SCC-LP Series Lowpass Filter Modules User Guide
4
ni.com
Device Specific Information
Note
For general SCC module installation and signal connection information, and
information about the SC-2350 carrier, refer to the
SCC Quick Start Guide
, available
for download at
ni.com/manuals
.
Installing the Module
Caution
Refer to the
Read Me First: Safety and Radio-Frequency Interference
document
before removing equipment covers or connecting/disconnecting any signal wires.
You can plug the SCC-LP
XX
into any analog input socket on the SC-2345.
It can function as a single-stage module or as the first or the second stage
of a dual-stage signal conditioning configuration. The socket you choose
determines which E Series DAQ device channels receive the SCC-LP
XX
output signals, as explained in the
Connecting the Input Signals
section.
For single-stage conditioning, plug the SCC-LP
XX
into any socket J(
X
+
1),
where
X
is 0 to 7, and connect the input signals to the module as described
in the
Connecting the Input Signals
section.
The SCC-LP
XX
can function as either the first or the second stage of a
dual-stage configuration. Plug the first-stage SCC into any socket J(
X
+9)
and plug the second-stage SCC into socket J(
X
+1), where
X
is 0 to 7.
Connect the input signals to the first-stage SCC. The SC-2345 connects the
output signals of the first-stage SCC to the inputs of the second-stage SCC.
An example of dual-stage conditioning is an SCC-A10 voltage attenuator
module followed by an SCC-LP
XX
.
Sockets J9 to J16 also are available for digital input/output (DIO)
conditioning or control. Refer to the
SC-2345 User Manual
and
SCC Quick
Start Guide
for more information on configuring, connecting, and
installing SCC modules.
Connecting the Input Signals
Note
The signal names have changed. Refer to
ni.com/info
and enter
rdtntg
to
confirm the signal names.
Each screw terminal is labeled by pin number <1..4>. Pins 1 and 2 form
a differential channel routed to E Series DAQ device channel
X
+8, and
pins 3 and 4 form a second differential channel routed to E Series DAQ
device channel
X
, where
X
is 0 to 7 depending on the socket where you plug
in the SCC-LP
XX
.
Содержание SCC-PWR02