NX50 Operations and Maintenance Manual
Operating the transmitter
Page 2-100
Issue 3.3 2016-02-08
Power Thresholds
The
Power Thresholds
page (see
) allows you to set two distinct low forward power
thresholds the transmitter. These thresholds are for monitoring purposes only. The transmitter will
not shut back if these thresholds are crossed, but alarm notifications are generated for each of the
two thresholds (
Low Forward Power Threshold 1
and
Low Forward Power Threshold 2
) on the
Transmitter Status
page.
Figure 2.73: System Settings - Power Thresholds
1. Select
Power Thresholds
from the left side of the
System Settings
page to open a related
window on the right side of the page.
2. Enter the desired low power threshold level for each of the two options, noting the level
represents the percentage of the normal operating setpoint. The default settings for
Low
Forward Power Threshold 1
and
2
are 50% and 25%, respectively.
3. Press
Apply
to activate the change(s) or press
Cancel
to abort.
Содержание NX50
Страница 2: ......
Страница 4: ......
Страница 8: ...NX50 Operations and Maintenance Manual Page viii Issue 3 3 2016 02 08...
Страница 17: ...NX50 Operations and Maintenance Manual Description Issue 3 3 2016 02 08 Page 1 9 Figure 1 4 Shutback Event...
Страница 19: ...NX50 Operations and Maintenance Manual Issue 3 3 2016 02 08 Page 1 11 NX Series Transmitter Block Diagram...
Страница 150: ...NX50 Operations and Maintenance Manual Operating the transmitter Page 2 132 Issue 3 3 2016 02 08...
Страница 156: ...NX50 Operations and Maintenance Manual Routine maintenance Page 3 6 Issue 3 3 2016 02 08...
Страница 162: ...NX50 Operations and Maintenance Manual Non standard maintenance Page 4 6 Issue 3 3 2016 02 08...
Страница 165: ......