background image

Make Your Job More Enjoyable 

J\

VAC 

3.3 Sensitivity level settings 

Sensitivity level can be set as required b,lthe end user. If it is necessary to change the sensitivity level, 

please press "Sensitivity Adjust Button" ( 'v ). Three sensitivity levels can be circularly adjusted. 

3.4 Setting of Environment Zero function 

Automatic environment zeroing function is started by default. 

Long press button "Environment Zero" ( 

Q) 

(for more than 3seconds) and the beeper gives one "BEEP" 

sound and the auto "Environment Zero" function is cancelled and system enters manual "Environment 

Zero" state. Under the state, short press the button "Environment Zero" ( Q ) and the beeper gives one 

"BEEP" sound and manually zero one time the current environment concentration. Long press the button 

"Environment Zero" ( 

Q) 

(for more than 3seconds) and the beeper gives one "BEEP" sound, the system 

is transferred to auto "Environment Zero" function. 

3.5 Leakage detection and positioning 

Move slowly the probe through the location area where leaks may occur (for a flexible probe, just bend it to 

a desired shape to extend it to the required area). If a leakage is detected, the leak detector alarms. With 

refrigerant concentration increases, the alarming frequency of leak detector speeds up and the number of 

LED leakage indicator lamps increase. While the device alarms, it means that you are close to the leaking 

source.  Re-check  the  neighbored  area  and  make  sure  if  it  alarms  again.  If  the  leaking  source  is 

determined, move slowly from different directions of the non-alarming area towards the leaking source to 

position  accurately  the leaking source. Additionally,  with the help of  "Environment  Zero"  function and 

sensitivity adjustment, accurately position the leaking point (first use high sensitivity to find the leaking 

area, then reduce the sensitivity level and repeat the above procedures to determine the leaking source.). 

Once the leaking source is determined,  make corresponding marks near the leaking source and then 

check the entire refrigerating system till all the leaking points are found. 

&

Note: 

Q)At detecting, there shall be some pressure (2:50 psi) in the system and the operation shall be performed 

in relatively static air condition. If there is wind, leaked refrigerant gas can be quickly diluted or be blown 

away from the leaking source, thus affect the accuracy of detection. Additionally, before detection, use a 

fan to blow off the suspected leaked refrigerant gas in the system in case it may affect the accuracy of 

detection. 

@"Auto Environment Zero" function is started by default. If the leak detector alarms before positioning the 

leaking source, the device will automatically shield the environmental refrigerant concentration. If the 

"Auto Environment Zero" function is off, the "Environment Zero button" 0 ) has to be used to shield the 

environmental refrigerant concentration. 

@ Leaking source usually occurs at the greasy dirt, dust position, node valve or pipe connection positions. 

Detection shall focus on these areas. 

© While detecting, the probe of the leak detector shall be 1/8"-1/4" away from the suspected leaking point 

to prevent greasy oil and others from contaminating the probe and affecting the detection accuracy. The 

probe shall move at a speed of around 1 inch/second. 

04 

Make Your Job More Enjoyable 

J\

VAC 

4. Maintenance

4.1 Proper maintenance can prolong the service time and maintain the performance of the leak detector. 

Keep the protective cover of the sensor clean and make sure there is no water drop, oil, grease, dust or 

other contaminants on the surface of the sensor. Clean the sensor with cotton cloth or dry gas. 

4.2 

The sensor has its working time. Under normal condition, its service time is more than a year. Long­

time working in high-concentration refrigerant environment will rapidly consume the life time of the 

sensor. When the sensor is out of service, replace it in time. 

4.3 

First remove the sensor protective cover; then take out the old sensor; align the pins and insert the new 

sensor along the same position where the old one was taken out. Reinstall the sensor protective cover. 

Refer to the following illustrations. 

Compositions of leak detector head: installation seat, 

sensor, sensor protective cover 

Direction of sensor bump 

Sensor installation seat 

The protective cover 

is removed 

5. Accessory list

Leak detector 

Micro-USB Power cable 

Standard leakage cylinder 

Operation manual 

Outer case 

1pcs 

1pcs 

1pcs 

1pcs 

1pcs 

05 

Отзывы: