Technical parameter 

Model 

N2A4 

Refriaerant Tvoe 

R-22,  R-404A,  R-134a, R-41 0A 

Gauge Diameter 

in 

<1>3-1/8" 

Pressure Range 

psi 

-30 inHg to 800 psi; 
-30 inHg to 500 psi 

Hose 

in 

No 

Standard Length 

ft 

No 

Operation lnstruciton 

1. Pressure testing

1.1  Close both valves. 

N4A4H 
R-22,  R-404A, R-134a, R-41 0A 
<1>3-1/8" 

-30 inHg to 800 psi; 
-30 inHg to 500 psi 

Black  3/8"-3/8" 

Red 

1/4"-1/4" 

Blue  1/4"-1/4" 

Yellow  1/4"-1/4" 

4x5' 

1.2  Connect blue hose to the low side of system, connect red hose to the high 

side of system. 

1.3  Running the system, read the testing pressure indicated on manifold gauges. 
1.4  After testing.turn off the system. Then disconnect the hoses from the system 

and open all valves, make sure not vent refrigerant into the atmosphere. 

1.5  In order to prevent venting the refrigerant into the atmosphere, you can use a 

NAVAC recovery machine to recover any refrigerant remained in the hoses 

or mainfold gauges. 

2. Evacuation of a system

2.1 Connect blue hose to the low side of system, connect red hose to the high 

side of system and connect yellow hose to vacuum pump. 

2.2 Open both valves. 
2.3 Turn on the vacuum pump. 
2.4 Check pressure on low pressure gauge for 3 to 5 minutes, if desired vacuum 

reached, close valves, then turn off the vacuum pump. 

2.5  Observe the pressure on the low-pressure gauge, if the pointer sticks to 

04 

-30 inHG for 3 to 5 minutes, the system evacuation is completed. If not, repeat
the steps from 2.2 to 2.4.

Empowering you to work smarter 

N.AV.AC 

3. Charging of a system after evacuation

3.1  Keep valve closed, disconnect the yellow hose from the vacuum pump and 

connect this hose to a refrigerant container. 

3.2  Open valve on the refrigerant container. 

3.3  Open the manifold valves. The system is now being charged with refrigerant. 

Check the correct quantity of refrigerant with a charging scale (such as a 
NAVAC NRS2i01 wireless scale), and observe the pressure on the gauge. 

If the refrigerant flow is too slow or insufficient the system compressor can 

be turned on to speed up the process. 

3.4  If the correct charging quantity has been reached, close valves. 
3.5  After testing, turn off the system. Then disconnect the hoses from the system 

and open all valves while making sure not to vent refrigerant into the 
atmosphere. 

Maintenance 

1.1  Do not apply excessive force when turning valves. 
1.2  Manifolds are high precision measuring instruments. After use, store manifold 

gauges always in the carrying case. 

1.3  For maintenance and repair of the manifold, contact authorized NAVAC 

distributors. Product warranty would be void if it is disassembled by 
unauthorized individuals. 