18.    Measure and adjust the gas/air ratio. 

Option 1. Using Combustion Analyzer (recommended) 
a.    Loosen the screw, rotate the plate and remove the gasket to access 

the emissions monitoring port as shown in Figure 7. 

b.    Insert the analyzer into the port (Figure 7). 

Figure 7. Insert the Analyzer 

 

 

 

Table 2. CO

2

 value 

(CO

2

 values must be within 0.5% of the values listed.) 

 

c.  Fully open several hot water fixtures and set the boiler to 

operate at 1-stage MIN mode (refer to page 8).     
Measure the CO

2

 value at low fire. If the CO

2

 value is not 

within 0.5% of the value listed in Table 2, the gas valve set 

screw will need to be adjusted. If adjustment is necessary, 

locate the set screw as shown in Figure 8. Using a 5/32 in 

or 4 mm Allen wrench, turn the set screw no more than 

1/4 turn clockwise to raise or counterclockwise to lower 

the CO

2

 value. 

Model 

Fuel 

High fire 

Low fire 

%CO

2

 

%CO

2

 

NCB-180 

NG 

8.9 

9.5 

LP 

10.2 

10.8 

NCB-210 

NG 

8.9 

9.5 

LP 

10.2 

10.8 

NCB-240 

NG 

8.9 

9.5 

LP 

10.2 

10.8 

b.

 

Connect a manometer to the offset pressure port. For dual 
port manometers, use the positive pressure side. 

 

Model 

Kit Part No. 

Gas Type 

Offset 

NCB-180 

NAC-01 

LP 

-0.03"±0.01" 

NAC-100 

NG 

-0.04"±0.01" 

NCB-210 

NAC-02 

LP 

-0.02"±0.01" 

NAC-200 

NG 

-0.04"±0.01" 

NCB-240 

NAC-03 

LP 

-0.02"±0.01" 

NAC-300 

NG 

-0.04"±0.01" 

Table 3. Offset value for low fire 

 

c.

 

Fully open a hot water fixture and set the boiler to 
operate at 1-stage MIN mode (refer to table 2). Measure 

the offset value at low fire and compare it to the values in 

Table 3. If the offset value is out of range, the gas valve set 

screw will need to be adjusted. 

If adjustment is necessary, locate the set screw as shown 

in Figure 10. Using a 5/32”or 4mm Allen wrench, turn the 
set screw no more than 1/4 turn clockwise to raise or 

counterclockwise to lower the offset value. 

 

Figure 10 

  The set screw is located behind the screw-on cover. 

This must be removed first. 

d.

 

At high fire, do not check the offset value and never adjust the gas 

valve. 

 

  DANGER 

Improper gas valve settings can cause severe personal injury, death or 
substantial property damage. 

 

 

Figure 8. Set Screw Location 

 

 

The set screw is located behind the screw-on cover. 
This must be removed first. 

d.    Fully open several hot water fixtures and set the boiler to operate at 

2-stage D. MAX mode (refer to page 8). Measure the CO

2

 value at 

high fire.   

If the CO

2

 values do not match Table 2 at high fire, do not adjust the 

gas valve. Check for the proper Gas Orifice. 

 

  DANGER 

Improper gas valve settings can cause severe personal injury, death or substantial 
property damage. 

 

Option 2. Using Digital Manometer 

a.

 

Open the offset pressure port by loosening the screw two 

turns as shown in Figure 9. 

 

Figure 9. Connect Digital Pressure Monometer 

 

12.

 

  Once the CO

2

 or offset values have been confirmed, apply the 

included conversion stickers to show that the appliance has 

been converted to propane gas. Place these labels adjacent to 

the rating plate as shown in Figure 11. 

 

Figure 11. Proper Placement of Gas Conversion Labels 

  Manifold Gas Pressure ratings can change due to 

updated orifice sizes. Please confirm new 

manifold pressures approved by CSA before 

production of gas conversion labels. 

 

 

Setting the Operation Mode 

1.

 

Using the Front Panel, press and hold the Diagnostics Button or over 5 

seconds until “1.PAR” is displayed. 

2.

 

Press the + (Up) button two to change the display to“3.OPR”. 

3.

 

Press the Information Button once to access the Operation Mode menu. 

4.

 

Press the + (Up) button once to set the boiler to operate at 1-stage MIN 

(“MIN.1”). 

5.

 

To set the boiler to operate at DHW 2-stage MAX, press the + (Up) 

button 4 times or until "D.MX.2" is displayed. 

6.

 

To exit the Operation Mode and return the boiler to normal operation, 

press the Reset button twice. 

 

 