exhaust Gas

12" (300 mm) min.

12" (3

00 mm

) min.

Exterior view

Vertical vent termination

Sidewall vent termination

12" min. from any 

obstruction above, 

below, left, or right

12" (300 mm) min.

12" (300 mm) min.

36" (900 mm) min.

12" (300mm) min.*

Concentric Vent Termination

Sidewall installation

Combustion Air

Combustion Air

1" (25mm) min

Maintain 12" min. 

clearance above 

highest anticipated 

snow level or grade.

Vent

Roof installation

Vent

Vent

Combustion Air

Maintain 12" min. 

(18" min. for Canada) 

clearance above 

highest anticipated 

snow level maximum 

of 24" above roof.

Combustion  

Air

Venting Length

4” pipe venting

3” pipe venting

8

1

3

7

2

Maximum Length 150'

Maximum number 

of elbows: 8

3-to-4 inch

6

1

3

4

5

2

Maximum number 

of elbows: 6

Maximum Length 60'

 

·

90˚ elbow = 5 linear feet of venting

 

·

45˚ elbow = 3 linear feet of venting

 

·

90˚ elbow = 5 linear feet of venting

 

·

45˚ elbow = 3 linear feet of venting

Exhaust Vent Piping Materials

 

·

All Navien boilers are Category IV appliances.

 

·

The venting system should be approved for use with Category IV appliances (typically Type BH 

Special Gas Vent approved by UL 1738-S636).

 

·

Venting requirements in the USA and Canada are different (see below).

Navien recommended venting materials

Locale

Recommended Vent Materials

USA

 

·

PVC/CPVC Schedule 40 or 80 (Solid Core)

 

·

Approved Polypropylene (PP)**

 

·

Approved Stainless Steel (SS)***

Canada*

 

·

Type BH Special Gas Vent Class IIA (PVC)

 

·

Type BH Special Gas Vent Class IIB (CPVC)

 

·

Type BH Special Gas Vent Class IIC (Polypropylene/Stainless Steel)

* For installation in Canada, field-supplied plastic vent piping must comply with CAN/CGA B149.1 (latest 

edition) and be certified to the Standard. For Type BH Gas Venting Systems, ULC-S636. Components of this 

listed system must not be interchanged with other vent systems or unlisted pipes or fittings. All plastic 

components and specified primers and glues of the certified vent system must be from a single system 

manufacturer and must not be intermixed with another system manufacturer’s parts.

The supplied vent connector and vent termination are certified as part of the boiler.

** Approved Polypropylene Systems include:

Duravent PolyPro® SW (Rigid)

: 3PPS-xxx (3”) or 4PPS-xxx(4”)

Duravent PolyPro® (Flexible)

: 3PPS-FLEXxx (3”), 3PPS-FAM (3” Rigid-to-Flex Male Adapter)

Centrotherm Innoflue® SW (Rigid)

: ISxx03xx (3”) or ISxx04xx (4”)

Hart & Cooley Polyflue™ SW (Rigid)

: 3PF-xx (3”) or 4PF-xx (4”)

Z-Flex Z-DENS SW (Rigid)

: 2ZDP_(3” or 4")

*** Approved Stainless Steel Systems include:

Duravent FasNSeal® (Rigid)

: FSA-PVC3 or FSA-PVC4 (3” or 4” PVC to FasN Seal Appliance Adapter), 

FSxxxxx03 or FSxxxxx04 (3” or 4”)

Heat Fab Saf-T Vent® EZ Seal

: 9301PVC or 9401PVC (3” or 4” PVC/CPVC Outlet Boiler Adapter),  

93xx or 94xx (3” or 4”)

External LWCO Connection  

(if required by local codes)

Power Connection

NULTI SW

T/S DHW

3.LWCO

2.AC24VL

1.AC24VN

FLOW SW

LP SW

OUT DOOR

DHW TANK

(+)

(-)

SYSTEM SUPPLY

SYSTEM RETURN

W

C

R

W

C

R

W

C

R

W

C

LWCO

LINE

LINE

Neutral

Refer to your local codes to determine if an 

LWCO device is required for your system and 

ensure that the built-in device meets the 

requirements. 

120 V AC 60 Hz 

Min. 2 Amp current with proper 

grounding

 CAUTION

Using abnormally high or low AC 

voltage may cause abnormal operation, 

thereby causing fire which reduces the 

life expectancy of this product.

 CAUTION

Disconnect the power to 

the boiler before installing 

any wire connections on 

the main PCB. 

Safety

DO NOT touch 

the power 

cord with wet 

hands.

DO NOT allow 

the boiler to be 

exposed to 

excessive 

amounts of 

water.

Confirmation of DIP Switch Settings

DIP Switch 1 (6 switch unit)

DIP Switch 2 (8 switch unit)

SW

Function

Setting

1 & 2 Operation 

Status

Normal Operation 1-OFF, 

2-OFF

2Step MAX

1-ON, 

2-OFF

1Step MIN

1-OFF, 

2-ON

1Step MAX

1-ON, 

2-ON

SW

Function

Setting

1

Gas Type

Natural Gas 

Propane Gas

1-OFF 

1-ON

2 & 3 High 

Altitude

0-1,999 ft 

(0-609 m)

2-OFF, 

3-OFF

2,000-5,399 ft 

(610-1,645 m)

2-ON, 

3-OFF

5,400-7,699 ft 

(1,646-2,346 m)

2-OFF, 

3-ON

7,700-10,100 ft 

(2,347-3,078 m)

2-ON, 

3-ON

4

Reserved

-

-

5 & 6 Country

US/Canada

5-OFF, 

6-OFF

7

Space 

Heating 

Thermostat

Used

7-OFF

Unused

7-ON

8

Exhaust 

Temperature 

Control

Used

8-OFF

Unused

8-ON

Note

When PCB DIP switch 2 #8 is set to 

On, ensure that CPVC, polypropylene, 

or stainless steel is used for exhaust 

venting.

 

 