VS1 Operations and Maintenance Manual
Routine maintenance
Page 3-8
Issue 3.1 2013-10-01
Inspecting lightning protection systems
You should inspect the lightning protection systems that are connected to your VS1 transmitter, ac
power, RF feedline, antenna and tower periodically to ensure that your site, equipment and personnel
are fully protected.
Interval
Every 6 months.
Parts and tools
Depends on your site, but may include a digital multimeter, ladder, binoculars, and continuity tester.
Procedure
Perform the following steps to test the lightning protection systems:
1. Test the continuity between ground available at your lightning arrestor and ground available
on various pieces of equipment connected to the transmitter. Ensure that there is no
resistance (near 0 ohms, accounting for multimeter test lead resistance).
2. Physically inspect the lightning arrestor to ensure that all connections are tight. Also look for
any sign of scoring or burning (indications of possible damage from earlier lightning strikes).
3. Using binoculars, visually inspect the hardware on the tower. Look for charred, broken or
frayed connections and corrosion.
Содержание VS1
Страница 2: ......
Страница 4: ......
Страница 8: ...VS1 Operations and Maintenance Manual Page viii Issue 3 1 2013 10 01...
Страница 12: ...VS1 Operations and Maintenance Manual Page xii Issue 3 1 2013 10 01...
Страница 24: ...VS1 Operations and Maintenance Manual Description Page 1 6 Issue 3 1 2013 10 01...
Страница 26: ...VS1 Operations and Maintenance Manual Issue 3 1 2013 10 01 Page 1 8...
Страница 30: ......
Страница 32: ......
Страница 34: ......
Страница 36: ......
Страница 204: ...VS1 Operations and Maintenance Manual Operating the transmitter Page 2 176 Issue 3 1 2013 10 01...
Страница 223: ......